104
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Programming
SWITCH
MAN_PULL
Use this switch type for manual pull stations. This input is
always latched. The switch can clear only when an alarm is
reset.
WATERFLOW
Use this switch type for monitoring water flow in a sprinkler
system. Switch closure will cause a sprinkler alarm. Water
flow switches can be programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be used with
a water flow switch. The delay allows for normal, brief
changes in sprinkler system water pressure. The water flow
alarm will not activate unless the switch is active for the
programmed delay time.
Waterflow delay of the FACP and the waterflow device shall
not exceed 90 seconds.
If a delay is used, the system begins counting down when the
switch closes. If the switch opens (restores) before the timer
expires, a water flow alarm is not generated. If the water flow
switch remains closed after the timer expires, a water flow
alarm will be generated.
SUPERVISORY
Non Latching
Use this switch type for tamper monitoring of sprinklers and
other fire protection devices. If a contact closes, a sprinkler
supervisory event will be generated. Supervisory switches can
be latching or non-latching.
FIRE DRILL
System-level, non latching switch. This switch is an alternative
way of causing a fire drill. It has the same operation as the fire
drill option available from the annunciator. When the switch is
activated, a fire drill begins; when the switch is de-activated, a
fire drill ends.
SILENCE
System-level switch provides an alternate way to silence the
system; same effect as pressing the Silence key.
RESET
System-level switch provides an alternate way to reset the
system; same effect as pressing the Reset key.
PAS_ACK
Positive acknowledge switch. This switch must be used in
zones programmed as Positive Alarm Sequence (see
Table 9.1).
If an acknowledge switch closes when an alarm or trouble
condition is not already in progress, a trouble will occur.
You must use a UL listed normally open, momentary switch
type. The switch must be rated at 5V, 100 mA (minimum) and
be used with an EOL resistor for supervision.
SWITCH
(cont.)
ZN_AUX1
Latching
Use these switch types if you want to monitor special zone-
level conditions (such as operation of a fan or damper).
Non Latching
ZN_AUX2
Latching
Non Latching
SYS_AUX1
Latching
Use these switch types if you want to monitor special system-
wide conditions (such as operation of a fan or damper).
Non Latching
SYS_AUX2
Latching
Non Latching
DETECT SW
Used to monitor conventional 4-wire detectors, a contact
closure will generate a detector alarm event.
TAMPER
Latching
Performs identically to a supervisory switch, but will be
indicated as a tamper switch on the LCD annunciator.
Non Latching
MAN REL
Manual release switch, typically a pull station.
ILOCK
Interlock release switch input.
CO DETECT SW
CO Detector Switch
CO SUPERVISORY DETECT SW
CO Supervisory Detector Switch
STATUS PT
Status Point Switch
Type Selection
Function
Latching Option
Comments
Table 9.2 SLC Point Programming
Содержание 6808
Страница 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Страница 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Страница 81: ...6808 Manual P N LS10146 001SK E C 09 28 2017 81 SK SD and SWIFT Wireless SLC Device Installation ...
Страница 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Страница 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Страница 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Страница 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Страница 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Страница 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Страница 168: ...Cut Along the Dotted Line ...
Страница 169: ......