GB-28
FAQ LIST
1
Question
:
If several JRMs are used within one system, can the central UP/DOWN function be activated jointly (parallel)?
Answer
:
The central UP/DOWN function may not be connected in parallel. A potential-free relay must be used.
2
Question
:
How can I operate more than one JRM with the one sensor?
Answer
:
Sensors can be used for more than one JRM via the compact bus (see page 24).
3
Question
:
Can more than 12 motors be connected to the 952 JRM?
Answer
:
Yes, for example with the help of the 409 SR multiple control relay.
4
Question
:
How can I prevent the shutter on the terrace door from closing whilst we are sitting outside?
Answer
:
The motor’s auto mode can be switched ON and OFF at a switch on input I32. The affected motor must be assigned to input I32 in the
AUTO device menu. Auto mode extends to the twilight sensor, sun sensor, and timer.
Caution
:
Timer commands are not repeated.
5
Question
:
Do the 0V terminals on the inputs have to be wired in a star pattern or can they be connected in parallel?
Answer
:
The 0V terminal that is closest to an input should always be used. Parallel connection is also permitted. Observe the length and dia
-
meter of the wires (approx. 400 m when d= 0.8 mm)!
6
Question
:
How are the outputs (relays) protected, or are internal fuses fitted upstream of the relays?
Answer
:
The connecting cables for supplying power to the outputs (L0-L3) must be protected with a 10 A automatic circuit breaker.
Make sure the loads and the power consumption (230 V~ /50 Hz /1A) are evenly distributed!
Содержание 00299517
Страница 2: ......
Страница 3: ...PEHA Elektro GmbH Co KG Compact 952 JRM Bedienungsanleitung D ...
Страница 34: ......
Страница 35: ...PEHA Elektro GmbH Co KG Compact 952 JRM Operating instruction GB ...
Страница 66: ......
Страница 67: ...PEHA Elektro GmbH Co KG Compact 952 JRM Bedieningshandleiding NL ...
Страница 98: ......
Страница 99: ...PEHA Elektro GmbH Co KG Compact 952 JRM Mode d emploi F ...
Страница 130: ......
Страница 131: ......