Honeywell 14506873-001 Скачать руководство пользователя страница 11

Power Supply Electrical Ratings For 14506873-001

24V output maximum load is 80 mA; auxiliary alarm output maximum load is 20 mA.

Auxiliary Relay Contacts

minimum contact current must be greater than 500 mA at 24 VDC
10 amps maximum at 30 VDC
10 amps maximum at 250 VAC

Accessories

Part No.

Remote LED

SSDRA400Z

Piezo Alert Sounder

SSDPA400

Replacement Filters

SSDF360500

Magnet

SSDM0204

End Plug For Sampling Tube

SSDP482100

Installation Kit (Parts bag)

SSDA2650-01

Photoelectronic Replacement Screen

SSDRS24

Ionization Replacement Screen

SSDRS14

Sensitivity Test Kit

SSDMOD400R

Ionization Cover Removal Tool

SSDCRT400

Remote Test Station

SSDRTS451/SSDRTS451KEY

SAMPLING (INLET) TUBES
TUBE

OUTSIDE DUCT WIDTH

SSDST-1.5

1 to 2 ft.

(30 to 61  cm)

SSDST-3

2 to 4 ft.

(61 to 122 cm)

SSDST-5

4 to 8 ft.

(1.2 to 2.4 m)

SSDST-10

8 to 12 ft.

(2.4 to 3.7 m)

Programming Specifications/Requirements For Intelligent System Control Panels.

NOTE: Models TC807A and TC806A can be used with the 14506873-001 if the following constraints are observed:

1. There may be a limit to the number of devices per zone that can have their LEDs latched on. The number of devices

is determined by the control panel and its ability to supply LED current. If more than the maximum number of devices
are on the same loop, Do NOT use the 14506873-001 for control purposes. Control for duct applications would need
to come directly from the control panel or by using control modules. If sensor models TC807A1036, TC807A1044,
TC806A1037, or TC806A1052 are used, the constraints above do not apply.

2. The duct control circuitry (auxiliary relay contacts and auxiliary alarm output) may change states if the sensor is test-

ed and the LED is turned on for more than 4 seconds. If the LED is latched on for less than 4 seconds, the control
circuitry of the 14506873-001 will NOT operate.

3. The panel must not continuously poll the same unit for more than 4 seconds or the auxiliary relay and auxiliary alarm

output may switch states. After 4 seconds of continual polling of a device, the panel must wait a minimum of 100ms
before polling or communicating to that same device.

4. Communications must not cease for more than 3 seconds without an additional clock pulse (after Pulse Width 5) to

turn off the LED on the sensor.

5. To allow the auxiliary relay and auxiliary alarm output to return to a standby condition, (after being in alarm) the panel

must wait a minimum of 100ms after turning off the sensor LED before communicating with that device again.

Power

120 VAC (102 - 132)

240 VAC (204 - 264)

24 VAC (20.6 - 26.4)

24 VDC (20 - 30)

Requirements

mA rms MAX.

mA rms MAX.

mA rms MAX.

mA DC MAX.

  

Device

Standby

Alarm

Standby

Alarm

Standby

Alarm

Standby

Alarm

  

14506873-001

44

52

25

30

65

182

26

87

  

BRKPA400*

--

3

--

1.5

--

29

--

15

  

SSDRA400ZA*

--

1.5

--

1

--

17.3

--

10

  

SSDRTS451/SSDRTS451KEY*

--

1.5

--

1

--

17.3

--

10

  

SSDRTS451**/SSDRTS451KEY

11.5

13

5.5

6.5

140

157

95

103

The 14506873-001 Air Duct Detector Housings are used with Honeywell’s model TC807A ionization detector heads and
model TC806A photoelectronic detector heads (purchased separately). These two smoke detection methods are com-
bined with an efficient housing design that samples air passing through a duct and allows detection of a developing haz-
ardous condition. When sufficient smoke is sensed, an alarm signal is initiated at the fire control panel monitoring the
detector, and appropriate action can be taken to shut off fans and blowers, change over air handling systems, etc. This
can prevent the distribution of toxic smoke and fire gases throughout the areas served by the duct system.

The 14506873-001s are built to operate on 120/240 VAC or 24 VAC/DC. Two form-C (SPDT) sets of relay contacts are
available for control purposes. Two LEDs on each detector latch on to provide a local alarm indication. Remote alarm
indication is made possible by utilizing the auxiliary alarm output (Figure 5). The duct detector can be tested and alarm
can be reset by using the correct respective code commands from the panel. See panel instructions for details.

CONTENTS OF THE DUCT DETECTOR HOUSING KIT

The 14506873-001 Air Duct Detector Housings consist of the following items: (See Figure 1.)

See Note 1 for Inlet Sampling
Tube and Detector Supply
information.

1. Complete housing base

and cover assembly.

2. Two #10 sheet metal mounting screws.
3. Two sampling tube filters.
4. One test magnet.
5. Drilling template.
6. Two 5/16-inch O-rings.
7. Two foam gaskets.
8. Four #6 self-tapping mounting

screws for the sampling tube.

9. One filter adapter.
10. One inlet tube end plug.
11. Two #10 speed nuts.

Note 1: The inlet sampling tube must be ordered separately. It must be the correct length for the width of the duct where

it will be installed. See Table 1 to determine the inlet tube required for different duct widths. A smoke detector
head (TC807A for ionization or TC806A for photoelectronic) must be ordered separately.

The currents shown for the
14506873-001 are maximum val-
ues with no accessories.
* All accessory currents are

additional to 14506873-001.
There are no additional cur-
rents for accessories in stand-
by.

**

SSDRTS451/SSDRTS451KEY
when the magnet is held in
place to initiate an alarm.

H500-03-00

2

I56-475-09R

H500-03-00

11

I56-475-09R

A78-2448-00

Figure 1.

SAMPLING TUBE

FILTERS

CONDUIT HOLES

DUCT DETECTOR 

HOUSING

PC BOARD 

INSULATOR

DUCT DETECTOR

COVER

SAMPLING TUBE

MOUNTING

SCREWS

DETECTOR HEAD

(SUPPLIED SEPARATELY)

EXHAUST 

FILTER ADAPTER

DETECTOR BASE

INLET SAMPLING TUBE

(SUPPLIED SEPARATELY)

O-RINGS

FOAM

GASKETS

HOUSING

MOUNTING SCREWS

TEST MAGNET

TUBE

END

PLUG

Содержание 14506873-001

Страница 1: ...72 requirements The detector should be cleaned at least once a year TABLE OF CONTENTS GENERAL DESCRIPTION 1 Contents of the Duct Detector Housing Kit 2 INSTALLATION SEQUENCE 3 Verify Duct Air Velocity 3 Drill the Mounting Holes 3 Mount Duct Housing 3 Install the Inlet Tube 4 Ducts Less Than 8 ft 244 cm Wide 4 Ducts More Than 8 ft 244 cm Wide 5 Interim Modification of Inlet Tube 5 Field Wiring 5 Wi...

Страница 2: ...respective code commands from the panel See panel instructions for details CONTENTS OF THE DUCT DETECTOR HOUSING KIT The 14506873 001 Air Duct Detector Housings consist of the following items See Figure 1 See Note 1 for Inlet Sampling Tube and Detector Supply information 1 Complete housing base and cover assembly 2 Two 10 sheet metal mounting screws 3 Two sampling tube filters 4 One test magnet 5 ...

Страница 3: ...he duct See Figure 2 Location of detectors mounted in or on air ducts should be at least six duct widths downstream from any duct openings deflection plates sharp bends or branch connections Exception Where it is physically impossible to locate the detector accordingly the detector can be positioned closer than six duct widths but as far as possible from the opening bend or deflection plates STEP ...

Страница 4: ...t tube If the inlet tube is shorter than the width of the air duct install the end cap into the inlet tube as shown in Figure 3 2 Slide the inlet tube into the bushing located in the center of the duct housing Position the tube so that the arrows point into the air flow 3 Secure the tube flange to the housing bushing with the two 6 self tapping screws 4 For tubes longer than the width of the air d...

Страница 5: ...ibration This vibration can slowly open the seal around the tube and permit air to escape To prevent this from occurring a 3 inch floor flange available at most plumbing supply houses may be used This flange connector mounting technique makes the initial installation easier because a 1 in to 1 1 4 in 25 to 32 mm hole may be drilled where the flange connector will be used It is easier to push the i...

Страница 6: ...CCESSORIES MAY BE USED SUCH THAT THE GIVEN CURRENT LOADS TOTAL AUX POWER TEST STANDBY STATE ALARM STATE 26mA MAX AT 24 VDC 87mA MAX 24 VDC TERMINALS 3 6 20mA MAX 12 VDC ALARM CONTACTS TERMINALS 2 6 NOTE THE SSDRTS451 SSDRTS451KEY RESET CANNOT BE USED ON THE 14506873 001 TEST RESET NOT USED 4 5 6 7 8 9 10 11 12 13 14 15 16 17 COMMUNICATION LINE FROM PANEL COMMUNICATION LINE TO REST OF SYSTEM NOTE F...

Страница 7: ...ust accumulation System filters remove a large percentage of this contami nation but cannot remove all of it Dust inside the duct detector causes problems First very fine particles of dust can enter the detector sensing chamber and cause the unit to go into alarm Second the accumulation of dust and dirt necessitates a more frequent periodic cleaning schedule which can result in substantial cost an...

Страница 8: ...utside of the housing see Figure 7 3 The LEDs on the detector should latch on as should any accessories SSDPA400 SSDRA400Z SSDRTS451 and the alarm condition should be verified at the control panel The control panel must be active for an alarm to be ini tiated A78 2452 00 A78 2453 00 Figure 7 Testing Detector Alarm Figure 8 Detector Head Removal B SSDRTS451 SSDRTS451KEY REMOTE TEST STATION The SSDR...

Страница 9: ...nel should indicate an alarm condition PERIODIC MAINTENANCE REQUIREMENTS Air duct smoke detectors should be maintained at least once a year more often if the detector heads become obviously dirty The detectors must also be cleaned immediately after a fire Failure to properly maintain air duct smoke detectors may cause unnecessary false alarms Honeywell recommends that a permanent Detector Test Log...

Страница 10: ... screens part no SSDRS14 d Brush or vacuum the inside of the cover Cover may then be blown out using clean compressed air e Vacuum sensing chamber before using clean compressed air to loosen and blow out any remaining debris f Press the screen back into the cover g Replace the detector cover on the sensing chamber Rotate it clockwise to lock it into place BOTH TYPES OF UNITS 5 Reinstall the detect...

Страница 11: ...806A1037 or TC806A1052 are used the constraints above do not apply 2 The duct control circuitry auxiliary relay contacts and auxiliary alarm output may change states if the sensor is test ed and the LED is turned on for more than 4 seconds If the LED is latched on for less than 4 seconds the control circuitry of the 14506873 001 will NOT operate 3 The panel must not continuously poll the same unit...

Страница 12: ...__________ ________ __________ ________ ______________ ____________________________ ________ __________ ________ ______________ ____________________________ ________ __________ ________ ______________ ____________________________ ________ __________ ________ ______________ ____________________________ ________ __________ ________ ______________ ____________________________ ________ __________ ____...

Отзывы: