LONWORKS BUS I/O MODULES – PRODUCT DATA
EN0Z-0980GE51 R0119
2
OVERVIEW
LonWorks
BUS MODULES
pluggable
ANALOG OUTPUT
pluggable
ANALOG INPUT
pluggable
BINARY INPUT
XS821-22
XSU821-22
CONTROLLER
XS823
XSU823
XS824-25
XSU824-25
pluggable
RELAY OUTPUT
LonWorks Bus
CLIOL821A
CLIOLR822A
CLIOL822A
CLIOL823A
CLIOLR824A
CLIOL824A
Fig. 1. Overview of CentraLine LonWorks Bus I/O Modules
Table 1. Overview of CentraLine LonWorks Bus I/O Modules
order number
description
LonWorks
Bus I/O Modules
CLIOL821A
L
ON
W
ORKS
Bus Bus Analog Input Module (with 8 analog inputs)
CLIOL822A
L
ON
W
ORKS
Bus Bus Analog Output Module (with 8 analog outputs)
CLIOLR822A
L
ON
W
ORKS
Bus Bus Analog Output Module (with 8 analog outputs and manual overrides)
CLIOL823A
L
ON
W
ORKS
Bus Bus Binary Input Module (with 12 binary inputs)
CLIOL824A
L
ON
W
ORKS
Bus Bus Relay Output Module (with 6 relay outputs)
CLIOLR824A
L
ON
W
ORKS
Bus Bus Relay Output Module (with 6 relay outputs and manual overrides)
Terminal Sockets
XS821-22
Push-in terminal socket for AI/AO modules (incl. bridge connector, swivel label)
XSU821-22
Screw-type terminal socket for AI/AO modules (incl. bridge connector, swivel label)
XS823
Push-in terminal socket for BI modules (incl. bridge connector, swivel label)
XSU823
Screw-type terminal socket for BI modules (incl. bridge connector, swivel label)
XS824-25
Push-in terminal socket for relay/floating output modules (incl. bridge connector, cross connector, swivel label)
XSU824-25
Screw-type terminal socket for relay/floating output modules (incl. bridge connector, cross connector, swivel label)
Table 2. Overview of auxiliary parts and spare parts
order number
description
XS814
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two
groups with seven internally-connected push-in terminals.
XS815
20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in the
Terminal Socket package.
XS816
10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package.
XAL10
10 Swivel Labels Holders (for attaching the application-specific label printed with CARE / COACH AX /
COACH NX). One Swivel Label Holder is included in each Terminal Socket package. NOTE: Phased
out.
NOTE:
The inputs and outputs of all CentraLine analog and binary I/O modules are protected against short circuit,
24 VAC +20%, and 40 VDC.
In the case of the relay outputs of other CentraLine I/O modules (i.e., relay output modules, floating output
modules, and mixed I/O modules), appropriate fusing must be provided to ensure that permissible load currents
are not exceeded. See also sub-section "Features" in section "Relay Output Modules" on pg. 14.