CT500 ELECTRONIC THERMOSTAT

7

69-1525—2

10 TROUBLESHOOTING

See Table 3 to troubleshoot your thermostat.

Table 3. Troubleshooting Your Thermostat.

Symptom 

Possible Cause

Corrective Action

Heating/cooling 
equipment does not 
operate.

No power to the 
thermostat.

Check power to heating/cooling equipment:
— On/Off switch.
— Fuse or circuit breaker.
— Loose 24V connection: at thermostat; at furnace/air 

conditioner.

— Incorrect wiring; check appropriate wiring diagram.

System switch on 
thermostat not in 
correct position.

Reset System switch.

Thermostat minimum-
off times operating for 
cooling.

Wait five minutes.

Incorrect wiring.

Check wiring.

Heating/cooling 
equipment not 
operating.

Consult equipment manfacturer instructions.

Partial display.

Thermostat not 
operating.

Replace thermostat.

Remained in customize 
mode.

See Customize Your Thermostat section to exit this mode.

No display.

No power to thermostat.

Check power to thermostat.

Thermostat mounted 
incorrectly on wallplate.

See Mount Thermostat to Wallplate section.

Temperature display 
is incorrect.

Thermostat is 
configured for °F or °C.

Reconfigure the display. See Customize Your Thermostat 
section for instructions to change the display.

Cannot change 
temperature setting.

The upper or lower 
temperature limits were 
reached.

Check the temperature setpoints; temperature setting range is 
40°F (4°C) to 99°F (37°C).

Snowflake is 
flashing.

Cooling equipment 
turns on after delay.

Wait approximately five minutes after the indicator starts flashing 
and then check the registers.

System on indicator 
(flame=heat) is 
displayed, but no 
warm air is coming 
from the registers.

Heating equipment 
turns on the fan when 
the furnace has 
warmed up to a 
setpoint.

Wait a minute after seeing the on indicator and then check the 
registers. If still no heat is coming from the registers, call your 
local heating and/or cooling contractor.

Содержание CT500

Страница 1: ...If this control is replacing a control that contains mercury in a sealed tube do not place your old control in the trash Dispose of it properly Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control If you have questions call Honeywell at 1 800 458 1502 1 PREPARE FOR INSTALLATION Check Table 1 to be sure this thermostat is compa...

Страница 2: ...ly two wires they do not need labeling Wrap wires around a pencil to keep them from falling back into the wall as shown in Fig 2 Fig 2 Wrapping wires around pencil Replacing Clock With C or C1 Clock Terminals If you are replacing a Honeywell Chronotherm Thermostat you may find one or two wires that go to the C or C1 clock terminals on the Chronotherm Thermostat wiring wallplate Do not allow them t...

Страница 3: ...m and is adaptable to most 4 wire 18 to 30 Vac heating cooling systems Refer to Fig 4 and 5 for typical system wiring diagrams Fig 4 CT500 wiring diagram 4 wire heat cool system Fig 5 CT500 wiring diagram 2 wire heat only system IMPORTANT Use 18 gauge maximum wire to wire the ther mostat All wiring must comply with local electrical codes and ordinances If unsure about household wiring procedures c...

Страница 4: ...wn separately on the digital display The indicator points to Set when the temperature setpoint is displayed and to Room when the room temperature is displayed 7 SET FAN AND SYSTEM SWITCHES Manually control fan and system settings using the switches located at the bottom of the thermostat case See Fig 9 for switch locations M14874 ALTERNATE MOUNTING SCREW HOLE MOUNTING SCREW HOLE MOUNTING SCREW HOL...

Страница 5: ...rate cooling system when outdoor temperature is below 50 F 10 C IMPORTANT Temporary protection delay protects compres sor the thermostat allows the compressor to remain off for five minutes before restarting Slide the System switch to Cool and the Fan switch to Auto Press the key to lower the temperature setting several degrees below the room temperature to start the cooling equipment Press the ke...

Страница 6: ...ol to C1 or C3 C1 Standard heating cooling temperature control C3 Agressive heating cooling temperature control can cause room temperature to overshoot the setpoint 9 Press the key again Factory information var ies by model is shown 10 Press the key to save all changes exit installer setup mode and return to normal operation NOTE After exiting installer setup mode slide the Sys tem switch to the d...

Страница 7: ...ostat section to exit this mode No display No power to thermostat Check power to thermostat Thermostat mounted incorrectly on wallplate See Mount Thermostat to Wallplate section Temperature display is incorrect Thermostat is configured for F or C Reconfigure the display See Customize Your Thermostat section for instructions to change the display Cannot change temperature setting The upper or lower...

Страница 8: ...as in the possession of a consumer Honeywell s sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF ANY WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PRODUCT Some states do not allow ...

Отзывы: