RM7885A 7800 SERIES RELAY MODULES

3

32-00215—01

Mounting of Remote Keyboard or 
Reset Module

To comply with CE EN60730 for remote mounting of the 
KDM and/or Remote Reset Module it is necessary to 
provide electrical separation using insulation at

  

least 

equivalent to double or reinforced insulation. 

This can be accomplished by either:

1.

Optically isolating the communication and/or 
remote reset lines from the control cabinet.

2.

Providing physical separation from the communica-
tion and/or remote reset lines using electrical con-
duit and a 204718A Remote Display Cover Assembly 
or other suitable enclosure that meets IP40 class of 
protection.

 

Mounting Wiring Subbase

1.

Mount the subbase in any position except 
horizontally with the bifurcated contacts pointing 
down. The standard vertical position is 
recommended. Any other position decreases the 
maximum ambient temperature rating. 

2.

Select a location on a wall, burner or electrical panel. 
The Q7800 can be mounted directly in the control 
cabinet. Be sure to allow adequate clearance for 
servicing, installation, access or removal of the 
RM7885A, expanded annunciator, keyboard display 
module, flame amplifier, flame amplifier signal 
voltage probes, run/test switch, electrical signal 
voltage probes and electrical field connections. 

3.

For surface mounting, use the back of the subbase 
as a template to mark the four screw locations. Drill 
the pilot holes. 

4.

Securely mount the subbase using four no. 6 screws 
(not provided).

NOTE:

You might receive an error code 101 (via KDM) if 
one of the following conditions exist:

a. The screws securing the relay to the subbase are 

not tight enough, re-tighten to insure there is no 
gap between the relay and the subbase. 

b. If you attempt to place a 2000 series relay on a 

non-compatible 1000 series subbase, this indi-
cates that you must:

Change out the subbase to a Q7800A2003/U 
or Q7800A2005/U

Choose a compatible 1000 series relay 
module

Relay Module and Subbase 
Compatiblity

NOTE:

There are several different subbase models that 
can be purchased. It is important to note which 
subbase is compatible with the relay module 
when purchasing new, repair or replacement 
parts. 

Series 1000 Relay Modules

All relay product codes that start with a 1 (example: 
EC7820A

1

026/U) can be used with existing subbase 

Q7800A1003/U and Q7800A1005/U. 

Series 2000 Relay Modules

All relay product codes that start with a 2 (example: 
EC7820A

2

026/U) must be used with subbase 

Q7800A2003/U and Q7800A2005/U.

Subbase Compatibility

Any Relay Module in the 1000 Series with a Software 
Revision level number starting with a "5" or greater will be 
compatible with all subbase models both installed and 
newly purchased. This includes (Q7800A1005/U, 
Q7800B1003/U), and the 2000 Series subbases 
(Q7800A2005/U, Q7800B2003/U).

See Fig. 1 for Software Revision Level number location on 
the label (located on the rear of the relay module). 

Any relay module in the new 2000 series will only be able 
to be installed on subbase Q7800A2005/U, 
Q7800B2003/U and will not be backward compatible with 
any Q7800A1003/U and Q7800A1005/U subbases 
already installed in the field. 

Fig. 1. Software revision location.

IMPORTANT

Make sure to check the relay model number and 
the software revision level on the relay. 

If you attempt to place a 2000 series relay on a non-

compatible 1000 series subbase, you will receive an error 
code of 101. This indicates that you must a) change out the 
subbase to a Q7800A2003/U or Q7800A2005/U or b) 
choose a compatible 1000 series relay module.

Wiring Subbase

WARNING

Electrical Shock Hazard.
Can cause severe injury, death or equipment 
damage.

Disconnect the power supply before beginning 
installation.

The internal block diagram of the RM7885A is shown in 
Fig. 1.

Содержание 7800 SERIES

Страница 1: ... conventional knee or foot operated start stop station 3 Direct ignition oil burner or electrically ignited pilot using the S445A Start Stop Station which main tains electric ignition as long as the Start Switch is depressed up to 15 minutes This document provides installation and static checkout instructions Other applicable publications are SPECIFICATIONS Electrical Ratings See Table 3 Voltage a...

Страница 2: ...y with NEC Class 1 Line Volt age wiring 4 Loads connected to the RM7885A must not exceed those listed on the RM7885A label or the Specifications see Table 1 5 Limits and interlocks must be rated to simultane ously carry and break current to the ignition trans former pilot valve and main fuel valve s 6 All external timers must be listed or component recognized by authorities who have proper jurisdi...

Страница 3: ...on compatible 1000 series subbase this indi cates that you must Change out the subbase to a Q7800A2003 U or Q7800A2005 U Choose a compatible 1000 series relay module Relay Module and Subbase Compatiblity NOTE There are several different subbase models that can be purchased It is important to note which subbase is compatible with the relay module when purchasing new repair or replacement parts Seri...

Страница 4: ...me detector leadwires without armor cable in metal cable or conduit d Follow directions in flame detector Data Control Bus Module or Remote Reset Module Instruc tions 8 For KDM because the KDM is powered from a low voltage energy limited source it can be mounted outside of a control panel if it is protected from mechanical damage NOTE A 13 Vdc power supply must be used any time more than one KDM i...

Страница 5: ...isted pair with ground or five wire Belden 8723 shielded cable or equivalent Remote Reset Module 22 AWG two wire twisted pair insulated for low voltage Communication Interface ControlBus Module 22 AWG two wire twisted pair with ground Belden 8723 shielded cable or equivalent 13 Vdc full wave rectified transformer power input 18 AWG wire insulated for voltages and temperatures for given application...

Страница 6: ... short circuit Use wide straps or brackets to provide minimum length maximum surface area ground conductors If a leadwire must be used use 14 AWG copper wire Make sure that mechanically tightened joints along the ground path are free of nonconducting coatings and protected against corrosion on mating surfaces Signal ground KDM Data ControlBus Module Communications Interface ControlBus Module Use t...

Страница 7: ...D ALARM SILENCING SWITCH CLOSED INTERMITTENT PILOT SAFE START CHECK FLAME PROVING LED DISPLAY POWER PILOT FLAME MAIN PFEP POWER SAFE START POWER POWER LIMITS STOP STATION AND SILENCING SWITCH FLAME SIGNAL EC RM7885 M15109A 00 00 15 MINUTES L1 TO 6 9 8 10 FOR DIRECT SPARK IGNITION OIL OR GAS 8 MAIN VALVE L2 9 3 4 5 2 1 RM7785A 120 VAC 50 60 HZ EC7885A 220 240 VAC 50 60 HZ POWER SUPPLY PROVIDE DISCO...

Страница 8: ...PPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS SEE FLAME DETECTOR SPECIFICATION FOR CORRECT WIRING 220 240 VAC TO 120 VAC 10 VA MINIMUM STEP DOWN TRANSFORMER NOT PROVIDED REQUIRED TO DRIVE SHUTTER EC7885A ONLY ALARM L1 HOT L2 Q7800 4 1 2 2 1 LIMITS STOP S445A START STOP STATION START B A D C INTERNAL JUMPER DPST ALARM SILENCING SWITCH...

Страница 9: ...ROTECTION AS REQUIRED DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS SEE FLAME DETECTOR SPECIFICATION FOR CORRECT WIRING 220 240 VAC TO 120 VAC 10 VA MINIMUM STEPDOWN TRANSFORMER NOT PROVIDED REQUIRED TO DRIVE SHUTTER EC7885A ONLY ALARM ALARM L1 HOT L2 Q7800 4 1 2 2 1 LIMITS STOP S445A START STOP STATION START B A D C INTERNAL JUMPER DPST ALARM SILENCING SWITCH G L2 3 5 6 7 8 9 10 F L1 13 14 15 16 1...

Страница 10: ...ERMINALS SEE FLAME DETECTOR SPECIFICATION FOR CORRECT WIRING 220 240 VAC TO 120 VAC 10 VA MINIMUM STEPDOWN TRANSFORMER NOT PROVIDED REQUIRED TO DRIVE SHUTTER EC7885A ONLY ALARM L1 HOT L2 Q7800 4 FLAME DETECTOR 1 2 2 1 LIMITS STOP S445A START STOP STATION START B A D C INTERNAL JUMPER DPST ALARM SILENCING SWITCH FUEL PRESSURE SWITCH MANUAL VALVE 1 2 6 7 8 R W B R W B T T CONTROLLER HI LO OR MODULAT...

Страница 11: ...e all manual fuel shutoff valve s before starting these tests 2 Use extreme care while testing the system Line voltage is present on most terminal connections when power is on 3 Open the master switch before installing or removing a jumper on the subbase 4 Before continuing to the next test be sure to remove test jumper s used in the previous test 5 Replace all limits and interlocks that are not o...

Страница 12: ...l damaged or incorrectly sized wires 8 Replace faulty controllers limits interlocks actua tors valves transformers motors and other devices as required 9 Make sure normal operation is obtained for each required test before continuing the checkout 10 After completing each test be sure to remove the test jumper s WARNING Explosion Hazard Can cause severe injury death or property damage Be sure all m...

Страница 13: ...e inch 76 mm minimum to both sides of the RM7885A for electrical sig nal voltage probes 3 Make sure no subbase wiring is projecting beyond the terminal blocks Tuck in wiring against the back of the subbase so it does not interfere with the knife blade terminals or bifurcated contacts IMPORTANT The RM7885A must be installed with a plug in motion rather than a hinge action Terminal No Description Ra...

Страница 14: ...e INITIATE sequence lasts for ten seconds unless the voltage or frequency tolerances are not met When not met a hold condition is initiated and displayed on the optional KDM for at least five seconds when met the INITIATE sequence restarts If the condition is not corrected and the hold condition exists for four minutes the RM7885A locks out Causes for hold conditions in the INITIATE sequence a AC ...

Страница 15: ...pplied via Run Test switch label seal It is intended to prevent and detect unauthorized access Modbus DDL Interface security Any conducts critical to device functionality DDL Modbus lines etc shall be physically protected installed outside public access since they could be damaged or tampered with by unauthorized people either accidentally or for purpose Modbus RS 485 DDL protocols do not support ...

Страница 16: ...Kromschröder and Maxon To learn more about our products visit ThermalSolutions honeywell com or contact your Honeywell Sales Engineer Honeywell Process Solutions Honeywell Thermal Solutions HTS 1250 West Sam Houston Parkway South Houston TX 77042 ThermalSolutions honeywell U S Registered Trademark 2019 Honeywell International Inc 32 00215 01 M S 08 19 Printed in Mexico ...

Отзывы: