Honeywell CHRONOTERM IV T8624D Скачать руководство пользователя страница 8

69-1074

8

T8624D CHRONOTHERM

 

®

 IV DELUXE ZONE MULTISTAGE THERMOSTAT

 

Press Time 

 or Time 

 until the current time is

displayed.

NOTE:

Tapping the Set Current Day/Time will
advance the time in one hour increments.

NOTE:

If the current time is Daylight Savings
Time, press Daylight Time until DST is
displayed.

M10314

Time

Set Program

System

Fan

Run

Program

Hold Temp

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Time

Heat/Cool

Settings

Daylight

Time

Copy

AM

Tue

Set Day/Time

M10315

Time

Set Program

System

Fan

Run

Program

Hold Temp

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Heat/Cool

Settings

Daylight

Time

Daylight

Time

Copy

AM

DST

Tue

Set Day/Time

Press Run Program.

INSTALLER SELF-TEST

Use the Installer Self-Test to check the thermostat
operation. Refer to Table 4 for a list of the available self-
tests.

To start the self-test:

CAUTION

The minimum off time for compressors is bypassed
during the Installer Self-Test. Equipment damage
can occur if the compressor is cycled too quickly.

Press and hold the increase 

 and decrease 

▼ 

keys at

the same time until 10 appears. All segments of the
display will be displayed before the 10 appears. See
Fig. 11 and 12.

M10316

Time

Set Program

System

Fan

Run

Program

Run

Program

Hold Temp

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Heat/Cool

Settings

Daylight

Time

Copy

Auto

System

Fan

Wake

Room

AM

DST

Tue

Heat

Fig. 11. Display of all the segments of the LCD.

Aux Ht

Heat

Auto

System

Fan

Off

Auto

Wake

Mon

Wait

In

Room

Outdoor

%Humid

Auto 

Sav

AM

PM

Hold for

Cool

Repl Batt

On

Recovery

DST

Cool

TueWedThuFriSatSun

LeaveReturnSleep

M10345

Set Program

Set Day/Time

Start Time

Temporary Setting Enrg

Em Heat

Em Ht

Table  4. Tests Available In The Installer Self-Test.

Fig. 12. Display of test number.

Refer to Table 5 for the directions and results of the
specific tests.

NOTE:

Press Time 

 to advance the next test and

Time 

 to go back to the previous test. Press

Run Program to exit the self-test from any test
number except 60 series tests.

M10257A

TEST NUMBER

Test  

Number

Self-Test Description

10-19

Heating equipment can be turned on and
off

30-39

Cooling equipment can be turned on and
off

40-49

Fan equipment can be turned on and off

60   0 to
60   19

Keyboard keys test

70-79

Thermostat information including date
code and software versions are displayed

Содержание CHRONOTERM IV T8624D

Страница 1: ...tructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermosta...

Страница 2: ...ng Loosely insert the mounting screws into the holes Tighten mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 and 4 for typical hookups A letter code is located near each terminal for identification CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage Loosen the terminal screws on the wallplate and connect the...

Страница 3: ...Be sure to align the subbase pins to avoid damage to the thermostat Press lower edge of case to close and latch NOTE To remove the thermostat from the wall first pull out at the bottom of the thermo stat remove top last Fig 5 Proper wiring technique O G B C Y1 R W1 W2 Y2 OT OT W2 L G Y R W M6 M4 M1 THERMOSTAT ZONE 1 M11418 TotalZone PANEL THERMOSTAT CONNECTIONS WHEN USING W2 ON THE THERMOSTAT TO C...

Страница 4: ...ing Off Both the heating and cooling are off Fig 8 T8624D System and Fan key locations NOTE Always press the keys with your fingertip or similar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard M15042 Hold Temp Run Program Copy Daylight Time Set Current Day Time System Fan Time Set Program Day System Fan Wake Leave Return Sleep Heat Cool Settings M10405 Time Set Prog...

Страница 5: ...Em Ht M10349 INSTALLER SETUP NUMBER DISPLAY COLUMN 2 OF TABLE 3 FACTORY SETTING OR OTHER CHOICE DISPLAY COLUMN 3 OR 5 OF TABLE 3 Fig 10 Display of Installer Setup number and setting IMPORTANT Only configurable numbers are shown on the device Example If thermostat does not have a system key Installer Setup Number 12 will not be displayed Review Table 3 factory settings and mark any desired changes ...

Страница 6: ...aptive Intelligent Recovery control is activated system starts early so setpoint is reached by start of program period 1 Conventional recovery system starts recovery at programmed time Degree tempera ture display 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not used 17 and 18 Extended fan operation in h...

Страница 7: ...eat Cool Settings Daylight Time Copy PM Tue Set Day Time Installer Setup Number Press Time key to Factory Setting Other Choices Press or key to change Actual Select change Display Description Display Description Setting Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Minimum number of minutes 0 thru 5 the compressor will be off between calls for the c...

Страница 8: ...same time until 10 appears All segments of the display will be displayed before the 10 appears See Fig 11 and 12 M10316 Time Set Program System Fan Run Program Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Auto System Fan Wake Room AM DST Tue Heat Fig 11 Display of all the segments of the LCD Aux Ht Heat Auto System Fan Off Auto Wake M...

Страница 9: ...ge one heat comes on The system fan is also energized 12 Stage two heat comes on Stage one heat and system fan remain on 11 Stage two heat turns off 10 Stage one heat and system fan turn off Cooling Equipment Self Test Time 30 Change from heating to cooling equipment self test 31 Stage one cool and system fan come on 32 Stage two cool comes on Stage one cool and system fan remain on 31 Stage two c...

Страница 10: ...r to soak in the outdoor air for a minimum of five minutes before taking a reading TROUBLESHOOTING GUIDE Continued Symptom Possible Cause Action Display will not come on Thermostat is not being powered Check for 24 Vac between R and C terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power s...

Страница 11: ...et heating setpoint to desired temperature Cooling will not come on No power to the thermostat Check for 24 Vac between R and C If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and zone co...

Страница 12: ...69 1074 12 T8624D CHRONOTHERM IV DELUXE ZONE MULTISTAGE THERMOSTAT 69 1074 J H 3 97 Printed in Taiwan R O C 57 Bushes Lane Elmwood Park NJ 07407 3204 www honeywell com yourhome ...

Отзывы: