Honeywell 5800PIR-RES Скачать руководство пользователя страница 5

– 5 – 

 6 

  Perform a Walk Test

 

NOTE: 

With the Walk Test switch set to ON the LED will light when the detector is tripped, and the alarm is generated instantly.

 

1.

 

Set the walk test 
switch (DIP switch 
1) to ON.  Replace 
the cover. 

2.

 

Perform a walk test 
through the detec-
tion area, and verify 
satisfactory results. 

3.

 

Allow the detection 
area to remain 
static, and check for 
false or unwanted 
detections. 

 

4.

 

If necessary, adjust 
the detection area (see 
Perform Settings & 
Adjustments). 

5.

 

Repeat the walk test 
through the detection 
area, and verify 
satisfactory results. 

6.

 

Set the walk test DIP 
switch 1 to OFF, and 
secure the Cover with 
the M3 x 10 Captive 
Lock Screw. 

Notes: 

ƒ

 

If normal car or people traffic 
pass close to the detection 
area, adjust the detection 
area 1.5 to 2.0m (5 to 7ft) 
shorter to reduce false 
detections.  This also allows 
for changes due to environ-
mental thermal conditions. 

ƒ

 

If the detection length is 
adjusted to position "A" [12m 
(40ft)], the detection area 
may increase when there is a 
big temperature difference 
between the moving object 
and the background.    

ƒ

 

If this causes a problem, adjust the detection 
length to position "B".  Then walk test to verify 
satisfactory results. 

Approx.8m (27ft)

position B

Approx.12m (40ft)

 

 

WALK TEST

 

ƒ

 

This sensor has a multi-level 
detection pattern (from side 
view).  A heat source beyond 
the detection area may cause 
the detector to issue a false 
alarm by reflecting off the 
ground.  Examples include 
puddles, wet surfaces, very 
smooth asphalt or concrete 
surfaces. 

ƒ

 

If this causes a problem, 
adjust the detection length to 
position "B".  Then perform a 
walk test to verify 
satisfactory results.  

 7 

  Program the Control Panel

 

Prior to use in the system, you must program the transmitter's serial number, input type (RF Supervised), response type, and loop # (set to 1) 
in the control panel.  Refer to the control panel’s instructions for further details.   

Note: 

 If you are learning the control panel by walking, either use the Walk Test setting or temporally set the Battery Saving Timer to 5 sec.  

When the programming is complete ensure the Walk Test switch is set to OFF, and the Battery Saving Timer is set to your desired setting.  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание 5800PIR-RES

Страница 1: ...e ments from center up to 45 Sensitivity 2 0 C at 0 6m s 3 6 F at 2 0ft s Detection Speed 0 3 1 5m s 1 5ft s Operating Voltage 6 VDC uses 4 lithium 1 5VDC AA cells Battery Saving Timer Adjustable 120sec or 5sec Alarm Period 2 5 seconds LED Indicator Enabled during a walk test Disabled for normal operation Weatherproof IP54 compliance Operating Temperature 20 to 50 C 4 to 122 F Humidity 95 Max Acce...

Страница 2: ...0 mounting screws UP 2 Secure the Detector to the Back Box 3 Fasten with four self tapping M3 x 14 screws 4 Perform Settings Adjustments 5 Perform a Walk Test 6 Secure the Cover with the M3 x 10 Captive Lock Screw 7 Program the control panel POLE MOUNTING 1 Use a pole with an outside diameter of 43 48mm 1 69 1 89 2 7 4ft 0 8 1 2m 2 Attach the Brackets to the Back Box with two M3 x 8 screws 3 Using...

Страница 3: ...PER and LOWER beams are blocked detection is made Only the LOWER beam is blocked detection is not made Only the UPPER beam is blocked detection is not made Press and slide the Detection Length Adjustment Switch to the desired position A B C D DETECTION LENGTH D 02 0m 6 7ft C 05 0m 16 7ft B 08 0m 26 7ft A 12 0m 40 0ft NOTES This table is based on a motion sensor height of 1m 3 3ft The height of the...

Страница 4: ...itivity Best to prevent false detections High sensitivity Best detection catches increased false detections Use for applications where you are tagging video or need high security awareness 1 At the DIP switches set switch 2 for the desired Battery Saving Timer period Note The alarm output activations are limited by the timer selection 5 or 120 seconds Even if there are continuous alarm events the ...

Страница 5: ... when there is a big temperature difference between the moving object and the background If this causes a problem adjust the detection length to position B Then walk test to verify satisfactory results Approx 8m 27ft position B Approx 12m 40ft WALK TEST This sensor has a multi level detection pattern from side view A heat source beyond the detection area may cause the detector to issue a false ala...

Страница 6: ...orrectly Perform a Settings Adjustments procedure Low battery fault indicated on system keypad display Batteries are very low or dead Replace batteries Alarms when no one is walking through the detection area Sensor is not perpendicular to ground Remount and align sensor so the detection area is parallel to the ground Sensor is detecting moving trees bushes or a strong source of light Check for mo...

Страница 7: ...D Indicator Cover Lens Back Box Use four M4x30 screws if mounting to pole brackets or two M4x20 screws if mounting to wall Captive Lock Screw M3 x 10 Masking Strip Use as required Lens Holder UP DIP Switch Sensitivity Select Switch Detection Length Ajustment Switch Pole Bracket ...

Страница 8: ...ized changes or modifications could void the user s authority to operate the equipment DOCUMENTATION AND ONLINE SUPPORT For the latest documentation and online support information please go to http www security honeywell com hsc resources MyWebTech WARRANTY For the latest warranty information please go to http www security honeywell com hsc resources wa 2 Corporate Center Drive Suite 100 P O Box 9...

Отзывы: