TB1

CURRENT DRAW:

• 50 mA + EXTENSION LOOP DRAW

DURING ACTUAL OPERATION.

• INCREASES TO 400 mA WHEN

EXTENTION LOOP SHORTENED 

INPUT POLLING LOOP (FROM CONTROL).
WHEN USING SUPPLEMENTARY POWER, ON
COMMERCIAL FIRE PANELS, DO NOT CONNECT
THE INPUT POLLING LOOP GROUND ON TERMINAL 7. 

NO CONNECTION 

4297

USE CONTROL PANEL’S

AUXILIARY POWER OR USE 

A SEPARATE POWER SUPPLY

TAKE CARE TO OBSERVE

POWER SUPPLY RATINGS.

+

SUPPLEMENTARY

POWER SUPPLY

+12VDC
POWER

NOTE

USE A CLASS II (POWER LIMITED) POWER
SUPPLY WHICH IS UL LISTED FOR THE
DESIRED FIRE AND/OR BURGLARY
APPLICATION. FOLLOW THE POWER SUPPLY'S
INSTRUCTIONS REGARDING BACKUP
BATTERY AND AC/BATTERY SUPERVISION
SIGNAL CONNECTIONS THAT APPLY TO THE
DESIRED APPLICATION.

GAUGE    LENGTH

#22        100 FT

#20        150 FT

#18        225 FT

#16        375 FT

WIRE RUN LENGTH
MUST NOT EXCEED:

4297-001-V0

 

Note:  See the Installation & Setup Guide for the control panel being used for specific power and wiring requirements. 

 

Figure 2.  Typical Supplementary Power Supply Connections 

 

 

CONTROL PANEL

INPUT POLLING LOOP

EXTENSION POLLING LOOP 

TO
OTHER
RPMS

polling_loop_005-V0

V-PLEX

DEVICE

V-PLEX

DEVICE

V-PLEX

DEVICE

V-PLEX

DEVICE

4297

 

 

Figure 3.  Connections Using One 4297 Module 

 

 

CONTROL PANEL

EXTENSION POLLING LOOP #1 

4297

4297

INPUT POLLING LOOP

polling_loop-006-V1

EXTENSION POLLING LOOP #2 

•  DO NOT CONNECT 4297 MODULES IN SERIES

(i.e., DO NOT CONNECT ONE MODULE'S EXTENSION
LOOP TO ANOTHER MODULE'S INPUT LOOP.)

DO NOT CONNECT MORE THAN EIGHT
4297 MODULES IN PARALLEL.

• 

V-PLEX

DEVICE

V-PLEX

DEVICE

 

Figure 4.  Typical Connections Using Multiple 4297 Modules 

 

CONFIGURATION GUIDELINES 

These guidelines apply to control panels that support V-Plex polling loop devices.  Some of these control panels 

may have additional limitations; refer to the control panel's Installation & Setup Guide for specific power and 

wiring requirements. 

Maximum number of devices: 

 

All input loops (combined) = 64 devices max. 

 

All input loops (combined) plus 

1

 output loop = 

11

9 devices max. 

Maximum wire length limits: 

Refer to Table 

1

 (at right) for wire length per gauge, 

and observe the maximum wire length limits. 

 

No individual wire run can exceed 2400 ft. max. 

 

1

 input loop plus 

1

 output loop (combined) = 4000 ft. max 

 

All input loops (combined) plus 

1

 output loop = 6400 ft. max 

Note:

 Reduce wire length by ½ if using unshielded  

wire in conduit, or if using shielded wire. 

Maximum Current: 

 

All input loops (combined) = 

1

28mA maximum current limit. 

 

Each output loop = 

1

28mA 

 

Any single wire run = 64mA 

Table 1 

Wire Gauge

 

Wire Length

 

#22

 

650 ft.

 

#20

 

950 ft.

 

#

1

8

 

1

500 ft.

 

#

1

6

 

2400 ft. 

Содержание ADEMCO 4297

Страница 1: ...d to connect fire alarm detectors to the ADEMCO Vista fire transmitter 4297 003 V1 9 8 7 6 5 4 3 2 1 TB1 EXTENSION POLLING LOOP CLASS B STYLE 3 MAX LINE IMPEDANCE 20Ω INPUT POLLING LOOP FROM CONTROL CLASS B STYLE 3 12VDC POWER INPUT FROM CONTROL PANEL OR A SUP PLEMENTAL POWER SUPPLY LISTED FOR THE APPLICATION NO CONNECTION FOR IMPEDANCES BELOW WHICH GROUND FAULTS WILL BE ANNUNCIATED REFER TO THE S...

Страница 2: ...nections Using One 4297 Module CONTROL PANEL EXTENSION POLLING LOOP 1 4297 4297 INPUT POLLING LOOP polling_loop 006 V1 EXTENSION POLLING LOOP 2 DO NOT CONNECT 4297 MODULES IN SERIES i e DO NOT CONNECT ONE MODULE S EXTENSION LOOP TO ANOTHER MODULE S INPUT LOOP DO NOT CONNECT MORE THAN EIGHT 4297 MODULES IN PARALLEL V PLEX DEVICE V PLEX DEVICE Figure 4 Typical Connections Using Multiple 4297 Modules...

Страница 3: ... radio and television reception It has been type tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules which are designed to provide reasonable protection against such interference in a residential installation However there is no guarantee that interference will not occur in a particular installation If this equipme...

Страница 4: ...ÊN7571V4lŠ N7571V4 11 13 Rev A 2 Corporate Center Drive Suite 100 P O Box 9040 Melville NY 11747 Copyright 2009 Honeywell International Inc www honeywell com security ...

Отзывы: