151276-L8
Before You Begin Installing
2-5
Note: 33 max battery size for FM (Factory Mutual) installations
18 AH
685 mA
270 mA
35 AH
1370 mA
540 mA
*
Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote Station
Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
Table 2-3: Maximum Battery Standby Load
Rechargeable
Battery Size
Max. Load for 24 hrs. Standby,
5 mins. Alarm
*Max. Load for 60 hrs. Standby, 5
mins. Alarm