AQ252 Universal Injection/Mixing Boiler Reset Control Panels

69-1986—02

20

3.

Turn up the setpoint of one of the thermostats associated 
with the Boiler (Primary) loop.
a. The zone valve or pump associated with that zone 

turns on.

b. The Boiler T-T relay activates (Boiler displays in the 

demands section of the LCD screen), and the Boiler 
pump relay activates (PRIMary displays in the 
outputs section of the LCD screen). 

NOTE:

See Fig. 22 on page 17 for the demands and outputs 
display areas on the LCD.

c. Depending on the settings for the AUX.PUMP (line 

voltage rated dry contacts) and the AUX OUT (low 
voltage rated dry contacts), either or both of these 
relays may also close.

4.

Turn down the setpoint of one thermostat. The zone 
valve or pump associated with that zone should turn off. 
The Boiler T-T and Boiler pump relay outputs should de-
activate.

5.

Repeat steps 3 and 4 for all zones associated with the 
Boiler (Primary) loop to verify that each zone is operating 
correctly. Thermostats may be tested individually or all 
together to accelerate the check out process.

6.

Turn up the DHW Aquastat to simulate a call for hot 
water.
a. If the DHW device is a pump, the DHW relay output 

energizes immediately. The Boiler pump relay 
remains off.

b. If the DHW device is a valve, the Boiler pump relay 

energizes after a delay to allow the zone valve to 
fully open. This delay is selected from the 
EQUIPMENT SETUP>DHW>DHW VLV.OP menu 
option.

c. Turn up the setpoint of one of the AQ1000 zone 

thermostats.
(1) If the DHW relay is configured to control a pump, 

and DHW PRIOrity is selected, the Boiler and the 
associated zone pump’s relay remain off.

(2) If the DHW relay is configured to control a valve, 

and DHW PRIOrity is selected, the Boiler pump 
activates after a delay for the DHW zone valve to 
open, but the associated zone relays remain off.

(3) If DHW PRIOrity is disabled, space heating zone 

pumps and valves should operate during a call for 
DHW.

7.

Turn down the DHW Aquastat to end the call for hot 
water. Space heating operation should continue (if DHW 
priority is disabled) or resume (if DHW PRIOrity is 
enabled).

8.

Repeat the preceding steps for all zones associated with 
the Secondary (Mixed temperature) loop. The only 
difference between operation of the Primary zones and 
the Secondary zones is that the Secondary pump and 
the Mixing Device (Injection Pump or Motorized Mixing 
Valve) energize on a call for heat from a Secondary zone 
but not from a Primary zone.

6 PURGE AIR FROM ALL SYSTEM 

AND ZONE PIPING

The PURGE operation on the AQ252 Control Panel allows the 
installer to purge all zones (loops) sequentially, or each zone 
individually, for a period of time, PURGE TIME, which selected 
from the EQUIPMENT SETUP>TEST AND PURGE>PURGE 
sub-menu. The purge time can be adjusted in increments of 1 
minute, up to a maximum of 30 minutes per loop to be purged.

After you have defined which loops to purge (all loops, or an 
individual loop) and for how long (using the AQ252’s menus), 
position the indicator arrow 

(←)

 beside the START PURGE 

option and press the OK button. The START PURGE display 
will change to STOP PURGE and the AQ252 display begins 
counting down the time remaining for the purge cycle. 

Purging All Loops

When the purge time has elapsed for the first loop, the control 
proceeds to the next loop and performs the purge operation on 
each loop in sequential order. After all selected loops have 
been purged, the display shows PURGE COMPLETED.

7 DOCUMENT AND KEEP A RECORD 

OF ALL SYSTEM SETTINGS

After the AQ252 Series Control Panel and any AQ255/AQ257 
Expansion Zoning Panels have been set up and the entire 
hydronic installation is operating properly, it is important to 
document all the system settings for future reference.

Job Records

All AQ2000 Series Panels are shipped with Installation Job 
Records for documenting these settings. These should be filled 
out completely and saved in the Installing Contractor’s files.

NOTES: There are two classes of settings used by the AQ252 

to control the operation of the heating system, Zone 
Settings and System (or Equipment) Settings. Both 
types of settings are stored in non-volatile memory 
and are not lost following an extended power 
disruption.

WHEN USING AQ1000 THERMOSTATS

1.

Zone Settings are designed to be adjustable by the 
user or the installer and are stored in the faceplate 
of each zone's AQ1000 thermostat. These settings 
are not saved with the SAVE SETUP operation. If 
the faceplates of two AQ1000 thermostats are 
switched, the settings (setpoints, zone minimum, 
zone maximum, etc.) will also be switched. 

2.

System Settings are designed to be adjustable 
only by the system installer and are stored in the 
AQ151 Control Module. These are the settings 
that are saved with the SAVE SETUP operation.

SAVE Feature

In addition to the hardcopy Installation Job Records, the 
AQ252 Control Panel has a convenient SAVE feature that 
allows the installing contractor to save the specific equipment 
setting for this installation in the AQ252’s memory for future 
recall, in case the system’s settings are inadvertently changed. 
This feature is found in the EQUIPMENT SETUP > 
SAVE/RESTORE sub-menu.

There are three levels of settings in the AQ252’s memory – 
CURRENT, FACTORY and SETUP.

CURRENT

 settings are the settings that are currently 

displayed in any of the menus and are the settings that the 
AQ252 uses to operate. Any time a value is changed in any 
of the menus, the CURRENT settings are changed and 
these new settings are instantly used by the AQ252 Control 
Panel.

Содержание AQ252 Series

Страница 1: ...tor at 77 F 25 C 0 5 F 0 3 C Lead length 15 ft 4 6 m up to 500 ft 150 m using 18 AWG or larger wire beta 3892 Dimensions HxWxD 8 x 16 1 2 x 3 3 8 in 20 3 x 42 x 8 5 cm approximate Weight 4 9 lb 2 3 kg Approvals Canadian Standards Association Certified File No LR76030 1 INSTALLATION PREPARATION NOTES Throughout these instructions the following terminology conventions are used AQ155 refers to the AQ...

Страница 2: ...ry loop as well as coordinating the overall operation of the hydronic system 3 One of two different 4 zone Zoning Modules AQ15740B part of the AQ25244B Control Panel for zoning with 24 Vac zone valves with end switches AQ15540B part of the AQ25242B Control Panel for zoning with either line voltage circulators or 24 Vac zone valves without end switches AQ252 Control Panels can control a maximum of ...

Страница 3: ... Remove wire channel plugs from the AQ252 Control Panel and any Expansion Zoning Panels see Fig 3 2 Mount Expansion Zoning Panel on the right hand end of the AQ252 Control Panel Install two top screws of the Expansion Zoning Panel ensuring it is level with the adjoining Control Panel and install two lower screws 3 Reverse wire channel plugs and re insert them into their slot to form a wiring chann...

Страница 4: ...ixing Boiler Reset Control Panels 69 1986 02 6 Fig 3 Orientation of wire channel plugs for creating pass through wire channel and for joining Control Panel to Expansion Zoning Panels M23733A WIRE CHANNEL PLUGS WIRE CHANNEL PLUGS ...

Страница 5: ...l Module as well as the R and C inputs of the Zoning Module The B B Exp Bus terminals 26 and 27 of the Control Module are wired to the B B Exp Bus IN terminals of the Zoning Module Beginning with the top left of Fig 4 and moving clockwise around the panel wire components to the AQ252 Control Panel and Expansion Zoning Panels if installed in the following six steps Step 1 Transformer Wiring Step 2 ...

Страница 6: ...plicing SECONDARY MIXED LOOP SUPPLY SENSOR The secondary sensor should be installed on the secondary mixed water piping far enough downstream of the mixing device that the return water from the mixed loop and the boiler loop water are sufficiently well mixed but before it flows through a branch leading to a zoning pump zoning valve or manifold The sensor used for the secondary loop is the same typ...

Страница 7: ...utes of a call for heat and then allows the space heating needs to be added in for the next 30 minutes This cycle continues until the call for heat is satisfied DOMESTIC HOT WATER Wire the DHW terminals 15 and16 to the Aquastat or thermostat on the domestic hot water tank DHW priority allows only DHW heat for the first 30 minutes of a call for DHW and then allows the space heating needs to be adde...

Страница 8: ...c non communicating thermostats or AQ1000 communicating thermostats 1 Using low voltage thermostat wire connect one thermo stat from each zone to the corresponding THERMO STATS Zone X inputs on top of the Zoning Module see Fig 9 2 If there are additional zones on Expansion Zoning Panels connected to this Zoning Module run low voltage thermostat wiring from the B B Exp Bus Out connection terminals ...

Страница 9: ... Module IMPORTANT If low voltage zone valves are used with the AQ25242B Control Panel the supplied Low Voltage Output sticker shown in Fig 11 must be applied over the line voltage output sticker see Fig 10 that is already attached to the Zoning Module Fig 11 Low voltage output sticker Fig 12 Wiring an AQ15540B Zoning Module for use with low voltage zone valves without end switches 2 Low voltage zo...

Страница 10: ...o a set of dry contacts such as a zone valve motor s end switch If power is applied to these contacts for example by running line voltage through the zone valves end switches to bring on a circulator feeding those valves the internal circuitry of the Zoning Module will be damaged in which case the warranty for this product will be voided Fig 14 Wiring of additional low voltage VA capacity THERMOST...

Страница 11: ... zone valve wire the primary of a spud mounted transformer 115V to 24V to the DHW line voltage contacts and connect the low voltage zone valve to the secondary terminals of this transformer A spud mounted transformer may be located in one of the conduit knockouts on the bottom of the AQ252 Control Panel Alternatively a 24 Vac zone valve can be connected to the Aux pump line voltage rated dry conta...

Страница 12: ...17 The ground wire of the pump can be connected to any of the 8 ground screw terminals located on the back surface of the Control Panel enclosure The secondary pump terminals energize only when a zone that has been designated as a secondary zone has a call for heat This enables the pump and the mixing device you have chosen for the loop control Set up is enabled in the EQUIPMENT SETUP PRI SEC sub ...

Страница 13: ...hey are suitable for the job rather than having to input all the settings from scratch Although these factory default values for the Control Module and each Zoning Module are suitable for many installations Honeywell recommends that they be reviewed and changed as necessary to get optimal performance of the hydronic system controlled by the AQ2000 Series products Zoning Module DIP Switch Location ...

Страница 14: ... Control Panel and the cover of each Expansion Zoning Panel NOTE The snap on DIP switch covers are designed so they cannot be removed exposing the DIP switches when the front cover of the AQ252 Control Panel is in place Table 2 AQ15540B Zoning Module Pump Zoning Module DIP Switch Arrangement DIP Switch Switch Description Label and Factory Settings 1 2 3 4 Zone Address The positions of these 4 DIP ...

Страница 15: ...ilable options one at a time LCD Display The LCD on the AQ252 Control Panel is used to Monitor system status and performance Select and or modify control settings for the hydronic system Diagnose and troubleshoot system problems The layout of the display is logical and simple to navigate The information displays so that the installer can see at a glance the system s operating temperatures as well ...

Страница 16: ...DHW sensor use Detail view is the factory default setting for the Home Page The choice of the Simple or Detail Home Page view is made from the USER MENU PREFERENCES TIME menu option The Home Page together with the System Status information a selection from the User Menu provides a service contractor extensive diagnostic information for troubleshooting the installation NOTES Home Page display upon ...

Страница 17: ...ws and v position the indicator arrow beside that output and press the button to begin testing Press the button to de activate the output relay and stop its test Any combination of outputs can be activated at the same time when testing the outputs When finished testing the outputs press the Menu button to return to the TEST AND PURGE sub menu TEST SENSORS When TEST SENSORS is selected the AQ252 LC...

Страница 18: ...URGE TIME which selected from the EQUIPMENT SETUP TEST AND PURGE PURGE sub menu The purge time can be adjusted in increments of 1 minute up to a maximum of 30 minutes per loop to be purged After you have defined which loops to purge all loops or an individual loop and for how long using the AQ252 s menus position the indicator arrow beside the START PURGE option and press the OK button The START P...

Отзывы: