background image

61-86-03-13 

Page 5 

 

 

 

Set Up Group 

Configuration Parameter Selections/Settings 

SET LOCK

 

Enables lock 

out or access to selected 
set up group parameters 
and calibration values.

 

LOCKID – Set Security Password  
LOCK – Lock Out 

 

READ STATUS

 

Displays failsafe condition 
and the results of various 
diagnostics performed 
during power up.

 

FAILSF – Failsafe 
RAMTST – RAM Test Diagnostic 
SEETST – Serial EEPROM Test 
Diagnostic 

CFGTST – Configuration Test Diagnostic 
CALTST – Calibration Test Diagnostic 

SET DRVINF

 

Allows 

access to actuator device 
information.

 

 

VERSON – Firmware Version 
SPEED – Stroke Speed 
POWER – Power Input Voltage and Line 
Frequency 
TAG – Tag Name 

MFGDAT – Manufacturing Date 
LREP – Date of Last Repair 
LCAL – Date of Last Field Calibration 
REPTYP – Repair Type 

SET MAINT

 

Allows 

access to parameters that 
monitor operating 
conditions.

 

TEMP – Actuator Temperature 
TEMPHI – High Temperature Limit 
TEMPLO – Low Temperature Limit 
ACST – Accumulated Motor Stall Time 
STARTS – Accumulated Motor Starts 

RLnCNTS – Relay Cycle Counts 
REGNn – Accumulated Motor Starts 
 

   (Regions of Travel) 

TOTDEG – Total Degrees of Motor Travel 
MANRST – Reset Maintenance Statistics 

 

Specifications – General 

Physical

 

Enclosure 

Precision-machined ductile iron with corrosion resistant paint 

Gear Train 

Precision-machined double reduction worm gear 

Operating Temperature 

-30 °C to +65 °C (-20 °F to +150 °F) 
except Model 11287S which has a range of: -20 °C to +65 °C (-4 °F to +150 °F) 

Storage Temperature 

-40 °C to +93 °C (-40°F to +200 °F) 

Relative Humidity 

0-99% R.H. noncondensing, over the full operating temperature range. 

Crank Arm 

Adjustable radii (8” to 14”) crank arm is standard 

Rotation 

Factory set to 90 degrees, for 0% to 100% travel 

Direction of Rotation 

Field programmable via local display and keypad 

Manual Handwheel 

Provides a means of positioning the actuator in the event of a power failure or set-up 

Lubrication 

Mobil Synthetic bearing and gear lubricant SHC 634 (ISO 460) or equivalent 

Weight 

 300 lb to 600 lb (136 kg to 272 kg)—See Table below for more information. 

Specifications continued on next page 

 

Содержание 11280S

Страница 1: ...o demand signal A double reduction worm gear set combines with a variable speed motor controller inverter that is continuous duty rated for accurate and repeatable positioning of final control elements The worm gear set combination also functions as a brake capable of holding greater than two times the output torque in a back driving condition Control options are available to interface with a modu...

Страница 2: ...ided and is programmable to provide override of all other input signals as an emergency override of control The digital input can be programmed to drive the actuator open closed remain in place or to a user specified position on contact closure Failsafe When input signal exceeds high or low range limits or input signal failure the actuator can be programmed to drive open closed remain in place or ...

Страница 3: ...n can be done through either the local HMI interface If mechanical switches are specified then the user must manually set the auxiliary output DISPLAY MAN AUTO FUNCTION SET UP STALLED ALARM MANUAL AUTO Upper Display Four Characters Lower Display Six Characters LED Status Indicators Control Arm Rotation Indicators CCW CW Pushbuttons to Access Actuator Set Up Status and Calibration Parameters Figure...

Страница 4: ...act closure can be wired to external annunciators or alarm points to indicate conditions for any of the Relay Types RTYPnn Relay Type Input Range Position Range Deviation Upper or Lower Limit Travel Temperature High or Low Motor Starts Motor Stalled Manual Mode Power Up Test Failure Input Signal Failure Position Sensor Signal Failure Digital Input Closure RnnE Relay Count Multiplier RnnVAL Relay V...

Страница 5: ...umulated Motor Stall Time STARTS Accumulated Motor Starts RLnCNTS Relay Cycle Counts REGNn Accumulated Motor Starts Regions of Travel TOTDEG Total Degrees of Motor Travel MANRST Reset Maintenance Statistics Specifications General Physical Enclosure Precision machined ductile iron with corrosion resistant paint Gear Train Precision machined double reduction worm gear Operating Temperature 30 C to 6...

Страница 6: ...al Mains Supply 115 220 Vac single phase 50 60 Hz up to 1500 lb ft 208 200 240 380 480 575 Vac three phase 50 60 Hz Motor Inverter rated continuous duty C face mounting Motor Current Motor Size Full Load Amps FLA Horsepower 230 Vac 460 Vac 1 1 2 3 1 6 2 2 2 6 4 4 5 6 7 8 0 8 1 1 1 3 2 2 2 8 3 9 Loss of Power Stays in place Local Auto Manual Switch Allows local manual and automatic operation of the...

Страница 7: ... and low pass filters Solid State Motor Control CW CCW open collectors opto isolators for use as discrete control inputs to the inverter for motor operation Failsafe operation If input signal exceeds configured input range Selectable and adjustable Feedback signals Output 0 to 20 mA 4 to 20 mA 0 to 5 Vdc 1 to 5 Vdc with 250 ohm resistor 0 to 16 Vdc with 800 ohm resistor Slidewire Emulation Provide...

Страница 8: ... Model Selection Guide Pipe Length Linkage Minimum 24in 61 cm Linkage Maximum 240in 610 cm This rod end supplied on Actuator with crank arm Pipe length Overall linkage length minus 20 inches 51 cm Figure 4 Pipe Linkage Kit Actuator Crank Arm The 11280S Series Actuator comes standard with an 8 to 14 adjustable radius crank arm The crank arm uses a standard right hand thread 1 rod end to compliment ...

Страница 9: ... for the transformer enclosure 575 Vac 3 Phase For customer applications requiring 575 460 Vac 3 phase operation a step down transformer is mounted in a separate enclosure Model Selection Guide Table I option 6 Figure 6 shows the installation for the transformer enclosure 10 0 254 mm 14 0 355 6 mm 16 0 406 4 mm Ground Stud 120 240 Vac Single Phase Transformer 575 460 Vac Three Phase Transformer Fi...

Страница 10: ...SUPPLY Single Phase 120 Vac 50 60 Hz a 240 Vac 60 Hz 200 Vac 50 Hz a Three Phase 200 240 Vac 60 Hz 380 480 Vac 50 60 Hz 575 Vac 60 Hz TABLE II STROKE SPEED Stroke Speed 60 Hz 10 sec 90 degrees 30 sec 90 degrees 60 sec 90 degrees TABLE III MOTOR ORIENTATION See specification 61 86 03 13 for diagrams Motor Right hand floor configuration H W Shaft Horizontal Orientation Left hand floor configuration ...

Страница 11: ...adii Standard 0_ _ _ _ _ None 1_ _ _ _ _ Linkage Kit None _0_ _ _ _ Up to 20 ft length customer supplies schedule 40 pipe _1_ _ _ _ Future Option None _ _0_ _ _ Future Option None _ _ _0_ _ Tagging None _ _ _ _0_ Linen Note 3 _ _ _ _1_ Stainless Steel Note 3 _ _ _ _2_ Future Option None _ _ _ _ _0 TABLE IX FACTORY OPTIONS Motor Orientation None 00 RESTRICTIONS Restriction Available Only With Not A...

Страница 12: ...61 86 03 13 Page 12 Figure 7 Mounting and Outline Dimensions for 11284S 11285S 11286S 11288S and 11289S Weather Proofed Motor Actuators Right Hand Floor Mounting Handwheel Shaft Horizontal D MTG 616 200 ...

Страница 13: ...61 86 03 13 Page 13 Figure 8 Mounting and Outline Dimensions for 11284S 11285S 11286S 11288S and 11289S Weather Proofed Motor Actuators Left Hand Floor Mounting Handwheel Shaft Horizontal D MTG 616 210 ...

Страница 14: ...arranties expressed or implied including those of merchantability and fitness for a particular purpose Specifications may change without notice The information we supply is believed to be accurate and reliable as of this printing However we assume no responsibility for its use Honeywell 2004 While we provide application assistance personally through our literature and the Honeywell web site it is ...

Отзывы: