2. Specifications
2.5. Additional functions
R200
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
41
September 2010
Honeywell
Perform the following steps to configure I/O parameters.
Step
Action
1
On the
Project Window
of SoftMaster, click
I/O Parameters.
The
I/O Parameter Setting
window is displayed.
2
On the
I/O Parameters Setting
window, click the module area of the
concerned slot to select the applicable module.
Click the arrow button on the Module cell, to display the modules. Select the
applicable module.
3
Double-click the
2MLF-DC4S
module.
The module’s
I/O Parameter Settings
window is displayed.
4
Set the
Rate control
setting to
Enable
.
5
Set the
Increase limit value
and the
Decrease limit value
.
6
When the rate control is set, the analog output value is as shown in the
following figure.