Honeywell GmbH
8
MU1H-1252GE23 R1015
GB
9. Disposal
• DZR brass housing
• Valve cartridge in high-grade synthetic material
• Outlet check valve in high-grade synthetic material for
connection size
1
/
2
" - 1
1
/
2
", outlet check valve in dezincifi-
cation resistant brass for connection size 2"
• Brass ball valves
• Sealing elements made of elastomer materials suitable for
drinking water
• Discharge connection in high-grade synthetic material
10. Troubleshooting
Observe the local requirements regarding correct waste
recycling/disposal!
Disturbance
Cause
Remedy
Discharge valve opens without
apparent reason
Pressure strokes in water supply system Install a pressure reducing valve upstream the
backflow preventer
Fluctuating inlet pressure
Install a pressure reducing valve upstream the
backflow preventer
Cartridge insert is contaminated
Remove cartridge insert and exchange it
Discharge valve don’t close
Deposits on valve seat
Remove cartridge insert and clean or exchange it
Damaged ’o’ring
Remove cartridge insert and exchange it
Leaky discharge valve
Remove cartridge insert and clean or exchange it
Flow is too low
Inlet strainer is blocked
Remove strainer and clean it