W-NXS AND CP-NXS
15
74-4059—01
Figure 13
Power-related connections for NXS without NXS-UPS option.
Figure 14
Power-related connections between modules for NXS with NXS-UPS option.
+
–
L
N
L+
M
Power
Supply
NXS
100–240VAC
Line
Neutral
24Vdc
NOTES:
The recommended range of wire gauge
(cross section) for making 24 Vdc connections is
from 18 AWG (0.75mm
2
) to 14 AWG (2.5mm
2
).
Do not install power wiring in cables or raceways
with communications wiring.
Use copper conductors only.
Fuse 4A, 32V
see
L+
M
L+
M
B+
B–
In
Out
Bat
+
–
+
–
L
N
L+
M
Power
Supply
NXS
SITOP Battery
SITOP UPS
100–240VAC
Line
Neutral
24Vdc
NOTES:
The recommended range of wire gauge
(cross section) for making 24 Vdc connections is
from 18 AWG (0.75mm
2
) to 14 AWG (2.5mm
2
).
Do not install power wiring in cables or raceways
with communications wiring.
Use copper conductors only.
Fuse 4A, 32V
see