1
SiXCOMBO
Combination Smoke/Carbon Monoxide (CO) Detector w/Built-in Wireless
Transmitter
(features voice and 360 degree viewable LED ring)
Installation and Setup Guide
This device is intended for use with Honeywell Home control panels that support SiX series devices.
Before installing detectors, please thoroughly read these installation instructions and read the
Limitations of Fire Alarm Systems
Insert (P/N 800-15144 5/13) and
System Smoke Detectors
Application Guide
(P/N SPAG9101 7/12).
FEATURES
•
Multi-Criteria Sensing:
uses four
sensing elements to react faster
while minimizing false alarms:
-
Photoelectric smoke sensor
detects airborne smoke
particles
-
Carbon Monoxide (CO) sensor
detects smoldering fires
-
Infrared (IR) sensor measures
ambient light and flame
signatures, such as flame
flicker
-
Heat detection monitors for
dangerous rise in temperature
•
One Go / All Go: all smoke
detectors in the system
programmed as one-go-all-
go will sound on alarm.
•
CO Detector End-of-Life
reporting (detector needs
replacing)
•
Smoke detector maintenance
reporting (detector needs
cleaning)
•
Low Battery Detection
Table 1: Operation Modes
MODE
Status LED
(Top)
LED Windows
(Side)
Sounder
Speaker
Power Up Blink Green,
every 2 secs
Dark
Silent
Voice welcome,
instructions after first
time power up or
after default
Normal
(Standby)
Single Blink
Green every
10 secs
Dark
Silent
Silent
Smoke
Alarm
Blink Red
every 10 secs
Blink red
Temp-3
Voice smoke
warning
Heat
Alarm
Blink Red
every 10 secs
Blink red
Temp-3
Voice smoke
warning
CO Alarm
Blink Red
every 10 secs
Blink blue
Temp-4
Voice CO
warning
Powered
Down
Dark
Dark
Silent
Silent
ENROLLMENT
The SiXCOMBO has a unique MAC ID number.
The heat, smoke, and CO are assigned to loops 1-
3 respectively and are enrolled in separate zones.
NOTE:
Once enrolled, the device cannot be used
with another system until it is removed from
the current controller. See the 24-hour
Enrollment Deletion section below or the
controller’s instructions.
Enroll the Device Services (Smoke, Heat, CO)
1. Remove the detector from the base plate.
2. Put the control panel in Programming mode.
3. Pull the battery tab to activate enrollment
process (be sure batteries are seated properly to
avoid a false low battery condition). If the battery
tab has already been removed and the unit is
powered up, press either Test switch for less
than 3 seconds to activate the enrollment
process.
4. The device attempts enrollment (green LED flashes about 8 seconds). If
successful, the green LED lights steady for 3 seconds and the device
announces successful enrollment.
If the LED does not light steady, enrollment failed. Retry by pressing either
Test switch for less than 3 seconds.
All services (Smoke, Heat, and CO) are automatically enrolled in sequential
(or next available) zone numbers with the following default attributes:
Zone
Device Type
Zone Response Type
Smoke Det. Smoke Detector
Fire No Verification
Heat Det.
Heat Sensor
Fire No Verification
CO Det.
Carbon Mono. Det.
Carbon Monoxide
NOTE
: Maintenance and CO End-of-Life are automatically enrolled for
the respective smoke and CO zones. Contact ID code E386 “Low
Maintenance Smoke” is sent for the CO zone at End-of-Life and Contact ID
code E385 “High Maintenance Smoke” is sent for the Smoke Zone when
dirty.
Supervision
: Detector supervision is factory set for 1 minute and is not
programmable.
24-Hour Enrollment Deletion
Use this procedure within 24 hours of initial enrollment to delete
this device from the controller. This allows reenrollment in a
specific controller in case enrollment in that controller failed. This
resets the device to factory default settings and removes the
communication link data in the controller in which it is enrolled.
1. Press and hold both the Smoke and CO test switches
simultaneously until the welcome message announces, then
release.
2. Wait for the green LED to flash rapidly.
3. Press and hold both switches again for one second and
release.
4. LED blinks rapidly after 15 seconds, confirming deletion.
LANGUAGE SELECTION
1. Press and hold both the Smoke and CO test switches
simultaneously for 5 seconds until Welcome message is
announced, then release. The green light flashes rapidly.
2. Press the Test button corresponding to the desired language:
English: Press the Smoke (•) test button
Spanish: Press the CO (••) test button
MOUNTING
After enrolling, verify adequate signal strength with
the device in its intended mounting location. Adjust
the device location and orientation as necessary.
1. Using two supplied screws and anchors, mount
the base.
2. Attach the smoke detector to the mounting base
with a clockwise motion.
3.Test each detector as described in the Testing
section.
4. Confirm all desired signals have been received
by the Central Station.
NOTE:
NFPA 72 recommends the installation of
detectors only after completing construction or
any other dust producing activity.
NOTE:
This device should not be located within 5
ft. (1.5 m) of any cooking appliance.