User’s Manual
www.honeywell.com/imc 22
6.4 Heater Break Alarm
Heater Break Alarm is a microprocessor based circuit to diagnose partial or total load failure and
short circuit on SCR and fuses failure.
•
discrimination better than 20%;
•
latching alarm plus reset;
•
relay output 0.5A at 125VAC.
Minimum current 3A. If load current is below this value make two turns or more
around current transformer. H.B. circuit also diagnose fuse failure.
H.B. circuit reads load current via a current transformer 25-50/0.05 or 100/0.05 depending on
thyristor size.
6.4.1 Heater Break Alarm indication
LED STATUS
DESCRIPTION
SC
SCR OK
SCR short circuit
HB
Laod OK
Load Fault
: LED off
: LED on
The thyristor unit is supplied with a normally closed (N/C) contact.
In alarm condition and without auxiliary voltage the contact is closed (relay coil not
energized). In normal condition (no alarm) the contact is open (relay coil energized).
6.4.2 Reset
To reset Heater Break Alarm open RESET contact on terminal 3-4.