User’s Manual
CD3000S-3PH from 125A to 500A
Honeywell
6.1 Auxiliary supply
Warning:
this procedure can be done just by specialized personnel
.
To change auxiliary supply voltage sold the correct link-jumper on main PCB.
Auxiliary supply jumpers for S11, S13 and S14 sizes
J11
J10
J9
230V Auxiliary supply
To set the auxiliary power
supply to 230V, close J9 and
J11 and open J10 as shown
below.
460V Auxiliary supply
To set the auxiliary power
supply to 460V, close J10
and open J9 and J11 as
shown below.
600V Auxiliary supply
This is a special version on request.
In this case the unit is supplied
already configured.
J11
J10
J9
J11
J10
J9
J11
J10
J9
19
www.honeywell.com/imc