SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

62-0242—01

2

Fig. 2. Sensor removed from DIN rail

Fig. 3. Wires through sensors

WARNING

The secondary of the 5 Amps Current 
Transformer must be shorted together before 
the power may be turned on to the monitored 
device.

For applications in which the normal operating current is 
greater than 250 Amps or for conductor diameters larger 
that 3/4 in. (19 mm) in diameter, and external 5 Amps 
Current Transformer (C.T.) must be used as shown in 
Fig. 4.

Fig. 4. Current transformer

Latch Operation

Pressing down on the two (2) side tabs and swinging the 
cover open opens the split core current switch as shown 
in Fig. 5. Lifting up the latch with a flat-tip screwdriver as 
shown in Fig. 6 can also open the unit. Press down firmly 
on the cover to close the current switch. An audible “

click

” 

will be heard as the tab slides over the tongue on the 
base.

CAUTION

Mating surfaces of the magnetic core are 
exposed when the sensor is open. Silicone 
grease, present on the cores to prevent rust, 
can capture grit and dirt if care is not 
exercised. Operation can be impaired if 
anything prevents good contact between pole 
pieces. Visually check the mating parts of the 
core before closing the current sensor.

Fig. 5. Opening sensor by hand

3X

M25290

C

R

U

L

U

S

M25291

U

R

C

L

US

U

R

C

L

US

EXAMPLE:  FOR CURRENTS UP TO 600 AMPS, USE A 600:5 RATIO C.T.

 AS 

SHOWN. 

INSULATED         CONDUCTOR

600:5 RATIO 5A C.T. 

WIRE NUT 

M25295A

C

U

R

L

US

C

US

R

U

L

M25298

Содержание CSP-C

Страница 1: ...urrent is above the adjustable trip point The green LED will indicate whether the current is below the adjustable trip point IMPORTANT The current switch should be used on insulated conductors only The current switch may be mounted in any position using the 2 8 x 3 4 in 19 mm Tek screws and the mounting holes in the base or snapped directly on to the 1 3 8 in 35 mm DIN rail See Figures 1 and 2 Lea...

Страница 2: ...ch as shown in Fig 5 Lifting up the latch with a flat tip screwdriver as shown in Fig 6 can also open the unit Press down firmly on the cover to close the current switch An audible click will be heard as the tab slides over the tongue on the base CAUTION Mating surfaces of the magnetic core are exposed when the sensor is open Silicone grease present on the cores to prevent rust can capture grit an...

Страница 3: ...ameter of 350 MCM 17 3 mm See Fig 7 for use as a digital input to a building management system and Fig 8 for use as a pilot relay application OPERATING SPECIFICATIONS Max Sensing Current Voltage 600 Vac Table 1 Specifications by Product Number Fig 7 Digital circuit Fig 8 Analog circuit M25299 C US R U L Product Number Core Type Normal Position Adjustable Trip Point OutputSwitch Rating Max Current ...

Страница 4: ...is 10 of the trip point typically TROUBLESHOOTING Table 2 Resistance Readings For Good Unit Problem Solution Red LED is on but the current switch didn t activate Disconnect the wires from the current switch output Measure the resistance across the contacts with an Ohmmeter See Table 2 below for resistance readings for a good unit Red LED didn t turn on and the current switch didn t activate Verify...

Отзывы: