8. Testing System
– Operation Mode – Section 8, Page 36
Pressing the key cycles thru the Operation screens
a. Verify Input reads correctly
b. Check Output.
i. Go to the Auto/Manual Control screen and select Manual Control.
ii. Adjust % PWR using the Up and Down keys and observe final control.
iii. Return to the Auto/Manual Control screen and select Automatic Control.
c. Make sure Control Loop is set to Control Enabled.
d. Tune Loop
–
i. Set Main Setpoint
– In the Operation Mode, continually press the key until
the Setpoint Value screen appears. Adjust Main Setpoint using the Up and
Down keys.
ii. Automatic Tuning
– Section 8.11, Page 70.
The automatic tune menu is used to engage pre-tune and/or self-tune to
assist setting up proportional bands and the integral and derivative time
values used by the control loops.
Pre-tune can be used to set PID parameters approximately. Self-tune (Pre-
tune needs to be run first) may then be used to optimize the tuning if
required. See the Tuning section on page 101 for more information.
FYI: Pre-tune can be set to run automatically after every power-up by
enabling Auto Pre-Tune (Not Recommended).
Steps to Automatic Tune
The Automatic Tuning Menu is entered from the Main Menu
Hold down and press to enter the Main Menu.
Press Up or Down to select the Automatic Tuning Menu.