Honeywell Braukmann D06G Скачать руководство пользователя страница 3

D06G PRESSURE REGULATING VALVE

62-3051

3

Water Capacities (See Table 1)

The suitability of a given regulator size is dependent on the
pressure requirements of each installation. To determine the
pressure regulator valve size required for a specific
installation, calculate the following:

���

Pressure differential between inlet and outlet pressure
in pounds per square inch (psi).

���

Capacity in gallons per minute (gpm), and

���

Allowable reduced pressure falloff in psi.

Given these variables, use Table 1 to determine the proper
size pressure regulator valve for your application.

Example:

An installation has 135 psi inlet pressure, 60 psi
outlet pressure (75 psi pressure differential). If
30 gpm capacity is required with only 10 psi
falloff allowable, a 1-1/2 in. D06G is required.
This pressure regulator valve allows a flow
capacity up to 46 gpm with a 10 psi falloff at a
no flow pressure differential of 75 psi.

Table 1. Water Capacities.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous
condition.

2. Check the ratings given in these instructions and on the

product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out the product as

provided in these instructions.

Procedure

���

Flush the system clear of sediment and debris.

���

Close the supply valve and downstream isolating valve
(if existing).

���

Install the D06G with the arrow pointing in the direction
of water flow (any mounting orientation is acceptable).
The D06G can be installed directly onto a pipe using
the female NPT threads on each end or by using single
or double unions, if required. (One union is provided.)

CAUTION

Heat from soldering can damage internal parts.
Always remove tailpiece or solder adapter prior
to soldering.

���

Open the supply valve slowly and open the
downstream valve, if provided.

���

Check for leaks at connections and correct, if necessary.

Adjusting Outlet Pressure (See Fig. 2)

The D06G is factory set at 60 psi (no flow). Follow this
procedure if adjustment is required:

���

Close the supply shutoff and open a downstream faucet
to relieve pressure in the line. Remove the gauge plug
and install a pressure gauge. Close the downstream
faucet and open the supply valve.

���

Loosen the locking screw one turn counterclockwise.
Do not remove the locking screw.

���

Turn the adjusting knob clockwise to increase pressure
and counterclockwise to decrease pressure. When
decreasing pressure, a slight downstream flow is
necessary to relieve pressure. Turn the knob until the
pressure gauge indicates the desired pressure (no flow
set pressure).

���

Tighten the locking screw.

Pressure Differential Between Inlet and Outlet (psi)—No Flow

25

50

75

100

Size

(in.)

Reduced

Pressure Fall

off (psi)

Flow

Capacity

(US gpm)

Velocity

(ft/sec)

Flow

Capacity

(US gpm)

Velocity

(ft/sec)

Flow

Capacity

(US gpm)

Velocity

(ft/sec)

Flow

Capacity

(US gpm)

Velocity

(ft/sec)

1-1/2

6

13

2.0

15

2.4

17

2.7

21

3.3

10

36

5.7

43

6.8

46

7.2

54

8.5

15

65

10.2

76

12.0

84

13.2

96

15.1

20

88

13.9

102

16.1

114

18.0

132

20.8

2

6

15

1.4

18

1.7

22

2.1

27

2.6

10

41

3.9

49

4.7

57

5.4

66

6.3

15

75

7.2

88

8.4

101

9.7

114

10.9

20

104

9.9

124

11.9

141

13.5

163

15.6

Содержание Braukmann D06G

Страница 1: ...stallation and application FEATURES Noncorroding unitized cartridge contains all working parts and is easily replaceable Outlet pressure range from 15 to 130 psi in all models inlet rating 400 psi Includes built in strainer and thermal bypass Narrow design to accommodate restricted installation requirements Balanced seat construction provides superior pressure regulation Inlet and outlet are inter...

Страница 2: ... Design Balanced single seat Inlet Pressure Maximum 400 psi Reduced Pressure Range 15 to 130 psi all models Outlet Pressure Factory set at 60 psi Differential 14 psi minimum for optimum regulation Reduced Ratio 10 1 maximum Temperature Maximum 180 F 82 C Ambient Temperature Range 33 F to 140 F 1 C to 60 C Pipe Sizes Available 1 1 2 and 2 in Connections All models have internal NPT on inlet and out...

Страница 3: ...nting in the direction of water flow any mounting orientation is acceptable The D06G can be installed directly onto a pipe using the female NPT threads on each end or by using single or double unions if required One union is provided CAUTION Heat from soldering can damage internal parts Always remove tailpiece or solder adapter prior to soldering Open the supply valve slowly and open the downstrea...

Страница 4: ...seal by placing the U seal on the strainer support and pushing the assembly into place The U seal open end must face the strainer support Fig 7 Replace the strainer onto the strainer support Assemble the strainer cup O ring onto the strainer cup and insert the assembly into the body of the valve Tighten securely using the service tool Do not over torque 쐅 Replace the new cartridge ensuring the O r...

Страница 5: ...rainer support Do not remove the U seal Clean the strainer cup and the strainer Replace the strainer on the strainer support Insert the assembly into the valve Assemble the strainer cup O ring onto the strainer cup and insert the assembly into the body of the valve Tighten securely using the service tool Do not over torque M11215 REMOVE STRAINER CUP USING MT06A SERVICE TOOL BONNET ASSEMBLY SPRING ...

Страница 6: ...ssure is set the D06G automatically regulates to maintain the downstream pressure TROUBLESHOOTING Table 2 is a troubleshooting guide for the D06G Pressure Regulating Valves Table 2 Troubleshooting D06G Pressure Regulating Valves Problem Probable Cause Solution Will not hold pressure or pressure gradually rises a Thermal expansion b Debris on valve seat c Damaged valve seat a Install a thermal expa...

Страница 7: ... Union Kit NPT 1 1 2 in includes female NPT threaded tailpiece union nut and gasket and fits all 1 1 2 in D06 and DS06 Valves K06U5034 Union Kit Sweat 1 1 2 in includes sweat tailpiece union nut and gasket and fits all 1 1 2 in D06 and DS06 Valves K06U1045 Union Kit NPT 2 in includes female NPT threaded tailpiece union nut and gasket and fits all 2 in D06 and DS06 Valves K06U5042 Union Kit Sweat 2...

Страница 8: ...imited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Helping You Control Your World 62 3051 G H 11 96 Printed in U S A Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell ca braukmann www sparco inc com ...