TESTING 

Test communications between the detector and the control panel.  The 

detector mode has two test buttons; one for smoke testing and one for 

CO testing. 

 

The detector may also be functionally tested using canned smoke and 

canned CO.  If the detector fails any of the test methods, the detector 

should be replaced. 

NOTE:

 Testing the detector will activate the alarm and send a signal to the 

panel. 

Before testing, notify the proper authorities to avoid any 

false alarms.  

Smoke Test (Alarm Test) 

Press and hold the Smoke Test button for 1 to 2 seconds. The 

detector will sound and illuminate per Table 2 and send a smoke alarm 

signal to the control panel (all programmed smoke detector loops are 

signaled). Verify that the smoke alarm signal was received at the 

control panel.  

Smoke System Test (Functional Smoke Test) 

CANNED SMOKE NOTE: 

Detector sounds an alarm when using 

canned smoke 

ONLY

 when in Functional Test mode (canned smoke 

does not cause alarm sounding when in normal mode.) 
Press and hold the Smoke Test button for 3 to 5 seconds to enter the 

functional smoke test mode. 

See Functional Smoke Test section below.

 

Functional Smoke Test 

With the detector in smoke system (functional) test mode, spray 

canned smoke into the detector. The canned smoke that can be used 

and is approved for test include: Home Safeguard Industries 25S, SDi 

CHEK02 and CHEK06, SDi SOLOA4, and SDi SMOKESABRE. 

1. 

The detector will sound and illuminate per Table 2 and a smoke 

alarm signal will be sent to the panel.   

2. 

Verify the smoke alarm signal was received by the control panel. 

CO Test (Alarm Test) 

Press and hold the CO Test button for 1 to 2 seconds. The control 

panel should display and sound a CO alarm (all programmed CO 

detector loops are sent). 

CO System Test (Functional CO Test) 

CANNED CO NOTE: 

Detector sounds an alarm when using canned 

CO 

ONLY

 when in Functional Test mode (canned CO does not 

cause alarm sounding when in normal mode.) 
Press and hold the CO Test button for 3-5 seconds to enter the 

functional gas test mode. 

See Functional Gas Test section below.  

 

Functional Gas Test 

Solo C6 brand canned CO may be used to verify the detector’s ability to 

sense CO by utilizing the RealTest® feature as follows: 
1.  Press and hold the CO test button for 3 to 5 seconds. The green 

LED will start blinking once per second indicating the detector is in 

RealTest® mode. (If the detector will not go into RealTest® mode, 

the CO sensor may be in fault or at end-of-life.) 

2.  While the green LED is blinking once per second, spray a small 

amount of canned CO directly into the CO gas entry port.  

3.  Upon successful gas entry and if functioning properly, the detector 

will go into CO alarm and send an alarm to the control panel. 

4.  The CO test will automatically clear when the CO clears from the 

sensor or in 30 seconds if no CO was introduced. 

 

HUSH FEATURE / ALARM SILENCE

 

If required, the audible alarm for smoke and CO conditions can be 

silenced for 5 minutes by pushing the “Test/Hush” button. In addition, 

low battery chirping can be silenced for 12 hours when the Test/Hush 

button is pressed.  

During a Smoke alarm, if an alarm condition still exists after the 5-

minute hush period, the alarm will sound.  The hush feature will not 

operate at levels above 4%/ft. smoke concentration. 

During a CO alarm, if carbon monoxide is still present after the 5-minute 

hush period, the alarm will sound. The hush feature will not operate at 

levels above 350 ppm (parts per million) carbon monoxide. 

CO SENSOR END-OF-LIFE FEATURE 

When the CO sensor has passed end-of-life, a trouble signal will be 

sent to the control panel (if programmed). This indicates that the CO 

sensor inside the detector must be replaced. If unresolved for 30 days, 

the detector will chirp every 45 seconds. The typical life of the CO 

sensor is ten years from the date of manufacture. It is recommended to 

periodically check the “Replace by” date located on the label on the 

back of the detector head. 

 

 

 

 

 

 

 

 

Table 3: Carbon Monoxide Detector: Events & 

Contact ID Codes

 

Event 

Panel Display 

CS Report 

Alarms 

CO Alarm 

CO alarm (CID 162) 

Test 

CO Alarm 

CO alarm (CID 162) 

Low Battery 

Lo Bat 

RF low-battery  

(CID 384) 

Detector 

Supervision 

CO Supervision 

Loss of RF Supervision 

(CID 381) 

Detector end-

of-life/trouble 

Low 

Maintenance 

Sensor trouble - (CID 

386) Low Maintenance 

Tamper 

Disarmed or Armed 

= Tamper 

RF sensor tamper  

(CID 383)

  

 

 

Table 4: Smoke and Heat Detector: Events &  

Contact ID Codes

 

Event 

Panel Display 

CS Report 

Alarms 

Fire Alarm 

Fire Alarm (CID 110) 

Test 

Fire Alarm 

Fire Alarm (CID 110) 

Low Battery 

Lo Bat 

RF low-battery  

(CID 384) 

Detector 

Supervision 

Smoke or Heat 

Supervision 

Loss of RF Supervision 

(CID 381) 

Detector 

Maintenance 

(Needs 

cleaning) 

Maintenance 

Smoke 

Smoke Detector  

High Sensitivity 

(CID 385) 

Tamper 

Disarmed or Armed 

= Tamper 

RF sensor tamper  

(CID 383)

  

 

Table 2: LED Indication & Sounder during Test and Trouble 

MODE 

Status LED 

(Top) 

Side LED 

Windows  Sounder 

Speaker 

Smoke Test 

Blink Green 

once every 

second 

Dark 

Temp-3 

Warning of 

alarm signal  

transmission.  

Voice smoke 

warning 

Functional SMOKE  

Test – 

Waiting for 

canned smoke 

entry 

 

Blink Green 

once a sec  

Dark 

Silent 

Voice 

instructions 

and warning of 

alarm signal 

Functional 

SMOKE Test  - 

Successful smoke 

entry

 

Blink Red 

every 10 secs 

Blink Red 

every 10 

secs 

Temp-3  

No voice 

announcment

 

RealTest™ 

Functional CO  gas 

entry test – 

Waiting 

for gas entry 

Blink Green 

once per 

second 

Dark 

Silent 

No voice 

announcment 

RealTest™ 

Functional CO  gas 

entry test  -

Upon 

successful gas 

entry

 

Blink Red 

once every  

10 secs 

Blink blue 

every  

10 secs 

Modified 

Temp-4 

Voice carbon 

monoxide 

warning 

Low Battery 

Blink Amber 

every 10 secs 

Dark 

Chirp 

every 45 

secs 

after 7 

days 

Voice instruc-

tions when chirp 

is silenced by 

pressing either 

test button 

Smoke 

Maintenance 

Blink Amber 

every 5 secs 

Dark 

Silent 

Voice smoke 

maintenance 

instructions if 

either test 

button is 

pressed 

CO Trouble 

Double Blink  

Amber  every 

5 secs 

Dark 

Silent 

Silent 

CO End of Life – 

First 29 days

 

Double Blink 

Amber  every 

3 secs 

Dark 

Silent 

Voice end-of- 

life instructions 

when either test 

button is 

pressed

 

CO End of Life – 

after 30 days

 

Double Blink 

Amber every 3 

secs 

Dark 

Chirp 

every 45 

secs 

Voice end-of-life 

instructions 

when either test 

button is 

pressed

 

Power Up 

Blink Green, 

for 30 secs  

Dark 

Silent 

Language set 

instructions only 

on first time 

power-up 

Normal (Standby) 

Single Blink 

Green every 

10 secs 

Dark 

Silent 

Silent 

 

 

 

Содержание SiXCOMBO

Страница 1: ...rollment process 4 The device attempts enrollment green LED flashes about 8 seconds If successful the green LED lights steady for 3 seconds and the device announces successful enrollment If the LED does not light steady enrollment failed Retry by pressing either Test switch for less than 3 seconds All services Smoke Heat and CO are automatically enrolled in sequential or next available zone number...

Страница 2: ...ing a Smoke alarm if an alarm condition still exists after the 5 minute hush period the alarm will sound The hush feature will not operate at levels above 4 ft smoke concentration During a CO alarm if carbon monoxide is still present after the 5 minute hush period the alarm will sound The hush feature will not operate at levels above 350 ppm parts per million carbon monoxide CO SENSOR END OF LIFE ...

Страница 3: ...possible to detect with the human senses Under normal conditions in a room where fuel burning appliances are well maintained and correctly ventilated the amount of carbon monoxide released into the room by appliances should not be dangerous CAUTIONS This device will only indicate the presence of carbon monoxide gas at the sensor Carbon monoxide gas may be present in other areas This device is desi...

Страница 4: ...rme NMB 003 du Canada FCC IC STATEMENT This device complies with Part 15 of the FCC Rules and Industry Canada s license exempt RSSs Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation Cet appareil est conforme à la partie 15 des règles ...

Отзывы: