Honeywell Aquastat L4006 Скачать руководство пользователя страница 9

L4006,7,8; L6006,7,8 AQUASTAT

®

 CONTROLLERS

9

60-2104—10

Fig. 6. Internal view of L6006A.

Installing Direct Immersion Models 
(L4006C, L6006B)

Models that provide for direct immersion of the sensing 

element into the boiler include a bulb compression fitting 

assembly instead of an immersion well. Install the fitting in the 

boiler tapping as follows:

1.

Be sure the sealing washer is in place as shown in 

Fig. 7. Make sure that the spud of the bulb compression 

fitting is screwed in tightly enough to prevent leaking.

Fig. 7. Direct immersion model 

with fitting partially removed.

2.

Insert the immersion sensing bulb through the bulb 

compression fitting. Adjust the adapter clamp so that the 

clamp fits over the groove at the opening of the bulb 

compression fitting.

3.

Tighten the adapter clamp screws so that the Aquastat 

Controller is firmly attached to the bulb compression 

fitting.

Mounting Remote Bulb Models 

(L4008A,B,E; L6008A,G,H)

The remote temperature-sensing bulb can either be installed in 

an immersion well (See Fig. 8) that extends into the boiler or 

tank, or it can be directly immersed in the controlled medium 

(See Fig. 9). For installations that do not use a well, secure the 

remote bulb with a bulb compression fitting (See Fig. 10), or 

capillary compression fitting. (See Fig. 11).

Order well, well adapter, bulb compression fitting or capillary 

compression fitting separately. See form no. 68-0040, Wells 

and Fittings for Temperature Controllers. If used, well must 

snugly fit sensing bulb for the best thermal response. Insert 

bulb until it rests against the bottom of the well. Hold it there 

while tightening the tubing clamp. (See Fig. 8).

The boiler manufacturer usually provides a tapping for the 

insertion of the Aquastat Controller sensing element. This 

tapping should be located at a point where typical water 

temperature can be measured. Never locate the bulb or 

protecting immersion well close to a hot or cold water inlet or a 

steam coil.

If the system is filled, drain system to a point below the boiler 

tapping, or wherever the sensing bulb is to be installed.

The bulb can also be installed in the supply line of an indirect 

water heater, in the direct water heater itself, or in the feed 

riser, about 6 in. (153 mm) above the boiler. If the riser is 

valved, the bulb can be installed between the boiler and the 

valve.

NOTE: Do not make sharp bends or kinks in the capillary. 

Make bends no sharper than 1 in. (25 mm) radius.

After installing the controller, carefully coil the excess capillary 

at the bottom of the controller case.

Mounting Immersion Well 

1.

Screw the well into the boiler, tank, or pipe tapping.

2.

Insert the bulb in the well, pushing the tubing until the 

bulb bottoms in the well.

3.

Attach the retainer clamp to the end of the well spud. 

Loosen the draw nut and spread the jaws of the clamp 

with the screwdriver if necessary. (See Fig. 8).

4.

With the retainer clamp attached to the well spud (be 

sure the jaws of the clamp hook over the ridge at the end 

of the spud, as shown at points A in Fig. 8), adjust the 

tubing to fit through the retainer clamp groove, as shown 

at point B in Fig. 8.

5.

Tighten the draw nut so that the retainer clamp is firmly 

attached to the well spud and the tubing is held securely 

in place.

M8806A

SETPOINT

INDICATING DIAL

DIFFERENTIAL

ADJUSTMENT

WHEEL

ADAPTER CLAMP

SCREWS

INSERTION

ELEMENT

WITH VERTICAL MOUNTING OF

IMMERSION WELL, ELEMENT IS 

ATTACHED TO BOTTOM OF THE 

CASE.

SELECT MODELS HAVE SCREW 

TERMINAL, NOT TAB TERMINAL.

1

2

2

1

M8774A

SENSING BULB

BULB COMPRESSION

FITTING

SEALING WASHER

ADAPTER CLAMPS

FIT OVER 

GROOVE

SPLIT SLEEVE

ADAPTER 

CLAMP

Содержание Aquastat L4006

Страница 1: ... and surface mounting L4008 L6008 include remote bulb for mounting controller at a location away from the sensing element Totally enclosed Micro Switch snap acting switches operate on temperature rise to set point Models calibrated for high limit use are also suitable for low limit control if a separate high limit controller is used Visible control point scale and external adjustment screw permit ...

Страница 2: ...handling and maximum replacement value Specifications of SUPER TRADELINE and TRADELINE controls are the same as those of standard models except as noted below SUPER TRADELINE Model L6006A Aquastat Controller SUPER TRADELINE Features SUPER TRADELINE package with cross reference label and special instructions Factory set stop at 240 F 116 C Vertical or horizontal mount Tube of heat conductive compou...

Страница 3: ...ing and Bulb See Fig 5 Accessories and Parts 137536A Scale Lock Assembly Includes one 137536 767 Scale Lock and one 80844C 767 Screw No 3 48 x 3 16 5 mm Q615A1004 Weatherproof Enclosure for remote bulb devices only 107408 Heat Conductive Compound 4 oz can 104488 Spring Clip stainless steel 124904 Well Adapter Immersion Well Assemblies and Compression Fittings See form no 68 0040 Wells and Fittings...

Страница 4: ...oximate immersion well dimensions in inches mm for all models except L4006C and L6006B Fig 5 Approximate boiler fitting and bulb dimensions in inches mm for L4006C and L6006B M8958A 7 8 IN 22 MM STANDARD KNOCKOUT 2 1 25 2 51 5 5 8 136 2 3 4 70 2 51 C L 1 2 14 IN NPT 7 16 11 3 76 1 1 2 38 M8789A 1 2 OR 3 4 14 IN NPT 3 8 10 3 76 1 5 16 33 M8799A ...

Страница 5: ...crew L4006B Circulator 100 F to 240 F 38 C to 116 C 5 F 3 C fixed or 5 F to 30 F 3 C to 17 C adjustable Horizontal Makes TRADELINE model available Insulation depth 1 1 2 in or 3 in 38 mm or 76 mm NPT brass spud 3 4 in 19 mm Screw in front of case on dial suitable for Powerpile control Factory set stop at 240 F 116 C L4006C High or low limit 65 F to 200 F 18 C to 93 C 3 1 2 F 2 C fixed Horizontal d...

Страница 6: ...1 7 m 8 1 2 ft 2 6 m or 10 ft 3 0 m Factory set scale stops at 120 170 or 200 F 49 77 or 93 C Celsius scale markings Front cover screw L4008B Circulator 100 F to 240 F 38 C to 116 C 5 F 3 C fixed or 5 F to 30 F 3 C to 17 C adjustable Remote bulb direct immersion Makes Capillary 5 1 2 ft 1 7 m L4008Eb High limit 40 F to 80 F 4 C to 27 C or 130 F to 270 F 54 C to 132 C Manual reset Remote bulb Break...

Страница 7: ...limit 65 F to 200 F 18 C to 93 C 5 F 3 C fixed or 5 F to 30 F 3 C to 17 C adjustable Horizontal or vertical surface mounted TRADELINE model available Strap on surface mount L6007A Circulator and low limit or high limit 40 F to 180 F 4 C to 82 C Fixed Horizontal or vertical Insulation depth 1 1 2 in or 3 in 38 mm or 76 mm L6008A Circulator and low limit cooling 100 F to 240 F 38 C to 116 C or 30 F ...

Страница 8: ...st the bottom of the well and to hold the outer end of the bulb firmly in contact with the side of the well Wipe off excess compound The manufacturer usually provides a tapping for insertion of the controller sensing element This tapping is located at a point where typical water temperature can be measured Depending on the model the element is inserted in an immersion well through a boiler fitting...

Страница 9: ... insertion of the Aquastat Controller sensing element This tapping should be located at a point where typical water temperature can be measured Never locate the bulb or protecting immersion well close to a hot or cold water inlet or a steam coil If the system is filled drain system to a point below the boiler tapping or wherever the sensing bulb is to be installed The bulb can also be installed in...

Страница 10: ...on the tubing in the order shown in Fig 11 Turn the brass washers so the slots are 180 degrees apart Fig 11 Capillary compression fitting Use with L4008 5 Slide the seal assembly into the fitting and tighten the packing nut Duct Mounting 1 Drill a 3 4 in 19 mm hole in the duct wall large enough to admit the sensing bulb into the holder 2 Using the holder as a template mark and drill holes for the ...

Страница 11: ...ase Bring out the bulb and tubing through a 3 4 in 19 mm hole in the outside wall avoiding sharp bends or kinks Leave excess tubing coiled near the case Do not make sharp bends near the case or bulb Slip the bulb through the supports in the shield Pinch the split supporting clip until it holds the bulb firmly in position If the seal off tube protrudes from under the shield bend it under as shown i...

Страница 12: ...iameter or larger for accurate temperature sensing Remove any insulation from the pipe Thoroughly scrape off all scale rust or paint Mount the controller using adjustable bracket provided Turn on power Wiring Disconnect power supply before beginning installation to prevent electrical shock or equipment damage All wiring must comply with local codes and ordinances regarding wire size type of insula...

Страница 13: ...PPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED L6006C USED AS HIGH LIMIT CONTROL L6006C USED AS AN OPERATING CONTROL R B OPENS R W CLOSES ON TEMPERATURE RISE M8960B PROTECTORELAY CONTROL HIGH LIMIT CONTROLLER CIRCULATOR AND LOW LIMIT CONTROL W R B 1 2 4 3 T T IGNITION BURNER MOTOR 24V THERMOSTAT SWITCHING RELAY CIRCULATOR LINE VOLTAGE LOW VOLTAGE 1 2 3 4 T T IGNITION BURNER L400...

Страница 14: ...fter a high limit shutdown L1 HOT L2 1 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED WHEN USING CIRCULATOR LOW LIMIT CONTROL REMOVE L1 L2 JUMPER 2 L6006 CIRCULATOR AND LOW LIMIT CONTROL L1 L2 3 T T R W B B R C1 C2 B1 B2 SERIES 80 THERMOSTAT L8148A CIRCULATOR PILOTSTAT LINE VOLTAGE GAS CONTROL OIL BURNER RELAY LINE VOLTAGE TERMINALS 1 1 2 2 1 2 M8783C LOW VOLTAGE LIN...

Страница 15: ...e boiler manufacturer recommendations To adjust models with adjustable differential rotate the wheel on the back of the snap switch See Fig 32 until the desired reading is aligned with the V notch in the frame The wheel provides an adjustment from 5 F to 30 F 3 C to 17 C Replace the cover on the Aquastat Controller Fig 31 Adjusting the differential TEMPERATURE RISE SETPOINT ADJUSTABLE LEFT SWITCH ...

Страница 16: ...mperature than indicated on the dial setting lower the dial setting the number of degrees listed in Table 3 Table 3 Temperature Adjustments EXAMPLE In the example shown in Fig 33 the L6008A case is located in a room with a lower temperature than the controlled space Adjusting the controlled space setting dial setting is necessary to compensate for the temperature difference of 35 F 20 C between th...

Страница 17: ...tems with a pressure relief valve Check to make certain that the Aquastat Controller is properly installed and adjusted Put the system into operation and observe the action of the controller through several cycles to make certain it provides proper control of the system as described in the OPERATION section Make any additional adjustments necessary for assuring comfort requirements ...

Страница 18: ... be a carcinogen by either OSHA NTP IARC or ACGIH Section 4 First Aid Measures Eye Contact Flush eyes with water for 15 minutes Remove any contact lenses and continue to flush Obtain medical attention if irritation develops and persists Skin Contact Remove excess with cloth or paper Wash thoroughly with mild soap and water Obtain medical attention if irritation develops and persists Ingestion Cont...

Страница 19: ... Specific Gravity 0 86 Section 10 Stability and Reactivity Stability Stable Reactivity Hazardous polymerization will not occur Incompatibilities Strong oxidizing agents and halogens Hazardous Decomposition Products Carbon dioxide carbon monoxide Section 11 Toxicology Information No data available Section 12 Ecological Information Chemical Fate Information Hydrocarbon components will biodegrade in ...

Страница 20: ...ywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com L4006 7 8 L6006 7 8 AQUASTAT CONTROLLERS U S Registered Trademark 2006 Honeywell International Inc 60 2104 10 J I Rev 12 06 ...

Отзывы: