User’s Manual
CD3000S-1PH from 125A to 700A
Honeywell
9. Maintenance
9.1
Trouble Shooting
Small problems sometimes can be solved locally with the help of the below tab of trouble shooting.
If you don’t succeed, contact us or your nearest distributor.
Symptom
LED Indication
Possible reasons of the
symptom
Actions
Green LED (PWR)
is always light off.
No voltage auxiliary power
supply to terminals 1-3
(see wiring diagram).
Give auxiliary voltage supply to
terminals 1-3.
Thyristor unit
doesn’t go in
conduction with
input signal.
Green LED (PWR)
light on and green
LED (ON) in off
condition.
No input signal.
Reversed polarities of input
signal.
Reset contact in open
condition (see wiring
diagram).
Provide to give input signal.
Reverse the input signal polarity.
Make link on reset terminals.
Load current flows
also with no input
signal.
Green LED (ON)
always in off
condition.
Short circuit on thyristor.
Wrong connection.
Substitute the thyristor. Check that
load is not in short circuit.
23
www.honeywell.com/imc