background image

 

 

HUSH FEATURE / ALARM SILENCE

 

If required, the audible alarm for smoke and CO conditions can be 

silenced for 5 minutes by pushing the “Test/Hush” button. In addition, low 

chirping can be silenced for 12 hours when the Test/Hush button is 

pressed.  

During a Smoke alarm, if an alarm condition still exists after the 5 minute 

hush period, the alarm will sound.  The hush feature will not operate at 

levels above 4%/ft smoke concentration. 
During a CO alarm, if carbon monoxide is still present after the 5 minute 

hush period, the alarm will sound. The hush feature will not operate at 

levels above 350 ppm (parts per million) carbon monoxide. 

CO SENSOR END-of-LIFE FEATURE 

When the CO sensor has passed end-of-life, a trouble signal will be sent to 

the control panel (if programmed). This indicates that the CO sensor inside 

the detector must be replaced. If unresolved for 30 days, the detector will 

chirp every 45 seconds. The typical life of the CO sensor is ten years from 

the date of manufacture. It is recommended to periodically check the 

“Replace by” date located on the label on the back of the detector head. 

TESTING SIGNAL STRENGTH

 

Perform this test in accordance with NFPA 72 inspection, testing and 

maintenance requirements to determine a strong communication path with 

the control panel.  

1. Activate the wireless system’s GO/NO GO TEST mode. 

2. Press the de

tector’s Smoke TEST button (•) for 1

-2 seconds. The 

detector should immediately transmit an alarm signal to the control 

panel. The built-in horn will start to sound about 2.5 seconds after 

pressing the button.  

3. The wireless system’s keypad should emit at least three beeps when 

the alarm transmission is received and display the transmitting 

detector’s zone number.  

4. When the console has received the test signal, the horn will stop and a 

few seconds later the detector’s zone number will clear from the console 

display.  

5. If the console does not respond as noted, and if this is an initial 

installation, try moving the detector to another location that provides 

proper reception. Also be sure that the detector has been “enrolled” by 

the control panel (see Enrollment section). Then, repeat the test. 

6. Turn off the system’s TEST mode (typically security code + OFF). 

REPLACING THE BATTERIES 

  

 

CAUTION:  

The batteries used in this device may present a fire or 

chemical burn hazard if mistreated.  Do not recharge, disassemble, heat 

above 100°C (212°F) or dispose of in fire.  Use only Panasonic CR123A 

Lithium batteries. Use of other batteries may present a risk of fire or 

explosion. Keep used batteries away from children.  Dispose of used 

batteries properly. 

 

Remove old batteries.  Wait 10 seconds and then replace with four new 

batteries. To avoid a low battery indication when installing new batteries, 

all 4 batteries must be installed within 15 seconds of installing the first one. 

Any low battery condition that may have occurred should clear when the 

base plate is installed. 

 

 

CLEANING 

NOTE:

 Notify the proper authorities when the system 

will be temporarily out of service. 

IMPORTANT:

 This detector must be tested and 

maintained regularly following NFPA-72 requirements.  

The detector should be cleaned at least once a year.

 

1.

 

Remove the detector from the base plate by turning 

counterclockwise. 

2.

 

Clean the outside casing with a cloth. Ensure that 

the holes on the front of the alarm are not blocked 

with dirt and dust. Canned air can be used to 

remove any dust or debris. 

3.

 

Reattach the detector to the base plate by rotating 

clockwise.  

4.

 

Test the detector to insure it is fully functional. (See 

Testing section). 

5.

 

Notify the proper authorities and Central Station 

when the system is back in service.

 

 

MAINTENANCE 

Do not paint, and do not use cleaning agents, bleach 

or polish the detector. 

NOTE:

 Before performing any maintenance on the detector, 

notify the proper authorities and Central Station that 

maintenance is being performed and the system will be 

temporarily out of service. Disable the zone or system 

undergoing maintenance to prevent any unwanted alarms. 

Power must be removed from the detector before performing 

maintenance of any kind. 

 

The 5800COMBO detector reports maintenance issues 

to the control panel and communicates them visually 

and audibly per Table 2. 

Trouble feature:

 When the sensor (supervision) is in a 

trouble condition (such as a detector that is dirty or CO 

sensor non-functioning), the detector will send a trouble 

signal to the control panel. Depending on the issue, the 

detector must then be serviced or replaced. 

NOTE:

 Smoke detectors are not to be used with detector 

guards unless the combination is evaluated and found 

suitable for that purpose. 

 

LED INDICATORS 

The 5800COMBO has a multi-color top LED:  

Green = Supervisory indication; blinks during power on, 

reset, and during normal operation 

Amber = Signal maintenance and trouble events 

Red =   Alarm condition (either Smoke or CO) 

Side LED windows indicate alarms:  

 

red = smoke 

 

 blue = CO

 

Table 3: Carbon Monoxide Detector: Events and Their ID Codes 

Event 

Alpha Keypad 

CS Report 

CO alarms 

CO Alarm 

CO alarm (CID 162) 

CO test 

CO Alarm 

CO alarm (CID 162) 

Low battery 

Lo Bat 

RF low-battery (CID 384) 

detector 
 

 

CO Trouble 

RF sensor supervision  
(CID 381) 

detector end-of-

life/trouble 

CO Trouble 

sensor trouble - end-of life 

(CID 380) 

tamper 

disarmed = CO Trouble  

armed = CO Alarm 

RF sensor tamper  
(CID 383)

  

Содержание 5800COMBO

Страница 1: ... the smoke detector zone Loop 1 Zone Type 09 Fire or 16 Fire with Verification Input Type 03 Supervised RF When prompted for the serial number press and release the Smoke Test button for 1 second The sensor sends two transmissions for enrollment Alternatively you can manually enter the smoke sensor serial number found on the unit s label 4 If Maintenance monitoring is desired VISTA 15P 20P 21iP LY...

Страница 2: ... Test Functional CO Test Press and hold the CO Test button for 3 5 seconds to enter the functional gas test mode See Functional Gas Test section below Functional Gas Test Solo C6 brand canned CO may be used to verify the detector s ability to sense CO by utilizing the RealTest feature as follows 1 Press and hold the CO test button for 3 to 5 seconds The green LED will start blinking once per secon...

Страница 3: ... from children Dispose of used batteries properly Remove old batteries Wait 10 seconds and then replace with four new batteries To avoid a low battery indication when installing new batteries all 4 batteries must be installed within 15 seconds of installing the first one Any low battery condition that may have occurred should clear when the base plate is installed CLEANING NOTE Notify the proper a...

Страница 4: ... including interference that may cause undesired operation SUPPORT WARRANTY For the latest documentation and online support information please go to https mywebtech honeywell com For the latest warranty information please go to www honeywell com security hsc resources wa For patent information see www honeywell com patents MyWebTech Warranty Patents REFER TO THE INSTALLATION INSTRUCTIONS FOR THE C...

Отзывы: