background image

C7061M MINIATURE DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR

3

65-0304—05

Fig. 1. Dimensions of C7061M in inches. (mm).

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced flame safeguard 

service technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

CAUTION

Equipment damage hazard. 

Sensing tube can fail to discriminate between 

flame conditions. Change sensing tube after 40,000 

hours of continuous use.

WARNING

Electrical shock hazard.

Can cause serious injury or death. 

Disconnect power supply before beginning 

installation to prevent electrical shock and 

equipment damage. More than one disconnect may 

be involved.

NOTICE

Per industry standards, a conduit seal or a cable type that 

is sealed is required to be installed in a device that can 

result in flammable gas or flammable liquid flow through a 

conduit or cable to an electrical ignition source in the 

event of a seal leakage or diaphragm failure.

IMPORTANT

1. Do not connect these detectors to non-Honeywell 

manufactured controls (primaries, programmers, 

multiburner systems, and burner management 

systems). Unsafe conditions could result.

2. All wiring must be NEC Class 1 (line voltage).

3. The C7061 is powered from the Flame Safeguard unit 

that delivers the necessary voltages to operate the 

sensing tube and shutter.

4. Sight the detector so it does not respond to ignition 

spark.

5. On multiburner installations, each detector must 

respond only to the flame of the burner it is 

supervising.

6. Do not connect more than two C7061 Flame 

Detectors in parallel.

Proper flame detector installation is the basis of a safe and 

reliable flame safeguard installation. Refer also to the burner 

manufacturer instructions. Carefully follow all instructions for 

the best possible flame detection application.

Basic Requirements

The combustion flames of most carbon-based fuels emit 

sufficient ultraviolet radiation to enable the C7061 (Purple 

Peeper) Ultraviolet Flame Detector to prove the presence of a 

flame in a combustion chamber. The detector is mounted 

outside the combustion chamber with its mounting nut 

threaded to one end of a sight pipe inserted through the wall of 

the combustion chamber. The ultraviolet sensing tube in the 

flame detector sights the flame through the pipe.

When a flame is present, the UV tube in the C7061 senses the 

ultraviolet radiation emitted. The C7061 then produces a signal 

that is sent to the amplifier in the flame safeguard control. The 

amplified signal energizes the flame relay in the control to allow 

proper system operation.

M29114A

2-9/64 (55)

13/16 (21)

2-21/32

(68)

3-15/32

(88)

1-33/64

(39)

PARALLEL

PIPETHREAD 

1-11/2 NPSM

33/64

(13)

2-9/64

(55)

1-35/64

(40)

CONDUIT TUBE CONNECTION

PORT 1/2 NPSM 

Содержание C7061M

Страница 1: ...ing tube is field replaceable Threaded conduit fitting and color coded leadwires allow rapid electrical installation C7061M1016 uses Molex Woodhead 1R5006A20A120 formerly Brad Harrison Type 41310 connector Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications 4 F 20 C to 175 F 80 C ambient temperature Incorporates UV sensor tube checking...

Страница 2: ... unit that delivers the necessary voltages to operate the tube and shutter Ambient Operating Temperature Ratings Outside the Case 4 F to 175 F 20 C to 80 C using part no 129464N UV Sensing Tube Storage Temperature Ratings 4 F to 158 F 20 C to 70 C Housing Violet plastic cover Housing protection is IP66 Similar to Nema 4 indoor outdoor protection rain tight dust tight hose directed water pro tectio...

Страница 3: ...nditions could result 2 All wiring must be NEC Class 1 line voltage 3 The C7061 is powered from the Flame Safeguard unit that delivers the necessary voltages to operate the sensing tube and shutter 4 Sight the detector so it does not respond to ignition spark 5 On multiburner installations each detector must respond only to the flame of the burner it is supervising 6 Do not connect more than two C...

Страница 4: ...field of view If the temperature of the hot refractory causes the flame relay in the flame safeguard control to pull in re aim the sight pipe so the detector views a cooler area of the refractory Ignition spark is an intense source of ultraviolet radiation When installing the detector make sure it does not respond to ignition spark by following the Ignition Spark Response Test listed on page 9 Sin...

Страница 5: ...e defined as locating all flame detectors so that each detector responds only to the flame of the burner it is supervising In multiple burner systems not every detector can be positioned so its line of sight does not intercept flames from other burners For example this situation occurs in front fired boiler furnaces having more than one row of burners or in multilevel opposed fired furnaces where ...

Страница 6: ...tilate the sight pipe to cool the detector or to clear a viewing path through UV radiation attenuating material For a negative pressure combustion chamber drilling a few holes in the section of the sight pipe outside of the combustion chamber allows air at atmospheric pressure to flow through the sight pipe and into the chamber A perforated pipe nipple between the sight pipe and the detector can a...

Страница 7: ...on source in the event of a seal leakage or diaphragm failure 1 All wiring must comply with applicable local electrical codes ordinances and regulations Use NEC Class 1 wiring 2 Keep the flame signal leadwires as short as possible from the flame detector to the terminal strip or wiring subbase Capacitance increases with leadwire length reducing the signal strength The maximum permissible leadwire ...

Страница 8: ...the sighting position of the detector for optimum flame signal It is suggested that a volt ohm meter with a minimum sensitivity of one megohm volt and a zero to five or ten Vdc scale be used for R7861 Amplifier flame signal measurements Measure the flame signal as illustrated in Fig 8 Be careful to make the proper connections of positive red meter lead to positive control jack and negative black m...

Страница 9: ...iew Continue adjustments until the flame signal due to ignition spark is less than the flame signal values indicated in step 2 Response to other Ultraviolet Radiation Sources Some sources of artificial light produce small amounts of ultraviolet radiation Under certain conditions an ultraviolet detector responds as if it is sensing a flame Do not use an artificial light source to check the response...

Страница 10: ...e the plug in amplifier Then recheck the flame signal 7 Replace the ultraviolet sensing tube see Service on page 10 Then recheck the flame signal 8 Remove detector from the sight pipe and sight it on a UV source and note the flame LED on the 7800 Series device 9 If you cannot yet obtain a meter reading replace the detector IMPORTANT At the completion of Troubleshooting be sure to perform the Adjus...

Страница 11: ...f ultraviolet rays with an orifice ring or the like If there is too much ultraviolet radiation it can penetrate the tube unit even when the shutter is closed causing faulty operation Inspection and Adjustment After replacing the UV sensing tube perform a pilot turndown test an ignition spark response test and a safety shutoff test to verify proper functioning of the tube unit IMPORTANT Do not put ...

Страница 12: ...AME DETECTOR Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 65 0304 05 M S Rev 07 13 Printed in United States ...

Отзывы: