background image

Contents

Cert. Version 04.20 · Edition 01.22 · EN · 03251549

EN, FR, ES – www

.docuthek.com

Pressure switches for gas DG..t

1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2 Checking the usage . . . . . . . . . . . . . . . . . . . . . 2
3 Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

4 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

5 Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6 Pressure switches with manual reset  . . . . . . . . 4

7 Tightness test. . . . . . . . . . . . . . . . . . . . . . . . . . 4

8 Maintenance cycles  . . . . . . . . . . . . . . . . . . . . . 4
9 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

10 Technical data  . . . . . . . . . . . . . . . . . . . . . . . . 5
11 Certification  . . . . . . . . . . . . . . . . . . . . . . . . . . 6
12 Logistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
13 Disposal  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1 sAFetY

1.1 Please read and keep in a safe place

 Please read through these instructions care-

fully before installing or operating. Following the installa-
tion, pass the instructions on to the operator. This unit 
must be installed and commissioned in accordance 
with the regulations and standards in force. These 
instructions can also be found at www.docuthek.com. 

1.2 explanation of symbols

 = Action 

 

= Instruction

1.3 Liability

We will not be held liable for damage resulting from 
non-observance of the instructions and non-com-
pliant use.

1.4 safety instructions

Information that is relevant for safety is indicated in the 
instructions as follows:

 DAnGeR

Indicates potentially fatal situations.

 WARnInG

Indicates possible danger to life and limb.

 CAUtIon

Indicates possible material damage.

All interventions may only be carried out by qualified 

gas technicians. Electrical interventions may only be 
carried out by qualified electricians.

1.5 Conversion, spare parts

All technical changes are prohibited. Only use OEM 

spare parts.

oPeRAtInG InstRUCtIons

Содержание DG-T Series

Страница 1: ...n accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c Action Instruction 1 3 Liability We will not be held liable for damage resulting from non observance of the instructions and non com pliant use 1 4 Safety instructions Information that is relevant for safety is indicated in the instructions as fol...

Страница 2: ...h cover 2 Lower housing section 3 Hand wheel 4 1 2 conduit coupling 5 Manual reset DG NT and DG HT only 2 3 Type label DG T Approval and type see type label For detailed information on the adjusting range mean switching differential max inlet pressure lock off me dium and switching properties see page 5 10 Technical data und and the table on page 3 5 Adjustment 3 INSTALLATION CAUTION Please observ...

Страница 3: ...articles in the surrounding air or in the medium Filter pad for port 4 The web app PartDetective for selecting spare parts is available at www ad latus org 4 WIRING CAUTION To ensure that the DL is not damaged during operation note the switching capacity see page 5 10 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend using an RC mod ule 22 Ω 1 μF in ...

Страница 4: ...n 4 Difference between switching pressure and possible reset 6 PRESSURE SWITCHES WITH MAN UAL RESET DG NT locks off if the pressure drops to the value set using the hand wheel DG HT locks off if the pressure rises to the value set using the hand wheel 1 Reset the pressure switch using the manual reset Requirement for reset DG NT the pressure must have risen at least to the set switching point plus...

Страница 5: ...The set switching point may palpably change in media and ambient temperatures below 22 F 30 C Transport temperature ambient temperature Storage temperature 4 to 104 F 20 to 40 C Enclosure IP 65 This unit is not suitable for cleaning with a high pres sure cleaner and or cleaning products 10 3 Mechanical data Gas types natural gas town gas LPG gaseous flue gas biogas max 0 1 by vol H2S and air Max i...

Страница 6: ...the ambient conditions described Storage time 6 months in the original packaging before using for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time 13 DISPOSAL Devices with electronic components WEEE Directive 2012 19 EU Waste Electrical and Electronic Equipment Directive At the end of the product life number of...

Отзывы: