6. Programming
6.1. Read/write operation of operation parameters setting area
114
Resistance Temperature Detector 2MLF-RD4A User's Guide
R200
Honeywell
September 2010
(Address) D area of CPU module
Internal memory
(Address)
D0
Used CH setting
Used CH setting
0
D1
CH0 sensor type setting
CH0 sensor type setting
1
-
-
Figure 68 – Example of read execution
Write data to the operation parameters setting area (PUT, PUTP instruction)
The instructions PUT, PUTP are used to write data to the special module from the CPU
memory.
Figure 69 – Example of write execution
Operand
Description
Available data
n1
Slot number where special module is installed.
Integer
n2
Start address of internal memory of special module.
h
d t ill b itt
Integer
S
Start memory address of CPU module where the data to
be written is saved.
M, P, K, L, T, C, D, #D,
Integer
n3
Number of words (data) to write.
Integer
Difference between PUT instruction and PUTP instruction
•
PUT
: executes at every scan when execution condition is turned ON. ( )
•
PUTP
: executes once at the rising edge of the execution condition. ( )