T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2605—5
36
Temperature Display
Calibration
No Change
X
No Change: Displayed temperature is actual room temperature.
Can adjust to display up to 3° F (1.7° C) higher or down to 4° F (2.2° C) lower than
room temperature.
TempOverride
3
X
X
Temporary Occupied Override duration. Range: 1 to 8 hours.
RoomTemp
Local
X
X
Room Temperature Input
Local: Use internal sensor; T7770A/D: Use remote sensor.
T7770B/C: Use remote sensor with setpoint adjustment capability (requires PDA).
T7771: Use remote sensor with setpoint adjustment capability (requires PDA); changes
T7771 LED and bypass button operation: LED on means either occupied or bypass,
pushing bypass can cancel bypass.
RoomRelHumidity
a
X
X
Room Relative Humidity Input.
None: No humidity sensor; Local: Use internal humidity sensor;
Remote: Use remote humidity sensor (0-10 Vdc signal).
Discharge AirTemp
None
X
X
Discharge Air Temperature Input.
None: No discharge air sensor; or Remote: Remote discharge air sensor.
Outdoor AirTemp
None
X
X
Outdoor Air Temperature Input.
None: No outdoor air sensor; or Remote: Remote outdoor air sensor.
OccSensor
0
X
X
None: No occupancy sensor; or Remote: Remote occupancy sensor.
AuxDO
Time of Day
X
X
Auxiliary Contact Operation:
Time of Day, Economizer, Dehumid Hot Gas BP, or Simple Dehumid.
Auxiliary contact not available if heat pump selected with T7350A.
Key Pad (Lockout)
Enable All
X
X
Keypad lockout enable/disable through special keypad sequence.
Enable All (0): No lockout.
SetPts & Ovrrd (1): Lockout all keys except: Temporary (Not) Occupied,
S
,
T
and
.
Info Only (2): Lockout all keys except
.
The special keypress features are never locked out.
Recovery Heat RampMin
5° F/hr
X
Minimum heating recovery ramp rate. Range: 0 to 20° F/hr.
Recovery Heat RampMax
8° F/hr
X
Maximum heating recovery ramp rate. Range: 0 to 20° F/hr.
Recovery Cool RampMin
3° F/hr
X
Minimum cooling recovery ramp rate. Range: 0 to 20° F/hr.
Recovery Cool RampMax
6° F/hr
X
Maximum heating recovery ramp rate. Range: 0 to 20° F/hr.
Recovery Heat OAT@Min
0° F
X
Minimum heating outdoor air temperature. Range: -20 to 100° F.
Recovery Heat OAT@Max
40° F
X
Maximum heating outdoor air temperature. Range: -20 to 100° F.
Recovery Cool OAT@Min
90° F
X
Minimum cooling outdoor air temperature. Range: -20 to 100° F.
Recovery Cool OAT@Max
70° F
X
Maximum cooling outdoor air temperature. Range: -20 to 100° F.
Demand Limit Control Bump
3° F
X
Demand limit control set point bump. Range: 0 to 10° F.
Power Failure Seq Start
0 (x10 sec)
X
X
Delays start of equipment (fan, heat, cool) after power restored to thermostat.
Range: 0 to 150 seconds (in 10-second increments).
Enable DAT High Limit
None
X
X
None: No Discharge Air Temperature (DAT) high limit; Enable: Use DAT High Limit.
Enable DAT Low Limit
None
X
X
None: No Discharge Air Temperature (DAT) low limit; Enable: Use DAT Low Limit.
High Limit DAT Setpoint
110° F
X
Discharge Air Temperature High Limit Setpoint. Range: 65 to 140° F.
Low Limit DAT Setpoint
45° F
X
Discharge Air Temperature Low Limit Setpoint. Range: 35 to 60° F.
Dehumidification Min On
None
X
X
None: No Minimum On Time dehumidification;
Enable: Dehumidification using Minimum On Time.
Dehumidification Min On Time 5
X
Minimum on time used with “Dehumidify Minimum On”. Range: 5 to 15 minutes.
Dehumidification Reset Temp None
X
X
None: No Reset dehumidification; Enable: Dehumidification using Reset.
Table 20. Thermostat Setup Options Through PDA. (Continued)
Configuration Option
Factory Default
a
PDA
Tool CnfgID
Description
a
The Factory defaults listed here apply to all subbase models with the exceptions of the items listed in Table 21.
b
12:00 Noon is the default start point when time is unknown.
c
Only Available if user selected one or more of following: Dehumidification Reset, Dehumidification Minimum On, or Dehumidification Reheat.
d
Config ID cannot handle Standby setpoints. Keypad users cannot set Occupied setpoints that violate Not Occupied setpoint relationship. The T7350 algo-
rithm never allows the effective setpoint outside Not Occupied setpoints.