RM7885A 7800 SERIES RELAY MODULES

32-00215—01

4

1.

For proper subbase wiring and sequence chart, refer 
to Fig. 2. For other possible wiring hookups, see Fig. 
3 through 6.

2.

For proper remote wiring of the KDM, refer to the 
Specifications for the 2-line VDF KDM (65-0090), 
the 4-line LCD KDM (32-00110), Data ControlBus 
Module™ (65-0091) or Extension Cable Assembly 
(65-0131).

3.

Disconnect the power supply from the main discon-
nect before beginning installation to prevent electri-
cal shock and equipment damage. More than one 
disconnect may be required. 

4.

All wiring must comply with all applicable electrical 
codes, ordinances and regulations. Wiring, where 
required, must comply with NEC, Class 1 (Line Volt-
age) wiring.

5.

For recommended wire size and type, see Table 1.

6.

For recommended grounding practices, see Table 2.

7.

Recommended wire routing of leadwires:
a. Do not run high voltage ignition transformer 

wires in the same conduit with the flame 
detector, Data ControlBus Module™, or Remote 
Reset Module wiring.

b. Do not route flame detector, Data ControlBus 

Module™ or Remote Reset Module leadwires in 
conduit with line voltage circuits.

c. Enclose flame detector leadwires without armor 

cable in metal cable or conduit. 

d. Follow directions in flame detector, Data Control-

Bus Module™, or Remote Reset Module Instruc-
tions.

8.

For KDM, because the KDM is powered from a low 
voltage, energy limited source, it can be mounted 
outside of a control panel if it is protected from 
mechanical damage. 

NOTE:

A 13 Vdc power supply must be used any time 
more than one KDM is used. A maximum of two 
KDM, Data ControlBusª Modules or S7810B 
Multi-Drop Switch Modules are allowed in any 
combination.

9.

Maximum wire lengths:
a. RM7885A leadwires: The maximum leadwire 

length is 300 feet (91 meters) to terminal inputs 
(Control, Preignition Interlock, Running/Lock-
out Interlock, High Fire Switch and Low Fire 
Switch). 

b. Flame Detector leadwires: The maximum flame 

sensor leadwire length is limited by the flame 
signal strength.

c. Remote Reset leadwires: The maximum length of 

wire is 1000 feet (305 meters) to a Remote Reset 
pushbutton.

d. Data ControlBus Moduleª: The maximum Data 

ControlBus Module™ cable length depends on 
the number of system modules connected, the 
noise conditions and the cable used. The 
maximum length of all Data ControlBus Moduleª 
interconnecting wire is 4000 feet (1219 meters).

10.

Be sure loads do not exceed the terminal ratings. 
Refer to the label on the RM7885A or to the terminal 
ratings in Table 4.

Содержание 7800 SERIES

Страница 1: ... conventional knee or foot operated start stop station 3 Direct ignition oil burner or electrically ignited pilot using the S445A Start Stop Station which main tains electric ignition as long as the Start Switch is depressed up to 15 minutes This document provides installation and static checkout instructions Other applicable publications are SPECIFICATIONS Electrical Ratings See Table 3 Voltage a...

Страница 2: ...y with NEC Class 1 Line Volt age wiring 4 Loads connected to the RM7885A must not exceed those listed on the RM7885A label or the Specifications see Table 1 5 Limits and interlocks must be rated to simultane ously carry and break current to the ignition trans former pilot valve and main fuel valve s 6 All external timers must be listed or component recognized by authorities who have proper jurisdi...

Страница 3: ...on compatible 1000 series subbase this indi cates that you must Change out the subbase to a Q7800A2003 U or Q7800A2005 U Choose a compatible 1000 series relay module Relay Module and Subbase Compatiblity NOTE There are several different subbase models that can be purchased It is important to note which subbase is compatible with the relay module when purchasing new repair or replacement parts Seri...

Страница 4: ...me detector leadwires without armor cable in metal cable or conduit d Follow directions in flame detector Data Control Bus Module or Remote Reset Module Instruc tions 8 For KDM because the KDM is powered from a low voltage energy limited source it can be mounted outside of a control panel if it is protected from mechanical damage NOTE A 13 Vdc power supply must be used any time more than one KDM i...

Страница 5: ...isted pair with ground or five wire Belden 8723 shielded cable or equivalent Remote Reset Module 22 AWG two wire twisted pair insulated for low voltage Communication Interface ControlBus Module 22 AWG two wire twisted pair with ground Belden 8723 shielded cable or equivalent 13 Vdc full wave rectified transformer power input 18 AWG wire insulated for voltages and temperatures for given application...

Страница 6: ... short circuit Use wide straps or brackets to provide minimum length maximum surface area ground conductors If a leadwire must be used use 14 AWG copper wire Make sure that mechanically tightened joints along the ground path are free of nonconducting coatings and protected against corrosion on mating surfaces Signal ground KDM Data ControlBus Module Communications Interface ControlBus Module Use t...

Страница 7: ...D ALARM SILENCING SWITCH CLOSED INTERMITTENT PILOT SAFE START CHECK FLAME PROVING LED DISPLAY POWER PILOT FLAME MAIN PFEP POWER SAFE START POWER POWER LIMITS STOP STATION AND SILENCING SWITCH FLAME SIGNAL EC RM7885 M15109A 00 00 15 MINUTES L1 TO 6 9 8 10 FOR DIRECT SPARK IGNITION OIL OR GAS 8 MAIN VALVE L2 9 3 4 5 2 1 RM7785A 120 VAC 50 60 HZ EC7885A 220 240 VAC 50 60 HZ POWER SUPPLY PROVIDE DISCO...

Страница 8: ...PPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS SEE FLAME DETECTOR SPECIFICATION FOR CORRECT WIRING 220 240 VAC TO 120 VAC 10 VA MINIMUM STEP DOWN TRANSFORMER NOT PROVIDED REQUIRED TO DRIVE SHUTTER EC7885A ONLY ALARM L1 HOT L2 Q7800 4 1 2 2 1 LIMITS STOP S445A START STOP STATION START B A D C INTERNAL JUMPER DPST ALARM SILENCING SWITCH...

Страница 9: ...ROTECTION AS REQUIRED DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS SEE FLAME DETECTOR SPECIFICATION FOR CORRECT WIRING 220 240 VAC TO 120 VAC 10 VA MINIMUM STEPDOWN TRANSFORMER NOT PROVIDED REQUIRED TO DRIVE SHUTTER EC7885A ONLY ALARM ALARM L1 HOT L2 Q7800 4 1 2 2 1 LIMITS STOP S445A START STOP STATION START B A D C INTERNAL JUMPER DPST ALARM SILENCING SWITCH G L2 3 5 6 7 8 9 10 F L1 13 14 15 16 1...

Страница 10: ...ERMINALS SEE FLAME DETECTOR SPECIFICATION FOR CORRECT WIRING 220 240 VAC TO 120 VAC 10 VA MINIMUM STEPDOWN TRANSFORMER NOT PROVIDED REQUIRED TO DRIVE SHUTTER EC7885A ONLY ALARM L1 HOT L2 Q7800 4 FLAME DETECTOR 1 2 2 1 LIMITS STOP S445A START STOP STATION START B A D C INTERNAL JUMPER DPST ALARM SILENCING SWITCH FUEL PRESSURE SWITCH MANUAL VALVE 1 2 6 7 8 R W B R W B T T CONTROLLER HI LO OR MODULAT...

Страница 11: ...e all manual fuel shutoff valve s before starting these tests 2 Use extreme care while testing the system Line voltage is present on most terminal connections when power is on 3 Open the master switch before installing or removing a jumper on the subbase 4 Before continuing to the next test be sure to remove test jumper s used in the previous test 5 Replace all limits and interlocks that are not o...

Страница 12: ...l damaged or incorrectly sized wires 8 Replace faulty controllers limits interlocks actua tors valves transformers motors and other devices as required 9 Make sure normal operation is obtained for each required test before continuing the checkout 10 After completing each test be sure to remove the test jumper s WARNING Explosion Hazard Can cause severe injury death or property damage Be sure all m...

Страница 13: ...e inch 76 mm minimum to both sides of the RM7885A for electrical sig nal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blade terminals or bifurcated contacts IMPORTANT The RM7885A must be installed with a plug in motion rather than a hinge action Terminal No Description Ra...

Страница 14: ...e INITIATE sequence lasts for ten seconds unless the voltage or frequency tolerances are not met When not met a hold condition is initiated and displayed on the optional KDM for at least five seconds when met the INITIATE sequence restarts If the condition is not corrected and the hold condition exists for four minutes the RM7885A locks out Causes for hold conditions in the INITIATE sequence a AC ...

Страница 15: ...pplied via Run Test switch label seal It is intended to prevent and detect unauthorized access Modbus DDL Interface security Any conducts critical to device functionality DDL Modbus lines etc shall be physically protected installed outside public access since they could be damaged or tampered with by unauthorized people either accidentally or for purpose Modbus RS 485 DDL protocols do not support ...

Страница 16: ...Kromschröder and Maxon To learn more about our products visit ThermalSolutions honeywell com or contact your Honeywell Sales Engineer Honeywell Process Solutions Honeywell Thermal Solutions HTS 1250 West Sam Houston Parkway South Houston TX 77042 ThermalSolutions honeywell U S Registered Trademark 2019 Honeywell International Inc 32 00215 01 M S 08 19 Printed in Mexico ...