IF-LON
Mounting Instructions
Copyright © 2013 Honeywell GmbH
●
All Rights Reserved
MU1Z-0974GE51 R0913
GENERAL
The CentraLine IF-LON L
ON
W
ORKS
® Interface can be used to
connect CentraLine controllers (via their USB port) with
L
ON
W
ORKS
® networks.
BEFORE INSTALLATION
All wiring must comply with local electrical codes and
ordinances or as specified on installation wiring diagrams.
IF-LON network wiring can be sized from 1.5 to 0.34 mm
2
,
depending on the application. The maximum length of wire
from the CentraLine controller to the IF-LON is 0.8 m.
CAUTION
EMI Noise Introduction. Risk of erratic system
operation.
Keep wiring at least 300 mm away from large induc-
tive loads such as motors, line starters, lighting
ballasts and large power distribution panels. During
installations, try to avoid areas of high EMI noise.
Run IF-LON wiring separately from 50 Vac or greater
power wiring.
WARNING / CAUTION
Risk of electric shock or equipment damage!
►
Disconnect the power supply before making connections
to or removing connections from the IF-LON’s terminals.
►
Do not reconnect the power supply until you have com-
pleted the installation.
►
Observe precautions for handling electrostatic sensitive
devices.
INSTALLATION
The delivery comes complete with the following parts:
IF-LON
L
ON
W
ORKS
®
Interface;
USB cable (0.8 meter long);
Clamp for connection of the IF-LON Interface to the
L
ON
W
ORKS
network;
A DIN rail-mounting bracket;
These Mounting Instructions (MU1Z-0974GE51).
Software Installation
The necessary driver software is already installed on the
CentraLine controller.
If you have installed CARE on a PC having Windows 7 as
the operating system, no further user action is necessary.
If you have installed CARE on a PC having Windows XP
as the operating system, you will have to install usbnet.
See CARE – Installation Guide (EN1Z-0964GE51) for details.
Hardware Installation
Using the supplied USB cable, connect the IF-LON Interface
to a free USB port of the CentraLine controller (see Fig. 1).
NOTE:
In performing this action, it is not necessary to
remove the CentraLine controller from power.
1
2
3
4
5
Fig. 1. Connecting the IF-LON
Table 1. Legend
no.
term remarks
1
LonWorks® connector
2-pin:
TP/FT-10
2
STATE LED (green)
OFF:
not ready to operate
ON:
ready to operate
3
SERVICE LED (yellow)
Display Service Pin Neuron
processor
4
Service Pin Button
Manual activation of a Service
Pin message
5
USB connector
Use supplied USB cable
See also IF-LON Interface – Installation Instructions (MU1B-
0538GE51) for more-detailed information.