background image

CM900 Wireless 

Installation Guide

CM927 / CM921 Wireless Programmable 
Room Thermostat & BDR91 Relay Box

Description

The  Honeywell  CM900  Wireless  (CM927  or 

CM921)  is  a  modern  wireless  programmable 

room  thermostat  based  on  Honeywell’s  proven 

programming  philosophy.  To  further  improve  the 

ease of use, this product includes an extra large 

LCD display with backlighting and LoT Technology 

to assist customers during daily use.
The  CM927/921  room  thermostat  communicates 

with  the  BDR91  Relay  Box  on  an  868MHz  Radio 

Frequency  (RF)  band  to  control  a  single  heating 

system  component  such  as  a  boiler,  pump  or 

zone valve. Neither product will communicate with 

other RF products that use different frequencies or 

communication protocols.

Note:  The  RF  link  between  the  individual  room 

thermostat  (CM927/921)  and  Relay  Box  (BDR91) 

in  system  packs  provided  by  Honeywell  is  pre-

configured  at  the  factory  and  therefore  SHOULD 

be  installed  at  the  same  site.  This  makes  the 

installation process fast and easy, but if products 

from  individual  system  packs  are  separated,  or 

mixed  with  other  pre-configured  system  packs 

during  installations  please  refer  to  section 

5.1 

Binding / Rebinding Procedure

 to bind the desired 

units together and allow them to communicate with 

each other.

Table of Contents

Section 

Page

1) Installation Information ................................. 2

2) Installing the CM900 Wireless System ......... 3

 

2.1 Installing the Relay Box

 ................................... 3

  2.2 Installing the Room Thermostat

 ........................ 4

    2.2.1 Power Up

 ............................................... 4

    2.2.2 RF Communication Check

 ........................ 4

    2.2.3 Locating the Room Thermostat

 ................. 5

  2.3 System Check

................................................ 5

3) Basic Operation of the System ..................... 6

 

3.1 Automatic Operation

 ....................................... 6

 

3.2 Temporary Manual Override

 ............................. 6

 

3.3 Communication Loss

 ...................................... 6

4) Installer Mode ................................................. 6

 

4.1 Entering Installer Mode

 ................................... 7

 

4.2 BDR91 Relay Box Fail-Safe Mode Setup

 ............ 7

 

4.3 Using the Room Thermostat for Specific Applications

 .. 8

  4.4 Using the Special Features of the Room Thermostat

 .. 8

  4.5 Installer Parameters Table

 ............................... 9

    4.5.1 Category 1 - Room Thermostat Settings

 ..... 9

    4.5.2 Category 2 - System Settings

 .................. 10

5) Additional Installation Information ............. 11

  5.1 Binding / Rebinding Procedure

 ...................... 11

  5.2 Multi-Zone System

 ........................................ 11

  5.3 Binding an HR80 Radiator Controller
     to the Room Thermostat

 ................................ 11

6) Trouble Shooting .......................................... 12

  6.1 Trouble Shooting Guide

 ................................. 12

  6.2 Diagnostics Mode

 ........................................ 12

50039987-003 A

Содержание BDR91

Страница 1: ...ual system packs are separated or mixed with other pre configured system packs during installations please refer to section 5 1 Binding Rebinding Procedure to bind the desired units together and allow them to communicate with each other Table of Contents Section Page 1 Installation Information 2 2 Installing the CM900 Wireless System 3 2 1 Installing the Relay Box 3 2 2 Installing the Room Thermos...

Страница 2: ... strength of the RF signal reaching the Relay Box depends on the number of walls and ceilings separating it from the room thermostat as well as the building construction the diagram below illustrates an example of typical signal strength reduction Walls and ceilings reinforced with steel or plasterboard walls lined with metal foil reduce the RF signal significantly more Once a position is selected...

Страница 3: ...iance considerations Keep AC mains supply load cables separate from signal wiring Refer to Code of Practice standards EN61000 5 1 and 2 for guidance NOTE The Relay Box contains no user serviceable parts It should be opened and installed by qualified installer only WARNING Electrostatic sensi tive device Do not touch the circuit board NOTE All wiring must be in accordance with IEE regulations CAUTI...

Страница 4: ...he green button to confirm 2 2 2 RF Communication Check Test Mode To check the RF communication hold the room thermostat about 2 3 metres from the installed Relay Box Move the slider on the room thermostat to the OFF position then press the and buttons together with the button for 3 seconds The unit will display TEST TRANSMIT and it will send test signals to the Relay Box flashing the green LED on...

Страница 5: ...der switch to the MAN mode 4 Adjust the setpoint up to the maximum 35 C by pressing the button The boiler should come on green LED ON on Relay Box after a few seconds and the symbol appears on the room thermostat LCD display 5 Set the slider switch to the OFF mode The boiler will go off green LED OFF on Relay Box after a few seconds and the symbol disappears 6 Check the system operation by moving ...

Страница 6: ...iod of 1 hour the red LED will illuminate to indicate that no RF messages have been received during the last hour The Relay Box will also enter the failsafe mode as selected in Installer Mode see section 4 2 BDR91 Relay Box Fail Safe Mode Setup To allow manual control of the Relay Box output manual override is available in fail safe mode When RF communication is restored the Relay Box will automat...

Страница 7: ...o accept the change 6 Attach appropriate label to the Relay Box to indicate the selected fail safe mode IMPORTANT To enable the frost protection when RF communication is lost select the fail safe mode 1 For systems with separate frost protection thermostat or where frost protection is not required select fail safe mode 0 Move the slider switch to the OFF mode Press and hold the button and the two ...

Страница 8: ...ature is factory enabled To enable Set parameter 3 tC category 1 to 1 Temperature Offset If the thermostat is located in a particularly hot cold location for reliable signal transmission reasons then the measured displayed temperature can be adjusted by 3 C This is useful if the homeowner wants the reading to match another appliance temperature display Set parameter 12 tO category 1 to the require...

Страница 9: ...grammed To restore the factory profile set to 1 Auto Summer Winter Time Change 3 tC 1 Auto Summer Winter Time Change Enabled 0 Auto Summer Winter Time Change Disabled LCD Backlighting 5 bL 1 Backlighting Enable 0 Backlighting Disabled Upper Temp Limit 6 uL 35 35 C Upper Temp Limit 21 to 34 21 C to 34 C adjustment in 1 C steps Lower Temp Limit 7 LL 5 5 C Lower Temp Limit 5 to 21 6 C to 21 C adjustm...

Страница 10: ...ed 1 Pump exercise enabled System Synchronisation 6 Sn 0 Standard operation of the Room Unit 1 Room unit configured as Synchroniser Loss of Communications Instruction 7 LC 0 Relay Off 1 Relay 20 on 80 off The following Parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating controls and Wireless Radiator controls For more information please contact H...

Страница 11: ... systems and the CM927 921 room thermostat is compatible with a variety of other Honeywell products including HR80 radiator controllers see below and HCE80 underfloor heating controllers If you intend to use it in this way additional installation and user instructions can be obtained by contacting the address at the end of this guide NOTE Some of the labels supplied with the pack are for use in mu...

Страница 12: ... LED is on and the green one is flashing once every 3 sec on the Relay Box Incorrect or incomplete binding procedure Incorrect position of the room thermostat during binding Repeat the binding procedure Repeat the binding procedure keeping approx 1 m distance between the Relay Box and the room thermostat The red LED on the Relay Box is illuminated Communication loss The Relay Box receives no RF me...

Отзывы: