Step-by-Step 

Tech Support 

 Updated 7/27/10 

Notes: 

ƒ

 

If a 4500 thermostat does not respond to the 4286 phone module for 2 minutes, the phone module will 
announce, 

“Check thermostat (1/2). (Descriptor),” 

instead of the temperature.  

ƒ

 

If the temperature falls below 37° F (3° C), the 4286 phone module will announce, 

“Check thermostat 

(1/2). (Descriptor),” 

instead of the temperature.  See Trouble Shooting Below. 

 

Troubleshooting the 4500 

Following the procedures in the 4286 Installation Instructions manual should result in a minimum number of system 
problems. If you experience problems that relate to the use of the 4500 thermostat(s), first check the possible 
resolution of some typical thermostat problems that follow. 
 

Thermostat is in check (4286 announces “Check Thermostat,” or the yellow light is flashing on the 4500): 

 

1.

 

Check that the DIP switch on each thermostat is properly set, and that the 4500 thermostat addresses have 
been properly programmed in the 4286 programming mode.  

See figure 11 above

 

2.

 

Check the connections from the 4286 to the 4500, and make sure that the cable connecting the 4500s to the 
4286 faces the correct direction (yellow toward the corner of the 4286 board). 

 

Heat is cycling on and off too often. 

1.

 

Increase the amount of “span” as described in the section “Programming the 4286 to add 4500 thermostats” 
in Section 4 of this manual. 

2.

 

Make sure that the location where the 4500 is mounted is free of drafts. 

 

Temperature in the room swings too widely when the 4500 is set to “ACTIVE” mode. 

1.

 

Decrease the amount of span as described in the section “Programming the 4286 to add 4500 thermostats” 
in Section 4 of the manual.  Also see figure 7 above for programming locations. 

 
Troubleshooting the 4286: 

 

Problem: 

“When I enter the phone code on premise the operator comes on or I get a busy signal.” 

 
Answer: 

This means the Voice Module does not hear the code entered. This can be caused by too many things, so 

narrow the problem down by attempting to call it from off premise. How far do you get from off premise? 

1.

 

Panel answers, gives download tone but 4286 does not come on. 

ƒ

 

Problem is caused by Reason

 3 or 5. 

(See Next Page)

 

2.

 

Panel answers, gives download tone; voice module comes on but does not accept code. 

ƒ

 

Problem caused by Reason

 1 or 4

.

 

(See Next Page) 

3.

 

Panel answers, gives download, voice module comes on and accepts code from off premise. 

ƒ

 

Site problem is caused by Reason 

2 or 4 

(See Next Page)

 

4.

 

Check for Line seizure

 

 
Problem: 

“Check 104 (10/15/20p series controls) or check 804 (32/128/250 series controls)”, also will complain the 

voice module does not work. 

 
Answer: 

This means the panel does not see the 4286, so of course it does not work. 

1.

 

This can only be caused by Reason 

3 or 5. 

(See Next Page)

 

 
Problem: 

“Call into System Off”, when the customer tries to remote access. 

 
Answer: 

This means the 4286 is not configured for remote access. 

1.

 

To toggle on or off enter Code #91 on the keypad

ƒ

 

Keypad beeps twice means it is on 

ƒ

 

Keypad beeps once means it is off 

 
 

Содержание 4286

Страница 1: ...supported 2 DSL requires an RJ31X DSL filter Wiring Notes 1 When using a power supply you MUST share a common ground with the control panel 2 The 4286 wires up directly to the keypad Terminals on your Control panel 3 Observe the panels ECP keypad data wire runs and do not exceed the 2000 max distance the panel offers 1500 on vista20 and lower control panels 4 Existing wires connected to the Handse...

Страница 2: ...Support Updated 7 27 10 Figure 2 Vista 40 50 128b bp 250bp Figure 3 Vista 32fb 128fb fbp 250fbp System Programming Notes 1 The 4286 has a Non Changeable address of 04 and can not be changed See below for programming on various panels ...

Страница 3: ... 2 digit access code Enter 1 9 for Customers with out an answering machine or a dedicated line to the panel If they have an answering machine you can use the Answering Machine Defeat option by Entering 15 here This requires the customer to call let ring once hang up and call back 4 10 15 20p Notes 4286 Phone Modules must have software version WA4286 15 1 V101 or higher refer to the label on the sq...

Страница 4: ...the telephone keypad Upon Doing so the panel will start speaking the 1st programming location and it value It will say Field 00 is 00 Programming can only be accessed within 3 hours of power up After programming the 98 mode you only have 15 minutes to re access it If it has been longer than that you can simply power the 4286 down for 5 seconds then back up and you have your 3 hour time window agai...

Страница 5: ... 0 50 0 30 3 0 75 0 40 3 0 75 0 40 4 1 00 0 60 4 1 00 0 60 5 1 50 0 80 5 1 50 0 80 6 2 00 1 10 6 2 00 1 10 7 2 50 1 40 7 2 50 1 40 Figure 5 Swing Points Do Not Select a 1 1 This field defines how many degrees below the set point the heat will turn on and how many degrees above the set point the heat will turn off These values also define the swing of the air conditioner operation 06 Announce the T...

Страница 6: ...IGHT 139 GLASS 063 POWER 069 0 125 BUILDING 166 PUMP 070 1 039 BURGLARY 050 HALL 136 1ST 010 HEAT 088 REAR 071 2 003 CALL 028 RIGHT 056 2ND 089 CENTRAL 209 INSIDE 018 ROOM 072 3 054 CHIME 159 3RD 126 CLOSED 022 KITCHEN 007 S 073 4 127 COMPUTER 150 SERVICE 217 4TH 140 LAUNDRY 151 SHED 218 5 208 DAUGHTER S 027 LEFT 152 SHOP 075 5TH 052 DEN 141 LIBRARY 153 SIDE 219 6 128 DETECTOR 019 LIGHT 024 SMOKE ...

Страница 7: ...onnecting power to the thermostat 4 While installation of the 4500 is possible without the services of a HVAC contractor some installers will prefer to have an HVAC contractor connect the 4500 to the HVAC system and test its operation This is recommended if you do not have HVAC experience In cases where you prefer to do the entire installation it is suggested that the HVAC contractor be contacted ...

Страница 8: ... adjust the temperature It has a Thermistor built on it that detects the temperature of the room When it determines that the temperature is above or below the set back it opens up the relay to prevent voltage feed to HVAC system preventing it from coming on at existing thermostat setting it then uses 4500 settings When temperature reaches Set back setting Relay will close to allow the on premise t...

Страница 9: ...ting for thermostat 1 will follow You can change its set point using menu selection 1 below If thermostat 1 is in BYPASS or CHECK that status will be announced instead of the set point The 4286 will also announce whether set back has been turned off by the user Menu Selections To change temperature enter 1 This selection is used to set the armed away set back temperature for thermostats 1 or 2 Thi...

Страница 10: ...on where the 4500 is mounted is free of drafts Temperature in the room swings too widely when the 4500 is set to ACTIVE mode 1 Decrease the amount of span as described in the section Programming the 4286 to add 4500 thermostats in Section 4 of the manual Also see figure 7 above for programming locations Troubleshooting the 4286 Problem When I enter the phone code on premise the operator comes on o...

Страница 11: ...plug on the 4286 and not the plug intended for the 4500 make sure it is plugged in with yellow towards the center of the board Meter for voltage or data at the harness and on the pins when pulled back a little Take everything else off the ECP buss and test again to confirm there is not a current overload or address conflict 4 Tones generated by phone are not long enough or not correct Hold the key...

Отзывы: