9.4 Thyristor unit Configuration
Parameter N.
Notes
Password 123
Write
Delay trigger
124L
Read /write
% HB
124H
Read /write
Firing type
125L
Read /write
Soft start time
125H
Read /write
N° burst
126L
Read /write
Delay time HB
126H
Read /write
Max power for SSR Input
127L
Read /write
Cycle time
127H
Read /write
N° of half period for Delayed triggering 128L
Read /write (Mantenere a 1)
128H
Read /write
9.4.1 Password
Parameter 123
Operations:
Write
Meaning:
If properly setted give the access to configuration
9.4.2 Delay triggering
Parameter 124L
Operations:
Read/Write
Meaning:
It’s correspond to a value in points (0-50, 0-32 Hex)
Each step is 0,1msec. Range is 0-5msec.
This parameter is the delay of firig in first half period with respect zero voltage crossing.
9.4.3 % HB
Parameter 124H
Operations:
Read/Write
Meaning:
It’s correspond to a value in point (0-255, 0-ff Hex)
This parameter is the value in % that decrease the load current to establish the HB current set
point
Example:
Load current
= 10A
Parameter 124H
= 20% 51 Dec
33 Hex
Parameter 2 will be setted at 8A
41
www.honeywell.com/imc