2. Specifications
2.3. Characteristics of I/O conversion
R200
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
31
September 2010
Honeywell
1.
If the range is 4~20mA
Digital
Input
Analog Current Output
Maximum
Resolution
3.808
4
8
12
16
20
20.192
Unsigned
value
-192
0
4000
8000
12000
16000
16191
1.0
µ
A
Signed
value
-8192
-8000
-4000
0
4000
8000
8191
Precise
value
3808
4000
8000
12000
16000
20000
20192
Percentil
e value
-120
0
2500
5000
7500
10000
10119
1.6
µ
A
In the case of 4~20mA current output, analog current output for digital value of “1” is
equivalent to 1.0
µ
A.