background image

Symptom

Checkout

Action

No heat.

Make sure power is on at
main service panel. Turn
the temperature setting
knob fully clockwise          .

Heater should start to warm up within two minutes. If not,
contact qualified electrician to check thermostat and heater.

Improper connections to
thermostat.

With power to circuit OFF, tighten all wiring connections. Repair
any frayed or broken wires.

Other.

Contact a qualified electrician for assistance.

Heater never turns
off.

Turn temperature setting
knob fully
counterclockwise           .

Heater should start to cool within minutes. If not, turn off power
at the main service panel, and contact qualified electrician.

Thermostat setting
and thermometer
reading disagree.

Thermostat affected by
drafts or radiant heat.

Contact electrician to change the location. The thermostat
should be about 5 ft (1.5m) above the floor and on an inside
wall.

Thermometer is out of
calibration.

Recalibrate. See step 8.

3

69-0829—1

Check Calibration

Turn the setting knob clockwise until the switch
makes (clicking sound). The heating equipment and

fan start.

No recalibration is necessary if the thermostat switch
makes with the thermostat setting at the same

temperature as indicated on the thermometer.

If the thermostat setting differs from the thermom-
eter, record the temperature difference and

recalibrate as instructed in the Recalibration Procedure
section.

Recalibration Procedure

Note the temperature difference between the
temperature setting and the thermometer.

Remove the thermostat cover.

Rotate setting knob clockwise

until you hear

switch click.

Hold the setting knob firmly and rotate the set point
scale ring counterclockwise

until the

12 o'clock position of the ring agrees with the cover
thermometer.

7

 TROUBLESHOOTING

Your Honeywell thermostat requires little or no attention. Most problems can generally be traced to the following:

8

  CALIBRATION

The CT62 Thermostats are calibrated at the factory using
precise instruments under closely controlled conditions.
Recalibration should not be necessary. Allow the thermo-
stat to operate for several hours before checking the
calibration. The CT62 Thermostat vapor-filled dual
diaphragm sensing element is affected by barometric
pressure and altitude. Temperature deviations of 1

°

F

(0.5

°

C) are normal. If the thermostat is mounted in a

suitable location and still appears out of calibration, check
calibration as follows:

M5796

THERMOSTAT 
BASE

SETTING KNOB 
AT 12 O'CLOCK 
POSITION

SETTING KNOB

SCALE RING

80

75

70

65

60

55

50

The heat from your hand will affect the diaphragm
sensor. Replace thermostat cover, wait five minutes

and recheck calibration.

Содержание CT62A

Страница 1: ...t base to outlet box and lift away Disconnect wires from old thermostat As you disconnect each wire tape the end and label it with the letter of the terminal designation to make reconnection to new thermostat easier Check the old insulation for cracks nicks or fraying and apply high quality plastic tape where necessary for adequate insulation Retain the old thermostat for reference purposes and un...

Страница 2: ...4 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED BREAKS ON POSITIVE OFF EXPOSED UNUSED LEADWIRES TO BE PROPERLY INSULATED THERMALLY ACTIVATED BREAKS ON TEMPERATURE RISE MAKES ON TEMPERATURE FALL L2 L1 L1 T2 T1 T1 CT62A CT62B 3 ELECTRIC HEATER CAUTION SPECIAL SERVICE CO ALR SOLDERLESS CONNECTORS MUST BE USED WHEN CONNECTING WITH ALUMINUM CONDUCTORS OTHERWISE A FIRE HAZARD...

Страница 3: ...e thermostat setting differs from the thermom eter record the temperature difference and recalibrate as instructed in the Recalibration Procedure section Recalibration Procedure Note the temperature difference between the temperature setting and the thermometer Remove the thermostat cover Rotate setting knob clockwise until you hear switch click Hold the setting knob firmly and rotate the set poin...

Страница 4: ... was caused by damage which occurred while the product was in the possession of a consumer Honeywell s sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF ANY WARRANTY EXPRESS OR IM PLIED ORANY...

Отзывы: