Capabilities, Connection
13
Installation and Commissioning
Installation and commissioning of
the Transmitter may only be carried
out in accordance with this instruc-
tion manual and per applicable local
and national codes. Be sure to ob-
serve the technical specifications
and input ratings.
Before connecting the
APT2000TC-0(H)-00 Transmitter to
a power supply unit, make sure that
this is not capable of outputting
more than 40 Vdc (safe areas) /
30 Vdc (DIV 2).
Before connecting the
APT2000TC-0(H)-IS Transmitter
to a power supply unit, make sure
that this is an associated apparatus
(for input ratings refer to the Control
Drawing or the annex of the EC
Type Examination Certificate).
Do not use alternating current or
mains power supply!
When commissioning, a complete
configuration must be carried out.
For easier installation, the terminal strips are of a
plug-in design. The terminals are suitable for single
wires and flexible leads up to 2.5 mm
2
(AWG 14)
(see Pg. 9).
A connection example is shown on Pg. 14.