background image

YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL

Automation and Control Solutions

Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN  55422
customer.honeywell.com

® U.S. Registered Trademark
© 2013 Honeywell International Inc.
66-2060—01    M.S.   06-13
Printed in United States

3.

Ground shield to subbase earth ground screw on low 

voltage side of subbase.

4.

Installation, operation, and maintenance shall conform 

with National Fire Protection Association standards, 

national and local codes, and authorities having jurisdic-

tion.

Fig. 4. Equipment mounting panel dimensions in in. (mm).

21 (533)

21

(533)

3A

FU100

FU121

.5A

1

FUEL/AIR

CONTROL

SPARE
SPARE
SPARE

SPARE

SPARE

SPARE

M34893

SPARE

Содержание ControLinks YP7999A1000

Страница 1: ...eady to install Includes the R7999A control wiring subbase and S7999D1048 touchscreen display Commission monitor and control ControLinks through the touchscreen interface Fuel selector switch Alarm light Reset button Unit shutdown Emergency stop button Auto manual switch Manual operation potentiometer S7999D touchscreen display is Modbus ready SPECIFICATIONS Electrical Ratings 100 120 Vac 50 60 Hz...

Страница 2: ...tightened joints along the ground path are free of nonconductive coatings and protected against corrosion on mating surfaces Electrical Connections 1 Refer to the appropriate product data sheet for details 2 Wire size and length will vary depending on the compo nent Refer to the component literature for specific wire lengths sizes and type recommendations 3 Wire according to specifications followi...

Страница 3: ...t from ControLinks controller to burner control 11 HF High Fire drive command input from burner controller 12 MV Main Valve command input from burner controller 13 LF Low Fire drive command input from burner controller 14 LCI Limit Control Input from burner limit string including on off control LWCO high limit etc 15 LCO Limit Control Output from ControLinks controller to burner control demand int...

Страница 4: ...xxL burner control and or Modbus enabled UDC2500 3200 3500 controls in a daisy chain fashion to the customer terminals for dis play on the S7999D Refer to the S7999D S7800A or S7810M and UDC control product manuals for further information on wir ing and S7999D display set up 6 Installation operation and maintenance shall conform with National Fire Protection Association standards national and loca...

Страница 5: ...ED 20 POLYVINYL FSG RESET CONTROLINKS RESET POTENTIOMETER BELDEN 8760 18 AWG TWISTED PAIR ACTUATOR INTERFACE BELDEN 9535 24 AWG 5 CONDUCTOR DISPLAY TO TERMINAL STRIP BELDEN 9535 24 AWG 5 CONDUCTOR DISPLAY COM1 COM2 FROM TERM STRIP TO DEVICES BELDEN 8770 18 AWG 3 CONDUCTOR TEMP CTRL MODBUS BELDEN 8770 18 AWG 3 CONDUCTOR TWIST TO START PUSH TO STOP M34890 24 610 24 610 MANUAL OPERATOR 5K OHMS MANUAL...

Страница 6: ...YP7999A1000 CONTROLINKS FUEL AIR RATIO CONTROL PANEL 66 2060 01 6 Fig 2 Wiring diagram part 1 M34891 ...

Страница 7: ...tion only It is the responsibility of the end user to provide appropriate protection on the service to this control panel Refer to the National Electric Code and UL Stan dard 1077 for more information 2 Wire to the firing rate actuator must be run in separate conduit L N M34892 Indicates terminals and wiring in control panel main terminal block Indicates external wiring Indicates terminals in valv...

Страница 8: ... 66 2060 01 M S 06 13 Printed in United States 3 Ground shield to subbase earth ground screw on low voltage side of subbase 4 Installation operation and maintenance shall conform with National Fire Protection Association standards national and local codes and authorities having jurisdic tion Fig 4 Equipment mounting panel dimensions in in mm 21 533 21 533 3A FU100 FU121 5A 1 FUEL AIR CONTROL SPARE...