background image

HAWK 8000 CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS 

Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

 

 
CentraLine 
Honeywell GmbH 
Böblinger Strasse 17 
71101 Schönaich, Germany 
Phone  +49 (0) 7031 637 845 
Fax 

+49 (0) 7031 637 740 

[email protected]

 

www.centraline.com 

 

 
 
 
 
 
 
Subject to change without notice 
EN1Z-1016GE51 R0218 

 

 

 

 

 

SPECIFICATIONS 

Power 

Voltage: 

24 VAC/DC (50/60 Hz) 

Max. power consumption:  18 VA (without Expansion 

Modules); 
20 VA (fully loaded with 
Expansion Modules) 

Rec. power supply: 

24 VAC (24 VA) / 24 VDC (1 A) 

 

Environmental Specifications 

Operating temperature: 

-20 … +60 °C 

Storage temperature: 

-40 … +85 °C 

Humidity: 

5 … 95%, non-condensing 

Shipping and vibration: 

ASTM D4169, Assurance Level II 

MTTF: 

+10 years 

Dimensions: 

See Fig. 3 to Fig. 5. 

 

APPROVALS, CERTIFICATIONS, ETC. 

▪  UL 916, Energy Management Equipment – Edition 4 
▪  CE: 2014/53/EU RED, 2011/65/EU RoHs 
▪  FCC Part 15, Subpart B, Class B; Part 15, Subpart C 
▪  C-UL listed to Canadian Standards Assoc. (CSA) C22.2 

No. 205-M1983 "Signal Equipment" 

▪  Ethernet: IEEEC 802.3 
▪  Purpose of the device is: multifunctional non-safety control 

intended for HVAC in home (residential, commercial, and 
light-industrial) environments 

NOTE:

 

Keep AC mains supply/load cables separate from 
signal wiring! 

 

RELATED TECHNICAL LITERATURE 

Table 11. Related Technical Literature 

Title 

Product 

Literature no. 

HAWK 8000 – Installation & Comm. Instructions 

EN1Z-1016GE51 

HAWK 8000 – Product Data 

EN0Z-1016GE51 

HAWK 8000 – Mounting Instructions 

MU1Z-1016GE51 

HAWK 8000 – Installation & Startup Guide 

EN1Z-1027GE51 

HAWK 8000 – Backup & Restore Guide 

EN2Z-1027GE51 

HAWK 8000 – PICS 

EN0Z-1028GE51 

HAWK 8000 – WiFi Guide 

EN2Z-1029GE51 

HON-NXEM-xxx Expansion Modules – M.I. 

MU1Z-1031GE51 

Panel Bus I/O Modules – Product Data 

EN0Z-0979GE51 

 

Содержание Centra Line CLNXHAW-5K

Страница 1: ...uded in Shipment 2 Overview of Features 3 Materials and Tools Required 4 Preparation 4 Mounting 4 Environmental Requirements 4 Dimensions Tab Mounting 4 Mounting on a DIN Rail 5 Wiring 5 Bus and Port Connections 6 Order Numbers 11 Drivers 11 Included Drivers 11 Optional Drivers 11 Specifications 12 Power 12 Environmental Specifications 12 Approvals Certifications etc 12 Related Technical Literatur...

Страница 2: ...ety are invalidated Rules regarding electrostatic discharge should be followed Use only accessory equipment which comes from or has been approved by Honeywell Construction The HAWK 8000 Controller is an independently mounted electronic control unit with fixed wiring Mounting Method The HAWK 8000 Controller is suitable for mounting as follows in cabinets in fuse boxes conforming with standard DIN43...

Страница 3: ...DC 50 60HZ 24W MAX OPERATING TEMPERATURE 20C to 60C REQ USE OF CLASS 2 24VAC TRANSFORMER OR EQUIVALENT 12977 8 Fig 1 HAWK 8000 overview of features 1 Earth ground 6 PRI primary LAN1 10 100 Mbit Ethernet connection 2 Terminal block for 24 VAC DC power supply 7 SEC secondary LAN2 10 100 Mbit Ethernet connection 3 RS485 A port and bias termination switch 8 Access shutter for microSD card slide to ope...

Страница 4: ...ecial system password stored in the controller base software If you swap in a card from a previously configured unit you must re enter this same password using a serial connection to the controller s Debug port WARNING Risk of electric shock or equipment damage Disconnect the power supply before removing or inserting the microSD flash memory card Failure to do so is likely to damage the equipment ...

Страница 5: ...ination 6 Carefully secure both ends of the final assembly with DIN rail end clips provided by the DIN rail vendor Wiring WARNING Risk of electric shock or equipment damage Before making power terminations de energize the 24V power source Do not restore power until completing all other mounting and wiring See also section Power Up and Initial Checkout on pg 8 Wiring Earth Ground and Power Earth gr...

Страница 6: ...ition WiFi adapter is disabled ACC Left position Controller provides operation as a WiFi access point for up to 20 clients CLT Right position Controller operates as a client to an existing 802 11a b g n router or access point To use either screw in the antenna directly see Fig 9 or use an optional coax cable extension kit CBL WIFI EXT to locate the antenna up to 2 m away An associated LED remains ...

Страница 7: ... baud and uses a 3 position screw terminal connector A A S RS485 A HAWK 8000 RS485 B DEVICE 1 DEVICE 1 DEVICE 2 DEVICE 2 DEVICE N DEVICE N B B S S S S S S S Fig 10 RS485 wiring example NOTE RS485 devices on the same network should use the same communication protocol and the same baud rate Up to 32 or more devices may be supported depending upon device specifications Use shielded twisted pair 18 22...

Страница 8: ...predictable behavior if other electrically non isolated devices are connected and the potential difference is too high In the case of the installation of HAWK 8000 con trollers in already existent RS485 two wire systems e g when replacing PANTHER or LION controllers with HAWK 8000 controllers not using a separate signal ground wire will probably have no undesirable effects The cable length affects...

Страница 9: ...at boot up also occurs during other critical operations such as a firmware upgrade to the controller and or any attached modules To be safe do not remove power from the controller while its BEAT LED is flashing in a 90 10 ON OFF duty cycle Instead wait for the normal 50 50 flash to return before removing power If the BEAT LED remains ON constantly does not light up or flashes very fast contact T A...

Страница 10: ...s door opened Legend 1 BACKUP button and corresponding BACKUP LED 2 PROG USB 2 0 for use with USB flash thumb drive 3 DEBUG Micro A USB for serial debugging communications 4 SHT DWN Recessed pushbutton for initiating a controlled shutdown The DEBUG port is a standard Micro A type USB port for serial debugging communications to the controller You can use a serial terminal program for example PuTTY ...

Страница 11: ...5 HAWK8 PLUS 1250 POINTS UPGRADE CLNX DEVICE UP 50 HAWK8 PLUS 2500 POINTS UPGRADE Table 8 Software upgrade licenses OS number description CLNX SMA 8005 1YR HAWK8 1YR SW UPDATE 250 499 PTS CLNX SMA 8005 3YR HAWK8 3YR SW UPDATE 250 499 PTS CLNX SMA 8005 5YR HAWK8 5YR SW UPDATE 250 499 PTS CLNX SMA 8010 1YR HAWK8 1YR SW UPDATE 500 1249 PTS CLNX SMA 8010 3YR HAWK8 3YR SW UPDATE 500 1249 PTS CLNX SMA 8...

Страница 12: ... MTTF 10 years Dimensions See Fig 3 to Fig 5 APPROVALS CERTIFICATIONS ETC UL 916 Energy Management Equipment Edition 4 CE 2014 53 EU RED 2011 65 EU RoHs FCC Part 15 Subpart B Class B Part 15 Subpart C C UL listed to Canadian Standards Assoc CSA C22 2 No 205 M1983 Signal Equipment Ethernet IEEEC 802 3 Purpose of the device is multifunctional non safety control intended for HVAC in home residential ...

Отзывы: