Honeywell Chronotherm III T8602A Скачать руководство пользователя страница 7

69-0309—9

7

T8602A,B,C,D AND TS8602A,C Chronotherm

 

®

 III FUEL SAVER THERMOSTATS

With Adaptive Intelligent Recovery™, the room will reach
the comfort temperature at the exact time programmed
into the thermostat. The control temperature will increase
gradually, and turn the equipment on and off several times
to reach the comfort temperature slowly and on time.
There will be no wasted of energy associated with rapid
temperature changes and temperature overshoot.

With conventional recovery, the start time should be
programmed to be earlier than the desired comfort time. It
may require some trial and error to arrive at the best
starting time.

Setting Time/Temperature (Some Models)

The display readout may be converted between a 12 and
24 hour clock or 

°

C and 

°

F using screws 2A and 2B as

indicated in Fig. 16.

Setting Fan Operation

Some T8602C models include a fan operation switch on
the back of the thermostat on the lower left corner. See
Fig. 15. See Table 2 to determine correct setting of fan
operation switch.

CAUTION

The fan operation switch, which is available on
some T8602C models, is factory set to the NON
ELEC. position. If the system requires direct
thermostat control of the fan in heat mode, the
switch must be set to the ELEC. position. See
Table 2.

Table 2. T8602C Fan Operation Switch Setting.

Installing Batteries

Power is supplied for the thermostat by three AA alkaline
batteries. Batteries are included with thermostat. Install
batteries in back of thermostat as shown in Fig. 17. The
display will flash 1:00 PM and room temperature.

When the batteries are going dead, the display will flash
REPL BAT. If device has system switch, set to OFF.
Remove the thermostat from the wall and install three new
AA alkaline batteries. We recommend Energizer®
batteries. Change batteries within approximately 30
seconds from the time the batteries are removed to
prevent program loss and the necessity to reprogram.

IMPORTANT

The low battery warning will be displayed about
two months before the batteries are dead. When
the batteries are dead, the system will shut down.
After batteries are replaced, thermostat will
require reprogramming.

Mounting The Thermostat

Hang the thermostat on the tabs at the top of the base.
See Fig. 18A. Swing down and press on the lower edge
until the thermostat snaps into place. See Fig. 18B. Open
the cover, and tighten the captive mounting screws. See
Fig. 18C.

Setting Day and Time

Set the present day and time. When the thermostat is first
turned on, the display will read 1:00 PM and the room
temperature. It will go off for only a few seconds, then
begin to flash on and off.

Press                 .

Press TIME                  or                  to set the current
time.

Press                 .

Press                    to set the current day. Each press of the

DAY key advances the display one day.

If the display will not come on:

Check mounting of thermostat to wallplate. If loose or
misaligned, remove thermostat and reinstall on the
wallplate, making sure it is firmly attached.

Check to see that all the batteries are good and
installed correctly.

SET

PRESENT
DAY/TIME

AHEAD

Fan Operation

Fan Operation
Switch Setting

(4A)

Comments

Fan controlled
directly by
thermostat in heat
mode (typically
electric furnaces).

Set to ELEC.
position.

Use only one
system
transformer
jumper R and
RC.  

Fan has
independent
control in heat
mode (typically
gas, oil, millivolt
and some electric
furnaces).

Set to NON
ELEC. position

System may
have one or two
transformers;  
if one
transformer,
jumper R and
RC.

SET

PRESENT
DAY/TIME

DAY

BACK

M2083

BATTERY
PLACEMENT
(NOTE CORRECT PLUS
AND MINUS DIRECTION)

Fig. 17. Battery placement.

Содержание Chronotherm III T8602A

Страница 1: ...ocal waste management authority for instructions regarding recycling and the proper disposal of your old control If you have any questions call Honeywell Inc at 1 800 468 1502 INSTALLATION When Installing This Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given on the product to make sure the product ...

Страница 2: ...late does not require leveling for operation but for appearance only The wallplate mounts directly onto the wall with the screws included Using the wallplate as a template with a pencil mark two of three mounting screw positions on the wallplate that fit the application See Fig 2 Use a 3 16 in bit to drill holes for the anchors Gently tap anchors into the holes until flush with the wall surface Th...

Страница 3: ...in an oil system L1 HOT L2 1 W R HEATING ONLY WALLPLATE 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M2923 RESISTANCE HEATER SWITCH HEATER BLACK BLUE RED RED WHITE R841C BIMETAL SWITCH Fig 8 T8602A B heating only circuit in an electric baseboard or ceiling cable system Fig 3 Keep wiring restricted to the ribbed area surrounding terminals W MILLIVOLT HEATING ONLY WALL...

Страница 4: ...ION AIR BLOWER MOTOR COMBUSTION AIR BLOWER RELAY AIR PROVING SWITCH W R Fig 9 T8602A B heating only circuit in a Honeywell Intermittent Pilot Gas Burner Ignition System L1 HOT L2 1 C W Y R G W R W R W R W R ZONE 1 HEATING ONLY WALLPLATE ZONE 2 HEATING ONLY WALLPLATE ZONE 3 HEATING ONLY WALLPLATE ZONE 4 HEATING ONLY WALLPLATE 2 3 3 3 3 R8239A1052 R8222B1067 R8222B1067 R8222B1067 1 POWER SUPPLY PROV...

Страница 5: ... PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PRIMARY CONTROL SUCH AS GAS VALVE OR ELECTRONIC IGNITION MODULE CURRENT DRAW FOR W OR Y PLUS G MUST BE LESS THAN 1 6A M2924 W G HEATING COOLING WALLPLATE R RC Y COOLING CONTACTOR FAN RELAY HEATING PRIMARY CONTROL L1 HOT L2 1 L1 HOT L2 1 1 2 3 3 2 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PRIMARY CONTROL...

Страница 6: ...CTORY SETTING IN IN TIME TEMP DISPLAY 2A 2B 24 HR IN 12 HR o o C F OUT 1 2 TO 1 TURN OUT 1 2 TO 1 TURN IN RECOVERY SELECTION ADAPTIVE INTELLIGENT CONVENTIONAL 3A IN FACTORY SETTING OUT 1 2 TO 1 TURN M2082C 1 SCREWS 2A 2B AVAILABLE ON SOME MODELS ONLY 2 SWITCH 4A FOR FAN OPERATION SELECTION AVAILABLE ON SOME MODELS ONLY 1 3A 1A 1B 2A 2B 4A 2 Fig 16 Cycle rate adjustment SETTINGAND ADJUSTMENTS Adjus...

Страница 7: ...mostat from the wall and install three new AA alkaline batteries We recommend Energizer batteries Change batteries within approximately 30 seconds from the time the batteries are removed to prevent program loss and the necessity to reprogram IMPORTANT The low battery warning will be displayed about two months before the batteries are dead When the batteries are dead the system will shut down After...

Страница 8: ...system switch to COOL and the fan switch to AUTO Press COOLER key until the setting is about 10 F 6 C below room temperature The cooling equipment and fan should start Press the WARMER key until the setting is about 10 F 6 C above room temperature The cooling equipment and fan should stop NOTE On an AUTO changeover thermostat T8602D the heating temperature must be set at least 3 F 2 C below the co...

Страница 9: ...e fan switch is in AUTO A HEAT displayed when system switch is in HEAT COOL when in COOL HEAT and COOL when in AUTO neither when in OFF Also a four digit code is displayed with each digit explained as follows m 1 m A This equipment is a Class B digital apparatus which complies with Canadian Radio Interference Regulations CRC c 1374 First Digit Cycle Rate Setting cph At 50 On Time 0 or 1 1 2 or 3 3...

Страница 10: ...69 0309 9 10 T8602A B C D AND TS8602A C Chronotherm III FUEL SAVER THERMOSTATS ...

Страница 11: ...69 0309 9 11 T8602A B C D AND TS8602A C Chronotherm III FUEL SAVER THERMOSTATS ...

Страница 12: ... and Building Control Honeywell Limited Honeywell Limitée 740 Ellesmere Road Scarborough Ontario M1P 2V9 Helping You Control Your World 69 0309 9 J H Rev 7 95 Printed in Taiwan R O C QUALITY IS KEY Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 ...

Отзывы: