background image

Installation Guide

11

5) Additional Installation Information

5.1 Binding / Rebinding Procedure

The binding operation described below is required if:
•  Any of the system components (room thermostat or Relay Box) are replaced.
•  The Relay Box has incorrect or no binding data stored (e.g. when pre-bound system pack components 

have been mismatched).

NOTE:

 During the binding procedure keep approximately 1m distance between the room thermostat and 

the Relay Box.

To bind/rebind:

1.

  Press and hold the Relay Box push button for 15 seconds to reset any previously stored data. After 15 

seconds the red LED will change to flashing 0.1sec on/0.9sec off. 

 

NOTE:

 After 5 seconds the red LED will start to flash 0.5sec on/0.5sec off, but continue to hold the button).

2.

  Release the push button.

3. 

Press and hold the Relay Box push button for 5 seconds to enter the binding mode. The Red LED will 

start flashing at 0.5sec on/0.5sec off to confirm the binding mode has been entered.

4. 

Move the room thermostat slider to the 

OFF

 position and press the     and   buttons together along 

with the   button. The unit will display InSt and ‘CONTROL BINDING’.

5.

  Press the green   button to send the binding signal out to the Relay Box. The red LED is switched off to confirm 

successful binding operation. If the red LED still flashes push the button again until binding is successful.

6. 

Now go to Section 

2) Installing the CM900 Wireless System

 to setup the system.

5.2 Multi-Zone System

Multiple  room  thermostats  and  Relay  Box  sets  can  also  be  used  to  control  multi-zone  systems  and  the 

CM927/921 room thermostat is compatible with a variety of other Honeywell products including HR80 radiator 

controllers (see below) and HCE80 underfloor heating controllers. If you intend to use it in this way additional 

installation and user instructions can be obtained by contacting the address at the end of this guide.

NOTE:

 Some of the labels supplied with the pack are for use in multi-zone applications.

5.3 Binding an HR80 Radiator Controller to the Room Thermostat

1.

  Press the bind button (

1

) for approximately one second and release. When the 

button  is  released,  the    symbol  flashes  and  the  software  version  number  is 

displayed for 30 seconds.

2.

  Move the room thermostat slider to the 

OFF

 position and press the     and   buttons 

together along with the   button. The unit will display InSt and ‘CONTROL BINDING’.

3.

  Press the green button to send the binding signal out to the radiator controller.

4.

  The radiator controller will display 

 once the signal has been received.

If several radiator controllers are to be controlled simultaneously in one room:

 

1.

  Press  the  bind  button  on  all  the  radiator  controllers  to  be  bound  to  the  room 

thermostat. The   symbol flashes continuously on the display of the radiator controller. 

2.

  Move the room thermostat slider to the 

OFF

 position and press the     and   buttons together along 

with the   button. The unit will display InSt and ‘CONTROL BINDING’.

3.

  Press the green   button to send the binding signal out to the radiator controllers. 

4.

  The radiator controllers will display 

 once the signal has been received. The set temperature at the 

radiator controller is automatically set to 20°C.

NOTE:

 The radiator controller can take up to 4 minutes to receive data from the room thermostat.

1

Содержание BDR91

Страница 1: ...ual system packs are separated or mixed with other pre configured system packs during installations please refer to section 5 1 Binding Rebinding Procedure to bind the desired units together and allow them to communicate with each other Table of Contents Section Page 1 Installation Information 2 2 Installing the CM900 Wireless System 3 2 1 Installing the Relay Box 3 2 2 Installing the Room Thermos...

Страница 2: ... strength of the RF signal reaching the Relay Box depends on the number of walls and ceilings separating it from the room thermostat as well as the building construction the diagram below illustrates an example of typical signal strength reduction Walls and ceilings reinforced with steel or plasterboard walls lined with metal foil reduce the RF signal significantly more Once a position is selected...

Страница 3: ...iance considerations Keep AC mains supply load cables separate from signal wiring Refer to Code of Practice standards EN61000 5 1 and 2 for guidance NOTE The Relay Box contains no user serviceable parts It should be opened and installed by qualified installer only WARNING Electrostatic sensi tive device Do not touch the circuit board NOTE All wiring must be in accordance with IEE regulations CAUTI...

Страница 4: ...he green button to confirm 2 2 2 RF Communication Check Test Mode To check the RF communication hold the room thermostat about 2 3 metres from the installed Relay Box Move the slider on the room thermostat to the OFF position then press the and buttons together with the button for 3 seconds The unit will display TEST TRANSMIT and it will send test signals to the Relay Box flashing the green LED on...

Страница 5: ...der switch to the MAN mode 4 Adjust the setpoint up to the maximum 35 C by pressing the button The boiler should come on green LED ON on Relay Box after a few seconds and the symbol appears on the room thermostat LCD display 5 Set the slider switch to the OFF mode The boiler will go off green LED OFF on Relay Box after a few seconds and the symbol disappears 6 Check the system operation by moving ...

Страница 6: ...iod of 1 hour the red LED will illuminate to indicate that no RF messages have been received during the last hour The Relay Box will also enter the failsafe mode as selected in Installer Mode see section 4 2 BDR91 Relay Box Fail Safe Mode Setup To allow manual control of the Relay Box output manual override is available in fail safe mode When RF communication is restored the Relay Box will automat...

Страница 7: ...o accept the change 6 Attach appropriate label to the Relay Box to indicate the selected fail safe mode IMPORTANT To enable the frost protection when RF communication is lost select the fail safe mode 1 For systems with separate frost protection thermostat or where frost protection is not required select fail safe mode 0 Move the slider switch to the OFF mode Press and hold the button and the two ...

Страница 8: ...ature is factory enabled To enable Set parameter 3 tC category 1 to 1 Temperature Offset If the thermostat is located in a particularly hot cold location for reliable signal transmission reasons then the measured displayed temperature can be adjusted by 3 C This is useful if the homeowner wants the reading to match another appliance temperature display Set parameter 12 tO category 1 to the require...

Страница 9: ...grammed To restore the factory profile set to 1 Auto Summer Winter Time Change 3 tC 1 Auto Summer Winter Time Change Enabled 0 Auto Summer Winter Time Change Disabled LCD Backlighting 5 bL 1 Backlighting Enable 0 Backlighting Disabled Upper Temp Limit 6 uL 35 35 C Upper Temp Limit 21 to 34 21 C to 34 C adjustment in 1 C steps Lower Temp Limit 7 LL 5 5 C Lower Temp Limit 5 to 21 6 C to 21 C adjustm...

Страница 10: ...ed 1 Pump exercise enabled System Synchronisation 6 Sn 0 Standard operation of the Room Unit 1 Room unit configured as Synchroniser Loss of Communications Instruction 7 LC 0 Relay Off 1 Relay 20 on 80 off The following Parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating controls and Wireless Radiator controls For more information please contact H...

Страница 11: ... systems and the CM927 921 room thermostat is compatible with a variety of other Honeywell products including HR80 radiator controllers see below and HCE80 underfloor heating controllers If you intend to use it in this way additional installation and user instructions can be obtained by contacting the address at the end of this guide NOTE Some of the labels supplied with the pack are for use in mu...

Страница 12: ... LED is on and the green one is flashing once every 3 sec on the Relay Box Incorrect or incomplete binding procedure Incorrect position of the room thermostat during binding Repeat the binding procedure Repeat the binding procedure keeping approx 1 m distance between the Relay Box and the room thermostat The red LED on the Relay Box is illuminated Communication loss The Relay Box receives no RF me...

Отзывы: