background image

SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

Automation and Control Solutions

Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN  55422

Toronto, Ontario  M1V 4Z9

customer.honeywell.com

® U.S. Registered Trademark
© 2007 Honeywell International Inc.
62-0242—01  C.H.   Rev.  06-07

Calibration of Adjustable Trip Point

The adjustable current switch has an operating range of 
0-200 Amps or 0-250 Amps. Do not exceed! The 
adjustable current switch comes with its fifteen-turn 
adjustable potentiometer set counter-clockwise 

 to 

its maximum position. The adjustable current switch can 
monitor Under load, Normal load and Overload 
conditions, depending on how it's set. The procedure 
below is for Normal load condition for part numbers 
CSS-O-A300-001 and CSS-O-A200-001.

Normal loads

With power on and the adjustable current switch on the 
proper range, turn the fifteen-turn adjustment 
potentiometer clockwise 

 until the red LED turns on 

and stop immediately. The adjustment switch is now 
tripped. The adjustable current switch Hysteresis (Dead 
Band) is 10% of the trip point typically.

TROUBLESHOOTING

Table 2. Resistance Readings For Good Unit.

Problem

Solution

Red LED is on but the 
current switch didn’t activate.

Disconnect the wires from the current switch output. Measure the resistance across the 
contacts with an Ohmmeter. See Table 2 below for resistance readings for a good unit.

Red LED didn’t turn on and 
the current switch didn’t 
activate

Verify that the conductor you are monitoring is above the adjustable trip point. If the 
sensor is monitoring less than the adjustable trip point, looping the wire may be 
required. See Fig. 3.

Sensor doesn’t switch at all, 
regardless of current level.

Adjustment potentiometer is probably set to its maximum or minimum position. Turn the 
potentiometer clockwise all the way and verify if the LED switches from red to green.

Product Number

Resistance if switch is open

Resistance if switch is closed

CSS-O-A300-001

Greater than 1 Meg ohms

Approximately 2 ohms

CSS-O-A200-001

Greater than 1 Meg ohms

Approximately 2 ohms

CSS-C-A300-001

Greater than 1 Meg ohms

Approximately 12 ohms

CSP-O-A300-001

Greater than 1 Meg ohms

Approximately 2 ohms

CSP-O-A200-001

Greater than 1 Meg ohms

Approximately 2 ohms

CSP-C-A300-001

Greater than 1 Meg ohms

Approximately 12 ohms

CSP-C-A200-001

Greater than 1 Meg ohms

Approximately 12 ohms

Содержание CSP-C

Страница 1: ...urrent is above the adjustable trip point The green LED will indicate whether the current is below the adjustable trip point IMPORTANT The current switch should be used on insulated conductors only The current switch may be mounted in any position using the 2 8 x 3 4 in 19 mm Tek screws and the mounting holes in the base or snapped directly on to the 1 3 8 in 35 mm DIN rail See Figures 1 and 2 Lea...

Страница 2: ...ch as shown in Fig 5 Lifting up the latch with a flat tip screwdriver as shown in Fig 6 can also open the unit Press down firmly on the cover to close the current switch An audible click will be heard as the tab slides over the tongue on the base CAUTION Mating surfaces of the magnetic core are exposed when the sensor is open Silicone grease present on the cores to prevent rust can capture grit an...

Страница 3: ...ameter of 350 MCM 17 3 mm See Fig 7 for use as a digital input to a building management system and Fig 8 for use as a pilot relay application OPERATING SPECIFICATIONS Max Sensing Current Voltage 600 Vac Table 1 Specifications by Product Number Fig 7 Digital circuit Fig 8 Analog circuit M25299 C US R U L Product Number Core Type Normal Position Adjustable Trip Point OutputSwitch Rating Max Current ...

Страница 4: ...is 10 of the trip point typically TROUBLESHOOTING Table 2 Resistance Readings For Good Unit Problem Solution Red LED is on but the current switch didn t activate Disconnect the wires from the current switch output Measure the resistance across the contacts with an Ohmmeter See Table 2 below for resistance readings for a good unit Red LED didn t turn on and the current switch didn t activate Verify...

Отзывы: