5. Internal Memory Configuration and Functions
5.3. Operation parameters setting area
102
Resistance Temperature Detector 2MLF-RD4A User's Guide
R200
Honeywell
September 2010
3.
Use I/O Parameter window for more convenient setting.
Figure 55 – I/O Parameter window 10 (process alarm HYS)
Input variation alarm type (address 47)
1.
Bit ‘0 to 3’ of memory address 47 are used to set the input variation alarm type for
channel ‘0 to 3’, respectively.
2.
If the bit is set to ‘1’, temperature variation rate (rate for input temperature range
based on the sensor type) is the criterion of alarm
for the specified channel.
Example
: for Pt100,
Address
Description
43
Channel 0 Process Alarm Hysteresis Setting
44
Channel 1 Process Alarm Hysteresis Setting
45
Channel 2 Process Alarm Hysteresis Setting
46
Channel 3 Process Alarm Hysteresis Setting