T8624D CHRONOTHERM

 

®

 IV DELUXE ZONE MULTISTAGE THERMOSTAT

Troubleshooting Guide (Continued).

Select models.

Symptom

Possible Cause

Action

Temperature
settings will not
change. (Example:
Cannot set the  

The upper or lower
temperature limits were
reached.  

Check the temperature setpoints:

Heating limits are 40 to 90°F (7 to 31°C)

Cooling limits are 45 to 99°F (9 to 37°C).

heating higher or
the cooling lower.)

The setpoint temperature
range stops were
configured.

Check Installer Setup numbers 34 and 35 and reconfigure the
setpoint stops.

Heating will not
come on.

No power to the  
thermostat.

Check for 24 Vac between R and C terminals.

If missing 24 Vac:

check if the circuit breaker is tripped—reset the  
circuit breaker.

check if the system fuse is blown—replace the fuse.

check if the power switch on the HVAC equipment is in
the Off position—set to the On position.

check wiring between thermostat and zone control
panel—replace any broken wires and tighten  
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Heating will not
come on.

Thermostat minimum off time
is activated.

Wait up to five minutes for the system to respond.

System selection is not set
to Heat.

Set system selection to Heat.

Heating setpoint is below
room temperature.

Check heating setpoint. Set heating setpoint to desired
temperature.

Cooling will not
come on.

No power to the  
thermostat.

Check for 24 Vac between R and C.

If missing 24 Vac:

check if the circuit breaker is tripped—reset the  
circuit breaker.

check if the system fuse is blown—replace the fuse.  

check if the power switch on the HVAC equipment is in
the Off position—set to the On position.

check wiring between thermostat and zone control
panel—replace any broken wires and tighten  
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time
is activated.

Wait up to five minutes for the system to respond.

Enter Installer Setup number 33. Reconfigure minimum off  
time (if required).

System selection is not set
to Cool.

Set system selection to Cool.

Cool setpoint is above  
room temperature.

Check cooling setpoint. Set cooling setpoint to desired
temperature.

System on indi-
cator (flame=heat,
snowflake=cool) is
displayed, but no
warm or cool air is
coming from the
registers.  

Heating or cooling
equipment is not  
operating.

Verify operation of heating or cooling equipment in self-test.

Outdoor tempera-
ture not displayed

a

Option not activated.

Enter Installer Setup number 24 and set to 1. Thermostat must
have OT terminals and a C7089B1000 installed.

Outdoor
temperature  

Outdoor sensor is  
connected incorrectly.

Refer to C7089B1000 installation instructions and check wiring
between the thermostat and sensor.

display is
incorrect

a

Wrong sensor.

Replace sensor with C7089B1000 sensor.

Содержание CHRONOTERM IV T8624D

Страница 1: ...tructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermosta...

Страница 2: ...ng Loosely insert the mounting screws into the holes Tighten mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 and 4 for typical hookups A letter code is located near each terminal for identification CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage Loosen the terminal screws on the wallplate and connect the...

Страница 3: ...Be sure to align the subbase pins to avoid damage to the thermostat Press lower edge of case to close and latch NOTE To remove the thermostat from the wall first pull out at the bottom of the thermo stat remove top last Fig 5 Proper wiring technique O G B C Y1 R W1 W2 Y2 OT OT W2 L G Y R W M6 M4 M1 THERMOSTAT ZONE 1 M11418 TotalZone PANEL THERMOSTAT CONNECTIONS WHEN USING W2 ON THE THERMOSTAT TO C...

Страница 4: ...ing Off Both the heating and cooling are off Fig 8 T8624D System and Fan key locations NOTE Always press the keys with your fingertip or similar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard M15042 Hold Temp Run Program Copy Daylight Time Set Current Day Time System Fan Time Set Program Day System Fan Wake Leave Return Sleep Heat Cool Settings M10405 Time Set Prog...

Страница 5: ...Em Ht M10349 INSTALLER SETUP NUMBER DISPLAY COLUMN 2 OF TABLE 3 FACTORY SETTING OR OTHER CHOICE DISPLAY COLUMN 3 OR 5 OF TABLE 3 Fig 10 Display of Installer Setup number and setting IMPORTANT Only configurable numbers are shown on the device Example If thermostat does not have a system key Installer Setup Number 12 will not be displayed Review Table 3 factory settings and mark any desired changes ...

Страница 6: ...aptive Intelligent Recovery control is activated system starts early so setpoint is reached by start of program period 1 Conventional recovery system starts recovery at programmed time Degree tempera ture display 14 0 Temperature is displayed in F 1 Temperature is displayed in C Not used 15 Clock format 16 0 12 hour clock format 1 24 hour clock format Not used 17 and 18 Extended fan operation in h...

Страница 7: ...eat Cool Settings Daylight Time Copy PM Tue Set Day Time Installer Setup Number Press Time key to Factory Setting Other Choices Press or key to change Actual Select change Display Description Display Description Setting Minimum off time for the compressor 33 5 5 minute minimum off time for the compressor 0 thru 4 Minimum number of minutes 0 thru 5 the compressor will be off between calls for the c...

Страница 8: ...same time until 10 appears All segments of the display will be displayed before the 10 appears See Fig 11 and 12 M10316 Time Set Program System Fan Run Program Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy Auto System Fan Wake Room AM DST Tue Heat Fig 11 Display of all the segments of the LCD Aux Ht Heat Auto System Fan Off Auto Wake M...

Страница 9: ...ge one heat comes on The system fan is also energized 12 Stage two heat comes on Stage one heat and system fan remain on 11 Stage two heat turns off 10 Stage one heat and system fan turn off Cooling Equipment Self Test Time 30 Change from heating to cooling equipment self test 31 Stage one cool and system fan come on 32 Stage two cool comes on Stage one cool and system fan remain on 31 Stage two c...

Страница 10: ...r to soak in the outdoor air for a minimum of five minutes before taking a reading TROUBLESHOOTING GUIDE Continued Symptom Possible Cause Action Display will not come on Thermostat is not being powered Check for 24 Vac between R and C terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power s...

Страница 11: ...et heating setpoint to desired temperature Cooling will not come on No power to the thermostat Check for 24 Vac between R and C If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and zone co...

Страница 12: ...69 1074 12 T8624D CHRONOTHERM IV DELUXE ZONE MULTISTAGE THERMOSTAT 69 1074 J H 3 97 Printed in Taiwan R O C 57 Bushes Lane Elmwood Park NJ 07407 3204 www honeywell com yourhome ...

Отзывы: