User’s Manual
CD3000M-1PH up to 110A
Honeywell
45
www.honeywell.com/imc
10.3.8 Command Table
Bit Meaning
Notes
0
HB Calibration
Read /write 0=Off -
1=ACTVATE Calibration
( normal mode set to 0)
1
Firing command
Read /write
0=from terminal - 1=from RS485
2
On-Off
Read /write
0=Off -
1=On
3 RESET
HB
Read /write
0=Off -
1=RESET
( normal mode set to 0)
N.B.: When unit is switch off all command parameter are set to 0
10.3.8.1 HB Calibration
Bit 0
Operations:
Read / Write
Meaning:
It’s a bit that starts the HB calibration procedure
When this bit is zero start the calibration procedure and reset itself automatically at the end.
10.3.8.2 Firing command
Bit 1
Operations:
Read / Write
Meaning:
It’s a command bit used to switch from analog external command to command via RS485
0
= Command of analog input
1
= Command of RS485 input
10.3.8.3 On-Off
Bit 2
Operations:
Read / Write
Meaning:
Its’ an enable bit to switch ON-OFF the power.
0
= Power disabled
1
= Power enabled
10.3.8.4 HB RESET
Bit 3
Operations:
Read / Write
Meaning:
It’s a command bit to reset HB alarm.
This parameter has to be at 0 to have the alarm working properly
0
= Reset disabled
1
= Reset enabled