W-NXS AND CP-NXS
74-4059—01
14
Power Input
Review the
page 5. Typically, power wiring involves all modules listed in
.
See the following sections for more details:
•
•
Power Wiring Between Modules
•
shows typical power wiring connections for NXS
without
the NXS-UPS option.
•
shows power wiring connections for the NXS
with NXS-UPS
option (W-NXS-AX-FL and CP-NXS-
AX-FL).
1
1 (On)
Buffering time set is 95 seconds.
2
0
3
0
4
1 (On)
5
0
6
0
7
1 (On)
8
1 (On)
5 second disconnect at end of buffering time.
9
1 (On)
Battery in ON state (as an alternative, jumper
terminals X2.9–X2.10). This provides a way to
disconnect the battery.
Table 3
Power, UPS and battery modules for NXS.
Module
Description
Notes
Power
Supply
LOGO!Power 100–240Vac input, 24Vdc output,
90W power supply module, DIN-mountable.
Mount and wire according to shipped installation
document. Also see
NXS-UPS
SITOP DC-USV-Modul 15, 24Vdc output UPS
(uninterruptable power supply) module, DIN-
mountable, with communications to NXS for
power monitoring.
Mount and wire according to shipped installation
document. Also see
and
“Power Wiring Between Modules,”
SITOP Power Battery 24V/1.2Ah battery pack
module, DIN-mountable, for use with UPS.
Mount and wire according to shipped installation
document. Also see
Table 2
DIP switch settings on SITOP UPS for use with NXS.
NXS-UPS DIP Switch
Default/Recommended Setting
Switch
Pos.
(0=Off)