T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
21
63-2605—5
Fig. 14. Using T7350A,B,D,M models with an external
relay (with loads greater than 1.5A).
Fig. 15. Using T7350H models with an external relay
powered from thermostat transformer.
Fig. 16. Using T7350H models with an external relay
powered from an auxiliary transformer.
Default Auxiliary Relay Operations
(T7350D, T7350H1009
only
)
Unless configured as a stage of heating or cooling, terminals
W2, W3, and Y3 operate for specific auxiliary functions. Each
output takes on different auxiliary functions depending on
configuration for Conventional or Heat Pump operation. See
Table 17 for details.
NOTE: The default functions cannot be modified. They are
limited to firmware version 1.3.0 or higher.
M19613
1
1
RELAY REQUIRED (R8222 OR SIMILAR).
T7350A,B,D,M SUBBASE
TO
LOAD
AUXILIARY
RELAY
CONTACT
AUX
RH
X
M22487
1
1
RELAY REQUIRED (R8222 OR SIMILAR).
T7350H SUBBASE
TO
LOAD
AUXILIARY
RELAY
CONTACT
AUX
RH
AUX
X
M22488
1
2
1
RELAY REQUIRED (R8222 OR SIMILAR).
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
T7350H SUBBASE
TO
LOAD
AUXILIARY
RELAY
CONTACT
AUX
AUX
2
L1
(HOT)
L2
AUXILIARY
TRANSFORMER
Table 17. Default Auxiliary Relay Operations.
a
Simple dehumidification uses a normally closed contact. The relay is closed when humidity is below the high limit. When the
humidity is above the high limit, the contact is open.
b
The PDA configuration tool output screen displays available Auxiliary Relay functions based on this configuration.
Heat Pump or
Conventional
Contact Not Used
as Heat or Cool Stage
Contact Configuration of Contact Not Used as Stage
Heat Pump
Y3 not
Simple
Dehumidification
a
Simple
Dehumidification
a
Time of Day
Time of Day
W2 not aux heat
Economizer
Time of Day
Economizer
Economizer
Conventional
W3 not
Simple
Dehumidification
a
Simple
Dehumidification
a
Simple
Dehumidification
a
Time of Day
Y3 not (W3 not)
Economizer
Time of Day
Time of Day
Economizer
Y3 not (W3 used)
Simple
Dehumidification
a
Simple
Dehumidification
a
Simple
Dehumidification
a
Time of Day
Auxiliary Contact Configuration
b
:
Time of Day
Economizer
Hot Gas Bypass
Dehumidification
Simple
Dehumidification
a