Model 5496 Intelligent Power Module Installation and Operation Manual                                      151276-L8 

2-2

2.4

5496 Board and Terminal Strip Description

Figure 2-1 shows the 5496 circuit board including location of terminals and the 
dipswitch for setting the module ID.

Figure 2-1  The 5496 Board Layout

DIP switches for

Setting ID

To AC

Regulated

SBUS Module

Connections

Battery

Connections

Output Circuits

All Circuits 
Supervised Power 
limited, except 
Battery and AC 
which are 
supervised non-
power limited.

Содержание 5496

Страница 1: ...Document 151276 L8 Rev F1 ECN 17 0338 Installation and Operation Guide 5496 Intelligent Power Module ...

Страница 2: ... fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explo sions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predet...

Страница 3: ...ith a normal room temperature of 15 27º C 60 80º F Verify that wire sizes are adequate for all initiating and indi cating device loops Most devices cannot tolerate more than a 10 I R drop from the specified device voltage Like all solid state electronic devices this system may operate erratically or can be damaged when subjected to light ning induced transients Although no system is completely imm...

Страница 4: ... Silent Knight Technical Support at 800 446 6444 Please give the following information Product name and version number if applicable Printed manual Topic Title Page number for printed manual Brief description of content you think should be improved or corrected Your suggestion for how to correct improve documentation To order parts contact Silent Knight Sales at 800 328 0103 ...

Страница 5: ...orksheet Requirements 4 Filling in the Current Draw Worksheet 4 2 6 1 1 Maximum Battery Standby Load 4 2 6 2 Current Draw Worksheet 5 2 6 3 Wire Routing 6 Section 3 Hardware Installation 1 3 1 AC Power 1 3 2 Battery Connection 2 3 3 Connecting the 5496 to the FACP 3 3 3 1 Setting the Device ID 4 3 4 Notification Appliance Wiring 5 3 4 1 Class A Supervised Wiring 5 Class A Output Notification Circu...

Страница 6: ...496 Intelligent Power Module Installation and Operation Manual 2 151276 L8 Appendix A Compatible Devices 1 Honeywell Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability ...

Страница 7: ...the need for sychronization modules when using AMSECO Faraday Gentex System Sensor or Wheelock synchronization appliances 1 2 Agency Requirements The 5496 has the same requirements as the main control panel These requirements are listed in Silent Knight addressable FACP Installation Manuals Silent Knight Addressable FACP Installation Manuals can be found on Silent Knight s web site at www silentkn...

Страница 8: ...tion Do not mount directly on exterior walls below grade condensation Protect from plumbing leaks Protect from splash caused by sprinkler system inspection ports Do not mount in areas with humidity generating equipment such as dryers pro duction machinery When selecting a location to mount the 5496 the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0 C 49 ...

Страница 9: ... shows the 5496 circuit board including location of terminals and the dipswitch for setting the module ID Figure 2 1 The 5496 Board Layout DIP switches for Setting ID To AC Regulated SBUS Module Connections Battery Connections Output Circuits All Circuits Supervised Power limited except Battery and AC which are supervised non power limited ...

Страница 10: ... 2 7 A Earth ground N A N A W AC input neutral 120 VAC 60 Hz 2 7 A 1 Battery Battery 24 VDC 0 75 A 2 3 I O 4 Output circuit 24 VDC 3 0 A Notification Circuits 4 5 I O 3 Output circuit 24 VDC 3 0 A Notification Circuits 6 7 I O 2 Output circuit 24 VDC 3 0 A Notification Circuits 8 9 I O 1 Output circuit 24 VDC 3 0 A Notification Circuits 10 11 SBUS SBUS power 24 VDC 1 0 A 12 13 A SBUS communication...

Страница 11: ... that the total alarm current you calculated including current for the panel itself does not exceed 6 0 A This is the maximum alarm current allowable 5 Complete the remaining instructions in Table 2 4 to determine battery size requirements 2 6 1 1 Maximum Battery Standby Load Table 2 3 shows the maximum battery standby load for the 5496 based on 24 and 60 hours of standby The standby load calculat...

Страница 12: ...uired for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service City Box and Remote Station Protected Fire Alarm systems Polarity Reversal and Digital Alarm Communicator Transmitter DACT Table 2 3 Maximum Battery Standby Load Rechargeable Battery Size Max Load for 24 hrs Standby 5 mins Alarm Max Load for 60 hrs Standby 5 mins Alarm ...

Страница 13: ...96 Current 40 mA 160 mA Auxiliary Devices Refer to device manual for current ratings Alarm Standby mA mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA B Auxiliary Devices Current mA mA Notification appliances Refer to device manual for current ratings Alarm mA 0 mA mA Alarm mA 0 mA mA Alarm mA 0 mA mA Alarm mA 0 mA mA C Notification Appliances Current 0 mA mA D Total curr...

Страница 14: ...ow power limited wiring techniques which include maintaining one quarter inch spacing between power limited and non power limited circuits and separating high and low voltage circuits Figure 2 2 Wire Routing Example 5496 Board To AC Power To Battery To SBUS Terminals To NACs ...

Страница 15: ... information Refer to Silent Knight addressable FACP Installation Manuals for software configuration information and other information about installing outputs Silent Knight Addressable FACP Installation Manuals can be found on Silent Knight s web site at www silentknight com 3 1 AC Power At installation connect the AC terminals to 120 VAC source as shown in Figure 3 1 It may be necessary for a pr...

Страница 16: ...Note If you require the power of back up batteries that are too large for the 5496 you can use the RBB cabinet The RBB Remote Battery Box holds batteries up to the 35 AH size Refer to P N 151306 for RBB installation instructions Wire batteries in series to produce a 24 volt equivalent Do not parallel batteries to increase the AH rating Figure 3 2 Battery Connection Red To Panel Black UL Listed 12V...

Страница 17: ...ows the location of the dipswitches on the 5496 board 3 Configure the 5496 module by adding it to the system through JumpStart or manually You can also assign a name to the module These procedures are described in Silent Knight addressable FACP Installation Manuals Silent Knight Addressable FACP Installation Manuals can be found on Silent Knight s web site at www silentknight com Figure 3 3 Class ...

Страница 18: ...S modules in the system must have a unique number 1 31 to identify them to the FACP Use the DIP switch on the 5496 board to set the module ID number Figure 2 1 shows the location of the dipswitch on the board Figure 3 4 shows dipswitch setting and the corresponding module ID numbers Figure 3 4 Possible Module Addresses ...

Страница 19: ...Use in out wiring methods for proper supervision Refer to Section 4 for notification appliances compatible with the 5496 Class A Output Notification Circuits The configuration shown in Figure 3 5 shows two 3 amp devices wired as Class A circuits When you are using the outputs as Class A circuits loop the wiring back to the corresponding circuit pair For Class A wiring no external EOL is necessary ...

Страница 20: ...hen using all outputs as Class B notification appliance circuits The 4 7k EOLs must be wired to the terminals whether or not you are using all output terminals Figure 3 6 Regulated Class B Supervised Input Output Connections 3 4 3 Releasing Operations Approved releasing solenoids are list in Table 3 1 Do not mix cross alarming zones with smoke verification zones There must be at least two automati...

Страница 21: ...der Sync Power Auxiliary power circuits are power limited Each circuit can source up to 3A total current for all output circuits must not exceed 6 A To configure an output circuit as auxiliary power 1 Wire the output circuit s that will be used for auxiliary power See Figure 3 7 for location of the output circuits 2 Configure the auxiliary power output through programming for Door Holder Constant ...

Страница 22: ...power is restored power is immediately restored to the door holder circuits 3 4 4 2 Constant Power Use constant power for applications that require a constant auxiliary power source Power is always present at Constant circuits 3 4 4 3 Resettable Power Resettable power is typically used to power beam detectors flame detectors and conventional 4 wire smoke detectors For circuits selected as Resettab...

Страница 23: ...notification appliances compatible with the fire alarm control panel Appliances which can be synchronized indicate the type of sync available in the columns marked Audio and or Visual Table A 1 Compatible Notification Appliances Manufacturer Model Audio Visual Type AMSECO SH24W 153075 x x Horn Strobe SAD24 153075 x Strobe SAD24 75110 x Strobe SL24W 75110 x Strobe SL24C 3075110 x Strobe SLB24 75 x ...

Страница 24: ... Horn Strobe P241575 FC x x Horn Strobe P241575W FC x x Horn Strobe P241575F FC x x Horn Strobe P241575K FC x x Horn Strobe P2430 FC x x Horn Strobe P2430W FC x x Horn Strobe P2430K FC x x Horn Strobe P2475 FC x x Horn Strobe P2475W FC x x Horn Strobe P2475K FC x x Horn Strobe P24110 FC x x Horn Strobe P24110W FC x x Horn Strobe P24110K FC x x Horn Strobe S2430W FC x Strobe S2430K FC x Strobe S247...

Страница 25: ...Strobe Ceiling Mount GCCR24 x Multi Candella Horn Strobe Ceiling Mount GCS24 x Multi Candella Strobe Ceiling Mount GCSR24 x Multi Candella Strobe Ceiling Mount GECR 24 x x Multi Candella Horn Strobe GES24 15 x Strobe GES24 30 x Strobe GES24 60 x Strobe GES24 75 x Strobe GES24 110 x Strobe GES24 15 75 x Strobe GES24 177 x Strobe GES3 24 x Multi Candella Strobe GESR 24 x Multi Candella Strobe GEH 24...

Страница 26: ... P x x 2 Wire Horn Strobe P2RH x x 2 Wire Horn Strobe High Candela P2RH P x x 2 Wire Horn Strobe High Candela PC2RH x x 2 Wire Horn Strobe High Candela PC2RH P x x 2 Wire Horn Strobe High Candela P2W x x 2 Wire Horn Strobe P2W P x x 2 Wire Horn Strobe PC2W x x 2 Wire Horn Strobe PC2W P x x 2 Wire Horn Strobe P2WH x x 2 Wire Horn Strobe High Candela P2WH P x x 2 Wire Horn Strobe High Candela PC2WH ...

Страница 27: ... x x Horn Strobe 2W WHT Ceil 4x4 P2GRL x x Horn Strobe 2W Red Wall 2x4 P2GWL x x Horn Strobe 2W WHT Wall 2x4 P4RL x x Horn Strobe 4W Red Wall 4X4 P4WL x x Horn Strobe 4W WHT Wall 4X4 PC4RL x x Horn Strobe 4W Red Ceil 4X4 PC4WL x x Horn Strobe 4W WHT Ceil 4X4 SR x Strobe SR P x Strobe SCR x Strobe SCR P x Strobe SRH x Strobe High Candela SRH P x Strobe High Candela SCRH x Strobe High Candela SCRH P...

Страница 28: ...Horn AH 24 x Horn AH 12WP x Horn Weatherproof AH 24WP x Horn Weatherproof AMT 241575W x x Multi Tone Horn Strobe AMT 24MCW x Mutli Tone Horn Strobe AMT 241575W NYC x x Multi Tone Horn Strobe AMT 12 24 x Multi tone Horn AMT 12 24 NYC x Multi tone Horn AS 121575W x Horn Strobe NH 12 24 x x Horn AS 241575W x x Horn Strobe AS 24MCC x x Horn Strobe AS 24MCCH x x Horn Strobe AS 24MCW x x Horn Strobe AS ...

Страница 29: ...ltitone Horn Strobe MTWPG 2475W x x Multitone Horn Strobe MTWPR 2475W x x Multitone Horn Strobe MTWPA 24MCCH x x Multitone Horn Strobe ZNH x Horn NS 121575W x x Horn Strobe NS 241575W x x Horn Strobe NS 24MCW x x Horn Strobe NS 24MCC x x Horn Strobe NS 24MCCH x x Horn Strobe ZNS MCW x x Horn Strobe ZNS MCWH x x Horn Strobe ZNS 24MCC x x Horn Strobe ZNS 24MCCH x x Horn Strobe RSS 121575W x Strobe R...

Страница 30: ...rproof RSSWPA 24MCCH x Strobe Weatherproof RSSWPG 24MCCH x Strobe Weatherproof RSSWPR 24MCCH x Strobe Weatherproof RSSWP 2475W x Strobe Weatherproof RSSWP 2475C x Strobe Weatherproof RSSWP 24MCWH x Strobe Weatherproof ZRS MCWH x Strobe ZRS 24MCC x Strobe ZRS 24MCCH x Strobe MB G6 24 x Motor Bell MB G10 24 x Motor Bell MB G6 12 x Motor Bell MB G10 12 x Motor Bell MIZ 24 R x Mini Horn MT 12 24 R x x...

Страница 31: ... ground Return the Honeywell Silent Knight product circuit board only Products that are returned in cabinets will be charged an additional 50 to cover the extra shipping and handling costs over board only returns Do not return batteries Honeywell has the authority to determine if a product is repairable Products that are deemed un repairable will be returned to the customer Product that is returne...

Страница 32: ...ANUFACTURER MAKES NO FURTHER WARRANTIES AND DISCLAIMS ANY AND ALL OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF O...

Страница 33: ......

Страница 34: ...Silent Knight 12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www silentknight com ...

Отзывы: