6.2.7
Manual address allocation via reader keypad, "stand alone" operating
mode
With this form of address allocation a
plausibility check
is not possible. This means that
an address collision may occur later during operation. (Double or multiple addressing).
Allocate address
Reconnect the reader only to the operating voltage.
Enter the address via the keypad (1 or 2 digit) and confirm with the
OK button (
3
). When the
operating voltage is interrupted, the address is saved in the reader.
Overwrite address
The address can be overwritten as long as the reader has not been linked by the controller and the
operating voltage is not interrupted.
Clear address
An address is
cleared
when the
keys
"1", "7"
and
"X"
are pressed simultaneously and keep
pressed whilst the operating voltage is re-applied.
An address can also be deleted in the programming mode „Stand alone“ (see 7.2)
Note:
If the reader is connected at a later stage to the controller, the entered address is
transmitted together with the serial number of the reader to the controller and stored.
6.2.8
Clear addresses
-
Via programming
-
or in "stand alone" operating mode (see 6.2.7)
-
or in "stand alone" programming mode (see Chapter 7.)
6.3
Keypad lighting
If permanent backlighting is desired, the brightness for the no-load status can be set in 16 stages
from "off" to "maximum brightness" via the programming of the controller or in the "stand alone"
programming mode, (see 7.4).
Maximum brightness during operation is not affected.