Honeywell
CD3000M-2PH from 125A to 700A
User’s Manual
10. Maintenance
10.1
Trouble Shooting
Small problems sometimes can be solved locally with the help of the below tab of trouble shooting.
If you don’t succeed, contact us or your nearest distributor.
Symptom Indication
on
front unit
Possible reasons of the
symptom
Actions
Green LED is
always light off.
-
No voltage auxiliary
power supply to
terminals 1-3 (see
wiring diagram).
-
Give auxiliary voltage supply to
terminals 1-3.
Green LED (PW)
light on and green
LED (ON) in light
off condition.
-
No input signal.
-
Reversed polarities of
input signal.
-
Reset contact in open
condition (see wiring
diagram).
-
Provide to give input signal.
-
Reverse the input signal polarity.
-
Make link on reset terminals.
Thyristor unit
doesn’t go in
conduction with
input signal.
Green LED (PW) in
light on condition
and green LED
(ON) in light on
condition.
-
Fuse failure.
-
Load failure.
-
Load connection
interruption.
-
Thyristor faulty and
always in open circuit.
-
With HB option the
yellow led (HB) in light
on condition.
-
Substitute the fuse.
-
Repair the load.
-
Provide to repair the wiring.
-
Substitute the faulty thyristor.
-
Check the load.
Load current flows
also with no input
signal.
Green LED (ON)
always in light off
condition.
-
Short circuit on
thyristor. If there is HB
circuit the red LED (SC)
is light on.
-
Substitute the thyristor. Check
that load is not in short circuit.
Current flows at
nominal value but
yellow LED (HB) in
light on condition.
Yellow HB in light
on condition.
-
HB circuit not tuned.
-
Current transformers
not properly wired (if
are external to
CD3000).
-
Push CAL button in front unit to
start HB calibration procedure.
-
Control current transformers
wiring and Push CAL button in
front unit to start HB calibration
procedure.
Red LED (SC) is
lighted also if
current is at
nominal value.
Red LED in light on
condition.
-
HB circuit not properly
tuned.
-
Push CAL button in front unit to
start HB calibration procedure.
Thyristor unit
doesn’t work
properly.
-
Wrong input signal
selection.
-
Wrong input signal
calibration (out of
range).
-
Auxiliary voltage supply
out of limits.
-
Control input signal setting.
-
Repeat input calibration
procedure.
-
Verify the auxiliary voltage
supply.